AURORA UPC ZS ZONE SENSORS INSTALLATION GUIDE
If display shows...
Then...
The sensor is not communicating with the network. Check:
x
Software/addressing setup
x
Wiring connections
x
Controller operating status
Characters that
seem out
of place
The sensor may have a memory problem. Try formatting the sensor.
Effective setpoints
fields
These fields display the effective setpoint values. They can display a maximum value of
99 or 99.5 if the
Edit Increment
is set to 0.5. If the effective setpoint exceeds this
maximum value or if the
Edit Increment
is set to 0.1, the value will flash.
TTIP
If you need an Edit Increment of 0.1, put the effective setpoints on the
Information screen in the Primary Value field. Hide the effective setpoints on the Home
screen by selecting
Sensor Setpoint Adjust Option 4
on the
BACnet Setpoint
microblock's
Rnet
tab.
Specifications for ZS zone sensors
ZS zone sensors