Service conditions
IP67
Standard:
Enclosure protection in accordance
with IEC 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Continuous immersion in water: maximal 96 hours
●
Up to 10 operations during immersion
●
Modulating duty is not possible during immersion
Option:
Pollution degree 4 (when closed), pollution degree 2 (internal)
Pollution degree according to
IEC 60664-1
2 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
Test proof for application class 3
Seismic resistance according to
IEC 60068-3-3
KS
Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:
Corrosion protection
KX (upon request)
Suitable for use in areas with extremely high salinity, permanent condensation, and high
pollution.
Option:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Available colours on request
Option:
During operation, accelerating loads up to 15 % of the max. torque may occur.
Driving load
10,000 operating cycles OPEN - CLOSE - OPEN
One operation cycle consists of 25 turns in both directions (OPEN - CLOSE - OPEN)
Open-close
duty:
Lifetime
1.8 million modulating steps
Modulating
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve
the modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the
number of starts per hour chosen should be as low as permissible for the process.
< 70 db (A)
Sound pressure level
Further information
ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
EU Directives
Dimensions PF-M25X – PF-M100X
Electrical data PF-M25X – PF-M100X
Reference documents
48
PF-M25X – PF-M100X
Technical data
Parallel
Содержание PROFOX PF-M100X
Страница 9: ...3 Name plate Figure 4 Name plate arrangement 9 PF M25X PF M100X Parallel Name plate ...
Страница 49: ...15 Spare parts 15 1 Multi turn actuators PF M25 PF M100 49 PF M25X PF M100X Parallel Spare parts ...
Страница 51: ...51 PF M25X PF M100X Parallel ...
Страница 52: ...52 PF M25X PF M100X Parallel ...
Страница 55: ...55 AUMA worldwide ...