2.
Operate actuator using push buttons OPEN - STOP - CLOSE.
➥
The limit switching is set correctly if (default indication):
-
the yellow indication light is illuminated in end position CLOSED
-
the green indication light is illuminated in end position OPEN
-
the indication lights go out after travelling into the opposite direction.
➥
The limit switching is set incorrectly if:
-
the actuator comes to a standstill before reaching the end position
-
the red indication light is illuminated (torque fault).
3.
If the end position setting is incorrect: Reset limit switching.
4.
If the end position setting is correct and no options (e.g. potentiometer, position
transmitter) are available: Close switch compartment.
9.6.3
PTC tripping device (option): test
1.
Turn selector switch to position Test (spring return).
➥
If the PTC tripping device is working properly, the tripping of the motor protection
is signalled via the red indication light "collective fault signal" on the local con-
trols.
2.
Turn selector switch to position Reset.
➥
The fault signal is reset if the device is working properly.
3.
If no fault signal is initiated: Request AUMA service to check both wiring and
selector switch.
9.7
Potentiometer setting
— Option —
The potentiometer as travel sensor records the valve position.
Information
This setting is only required if the potentiometer is directly wired to the customer
connection XK (refer to wiring diagram).
Information
Due to the ratio of the reduction gearing the complete resistance range/stroke is not
always passed. Therefore, external adjustment (setting potentiometer) must be pro-
vided.
Figure 46:
View of control unit
[1]
Potentiometer
1.
Move valve to end position CLOSED.
37
SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
AMExB 01.1
Commissioning (basic settings)