4.1.3) Connecting the C.H. pump
Connect the pump to the
OUT2
terminals on the controller
(L, , N). Connect the green or yellow-green conductor to
the terminal “ ” (protective earth or protective earth and
neutral), connect the blue conductor to the “
N
” terminal,
and the brown one to the terminal “
L
”.
4.1.4)
Connecting the valve
Connect the pump to the
OUT3
2 terminals on the
controller (L, , N). Connect the green or yellow-green
conductor to the terminal “¤” (protective earth or protective
earth and neutral), connect the blue conductor to the “
N
”
terminal, and the brown one to the terminal “
L
”.
4.1.5) Connecting the power supply to the controller
When the conductors are secured against accidental
breaking, connect the power cable to the
IN
terminals (L, ,
N). Then plug into a 230 VAC/50 Hz socket with an
earthing pin.
NOTE
: the ambient temperature in the controller location
o
should not exceed 40 C
4.2 Operation of the controller
4.2.1) Starting the controlle
Put the switch in position “I”. All display segments will
light up for about 2 seconds. Then, the display will show
the current temperature on the sensor.
4.2.2) Settings range
The temperature (from 0oC do 99oC) is measured by the
SR2 sensor. The C.H. pump is controlled by means of the
OUT 2 output. The three-way valve or the other C.H. pump
are controlled by means of the OUT 3 output. The settings
range for the C.H. pumps and the three-way valve (or the
other C.H. pump) is 10oC do 90oC, the hysteresis
(temperature difference between the activation and
deactivation) is 4oC.
4.2.3) Changing the temperature settings
Press the “
B
” button below the temperature settings - the
temperature setting indicator for the fireplace heating
system will start to blink. Then, use the “
+
” (increase) or “
-
“
(decrease) buttons to set the required temperature.
AURATON 1111 Multi
9