Operation instructions
AUMA valve actuators SV 05.1 – SV 07.1
6. Electrical
connection
Work on the electrical system or equipment must only be carried out
by a skilled electrician himself or by specially instructed personnel
under the control and supervision of such an electrician and in
accordance with the applicable electrical engineering rules.
AUMA valve actuators SV 05.1 – SV 07.1 are operated via the controls MEC 02.1.
These are designed to be mounted to a separate wall bracket.
Suitable flexible and screened cables must be used between controls and actuator.
The max. permissible cable length between actuator and controls is 50 m.
Controls
Actuator
Pins
Pins
Pins
XA
1
XG4
XG
3
XG
2
XG1
Su
pp
ly
(m
ai
ns
)
XA
2
Sockets
Sockets
Sockets
16
3
16
4
Co
ntr
o
ls
Si
gn
al
s
Ac
tu
at
o
r
Co
ntr
o
ls
Ac
tu
at
o
r
Outp.
Outp.
In
p
.
In
p
.
Figure B1: Electrical connection
The mains connection and the connection between actuator and controls MEC 02.1
is made by two plug/socket connectors each, with crimp technology.
For crimping a suitable tool, e.g. the Cannon four indent crimp tool, must be used.
Cross sectional areas: Mains/motor: max. 1.5 mm²
Control cables: max. 1.5 mm²
Figure B2: Connection controls (socket carrier)
Figure B3: Connection mains/motor (socket carrier)
Plug/socket connector XG2; XA2
Plug/socket connector XG1; XA1
17 contacts (pole diagram figure B2)
5 contacts (pole diagram see figure B3)
Plug/ socket connector XG4
Plug/socket connector XG3
17 contacts (pole diagram figure B2 mirror image)
5 contacts (pole diagram see figure B3 mirror image)
7