Autocall A49SVH-APPLC-O Скачать руководство пользователя страница 2

page 2

579-1241AC Rev A

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation

Instructions

Mounting instructions

1.

Select the mounting location and install the back box using screws suitable for the mounting surface.

2.

Connect the building wires to the terminals at the back of the appliance, see the wiring section.

3.

Secure the appliance to the back box using the provided hardware.

4.

Set the appliance settings. See 

Setting the address DIP switch

.

5.

Attach the cover to the appliance. For the A49SO, align the cover mounting tab with the tab in the backbox, and carefully place the cover onto

the unit. For the A49SVH, align the cover mounting tab with the strobe dome, and carefully place the cover over the unit.

6.

Press the cover until it snaps into place.

Cover

SO Appliance

Weather proof back box

Cover

S/V Appliance

Weather proof back box

Screws #8-16 x 1.25 inch

Screws #8-16 x 1.25 inch

Figure 3: Mounting instructions

Wiring instructions

Warning: 

Make sure that all power is disconnected before starting the installation.

1.

At the back box, connect the building wiring to the CKT + and CKT - terminals on the appliance.

2.

To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.

3.

Ensure that the correct polarity is maintained for each strobe unit.

4.

SLC wiring must be twisted pair (TWP). CKT Terminals accept 2 Wires: 12-18 American wire gauge (AWG) TWP .

Important: 

Strip the lead insulation to 7/16 inch maximum.

Содержание A49SVH-APPLC-O

Страница 1: ...locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification reference Table 1 Product Identification Reference Type Cover colors Models Operation Figure 1 Ceiling Mount Speaker Visible S V with cover Red White Components A49SVH APPLC O A49SVH APPLC O Covers A49SVC CRALT O A49SVC CRFIRE O A49SVC CRS O A49SVC CRBC O A49SVC CWBC O A49SVC CWFIR...

Страница 2: ...or the A49SVH align the cover mounting tab with the strobe dome and carefully place the cover over the unit 6 Press the cover until it snaps into place Cover SO Appliance Weather proof back box Cover S V Appliance Weather proof back box Screws 8 16 x 1 25 inch Screws 8 16 x 1 25 inch Figure 3 Mounting instructions Wiring instructions Warning Make sure that all power is disconnected before starting...

Страница 3: ...an individual module label 3 Maintain the correct polarity on the terminal connections 4 Terminals 1 through 6 each accommodate two wires one wire going in and one wire going out to the next appliance 5 These appliances are rated to the operating voltage limits of 23 30 VDC The appliance can fail to operate as intended and can cause permanent damage to this equipment if it operates outside of thes...

Страница 4: ...address Setting the strobe candela setting 1 The jumpers are factory set to FACP Use this setting when programming the candela setting at the 4100ES FACP The candela setting is visible through the slot on the side of the appliance 2 For manual selection remove the cover and slide the candela flag to the required setting W75 W110 W185 110 candela or FACP The candela setting is visible through the s...

Страница 5: ...erature rating for indoor and uncontrolled wet Public Mode 110 CD 0 F to 120 F 0 C to 49 C FM temperature rating 40 F to 120 F 40 C to 50 C UL ULC humidity range 95 non condensing at 60 F 60 C Connections Terminal for 18 AWG to 12 AWG 0 82 mm 2 to 3 31 mm 2 CAUTION The appliance covers and backboxes are available in red and white Do not paint or otherwise alter the factory finishes in any way Tabl...

Страница 6: ...0 103 60 40 111 65 35 98 65 35 120 70 35 87 70 35 103 75 30 90 75 30 75 80 30 96 80 30 83 85 25 96 85 25 70 90 25 83 90 25 47 Table 6 TrueAlert Addressable Ceiling Mount S V and SO Units speaker switch setting and output ratings 25 V or 70 V audio Tap Settings in Watts UL reverberant at 10 ft ULC anechoic at 3 m 1 4 80 82 1 2 83 85 1 86 88 25 V 2 88 90 1 4 78 80 1 2 82 84 1 85 87 70 7 V 2 88 90 No...

Отзывы: