Setting the address DIP switch

Each addressable TrueAlert ES notification appliance has a unique address that is set with an eight-position DIP switch (ADDR1). Assign up to 127

unique addresses to an SLC, however, the total appliance loading available may be less due to appliance current requirements.

To set the address, complete the following steps:
1.

Locate the 8-position DIP switch on the bottom left front of the appliance, see Figure 3.

You must set the DIP switch before you snap on the cover.

2.

Set the switches using a non-metallic stylus, or the equivalent.

3.

Record the set address.

4.

Confirm the setting for the appliance at this address with the Fire Alarm Control Panel (FACP) system configuration documentation.

DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type appliance.

Figure 3: Setting the DIP switch address

Setting the appliance configuration

You can configure certain options for the horn and strobe directly on the appliance using the appliance configuration switch (CFIG1) located on the

front of the appliance, see Figure 4.

A/O only:
Position 1:

 Configuration Control - OFF to enable Local Audible control,

ON for panel control.

Position 2:

 Audible Volume - High (OFF), Low (ON).

Position 3:

 Not used.

Figure 4: Setting the strobe and appliance configuration

page 3

579-1200AC  Rev. E

TrueAlert ES Addressable Indoor Audible Notification Appliance installation instructions

Содержание TrueAlert ES A59AOC-WRF

Страница 1: ...c requirements of the local Authority Having Jurisdiction AHJ These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification reference Table 1 Product identification reference Type Colors Models Wall Mount Audible Only A O Red White Components A59AO APPLWR A59AO A...

Страница 2: ...he field wiring diagrams for the driving compatible fire alarm control panel for further instructions b Notification appliances are rated using an individual module label c Maintain the correct polarity on the terminal connections d Terminals and can each accommodate 2 wires one wire going in and one wire going out to the next appliance e These appliances are rated to the operating voltage limits ...

Страница 3: ...e appliance at this address with the Fire Alarm Control Panel FACP system configuration documentation DIP switch position 8 determines whether this appliance is viewed by the system as an ALARM OFF or ALERT ON type appliance Figure 3 Setting the DIP switch address Setting the appliance configuration You can configure certain options for the horn and strobe directly on the appliance using the appli...

Страница 4: ...lume settings are configured with DIP Switch CFIG1 See Figure 4 4 If you install the A4905 9838 Sound Damper the anechoic measurements decrease by approximately 9 dBA Table 4 ULC directional characteristics for horn Axis Angle dBA 50 left and right 3dBA Horizontal 63 left and right 6dBA 20 above 48 below 3dBA Vertical 65 above 60 below 6dBA CAUTION The appliances are available in red and white Do ...

Отзывы: