Aurora UPC ZS ZONE SENSOR Скачать руководство пользователя страница 14

14

AURORA UPC ZS ZONE SENSORS INSTALLATION GUIDE

If display shows...

 

Then...

 

 

The sensor is not communicating with the network. Check: 

x

Software/addressing setup 

x

Wiring connections 

x

Controller operating status 

Characters that  

seem out  
of place 

The sensor may have a memory problem. Try formatting the sensor. 

Effective setpoints 

fields 

These fields display the effective setpoint values. They can display a maximum value of 

99 or 99.5 if the 

Edit Increment

 is set to 0.5. If the effective setpoint exceeds this 

maximum value or if the 

Edit Increment 

is set to 0.1, the value will flash.  

 TTIP

  If you need an Edit Increment of 0.1, put the effective setpoints on the 

Information screen in the Primary Value field. Hide the effective setpoints on the Home 
screen by selecting 

Sensor Setpoint Adjust Option 4 

on the 

BACnet Setpoint

 microblock's 

Rnet

 tab. 

 

 

Specifications for ZS zone sensors 

ZS zone sensors 

Содержание UPC ZS ZONE SENSOR

Страница 1: ...Aurora UPC ZS Zone Sensors Installation Guide Aurora Universal Protocol Converter UPC ZS Zone Sensors Installation Guide IG1582EW 06 18...

Страница 2: ......

Страница 3: ...pecifications Power requirements ZS zone sensors 8 Specifications for ZS zone sensors CO2 sensor installation Motion sensor installation To address a ZS zone sensor To wire and mount a ZS zone sensor...

Страница 4: ...x OEMPrtl Pro The following table shows the ZS Sensor models their features and the available configurations Zone Sensors Features Available configurations Part number ZS Standard x Local access port...

Страница 5: ...midity Temp and CO2 Temp humidity and CO2 Temp and motion Temp humidity and motion Temp CO2 and motion Temp humidity CO2 and motion ZS2P ZS2P H ZS2P C ZS2P HC ZS2P M ZS2P HM ZS2P CM ZS2P HCM x Green L...

Страница 6: ...troller s Rnet depends on how many control programs it can have If the controller supports x Only one control program the Rnet can consist of x Up to 5 ZS sensors x One Wireless Adapter supporting up...

Страница 7: ...r maximum signal integrity Description 4 conductor shielded or unshielded CMP plenum rated cable Conductor 22 AWG 7x0096 bare copper Maximum length 500 feet 152 meters Insulation Low smoke PVC or equi...

Страница 8: ...ION GUIDE Power requirements See the sensor specifications for power requirements and power supply information CAUTION Do not share power between controller s power and external 12 Vdc unless both dev...

Страница 9: ...0 C 0 36 F 0 2 C Temperature if humidity is included 50 to 104 F 10 to 40 C 0 54 F 0 3 C Humidity 10 to 90 1 8 typical Less than 0 5 drift per year CO2 400 to 1250 PPM 30 PPM or 3 of reading whichever...

Страница 10: ...dle to 190 mA CO2 measurement cycle A ZS Pro with motion sensor has the same power requirements as a ZS Pro without a motion sensor Power supply The 4 conductor Rnet cable from a controller supplies 1...

Страница 11: ...nsor on a ZS Pro needs to have a direct line of sight to the occupants in the room If the size of the room exceeds the maximum detector range use multiple sensors to adequately monitor the area Avoid...

Страница 12: ...l the Rnet communication cable through the wire guide in the backplate 3 30 in 8 38 cm 5 Use 2 screws to mount the backplate to the wall or outlet box Partially cut then bend and pull off the outer ja...

Страница 13: ...ield shield wire or a metal surface other than the terminal block the device may not communicate correctly 9 Attach the sensor s cover and circuit board to the mounted backplate inserting the top firs...

Страница 14: ...splay the effective setpoint values They can display a maximum value of 99 or 99 5 if the Edit Increment is set to 0 5 If the effective setpoint exceeds this maximum value or if the Edit Increment is...

Страница 15: ...from the sensor b Note the current position of the DIP switches c Set all DIP switches to the ON position d Reattach the wiring connector to format e After approximately 3 seconds remove the wiring c...

Страница 16: ...icy of continual product research and development and reserves the right to change design and specifications without notice Product Aurora UPC ZS Zone Sensors Document Type Installation Guide Part Num...

Отзывы: