INSTRUCTIONS
Register Description
Bits
Details
40006
Motor
temperature
0 to 7
Motor thermal model (%)
8 to 15
Reserved
40007
Reserved
40008
Reserved
40009
~
40200
Parameter
management
(single or
multiple
0 to 7
Manage soft starter programmable parameters.
Refer to the relevant soft starter literature for a
complete parameter list.
read/write)
8 to 15
Reserved
40600
Version
0 to 5
Binary protocol version
6 to 8
Parameter list version number
9 to 15
Product type code:
12 = EMX4e
13 = EMX4i
40601
Model number 0 to 7
Reserved
8 to 15
Soft starter model ID
40602
Changed
parameter
number
0 to 7
0 = No parameters have changed
1~255 = Index number of the last parameter
changed
8 to 15
Total number of parameters available in the
starter
40603
Changed
parameter value
0 to 15
Value of the last parameter that was changed,
as indicated in register 40602
40604
Starter state
0 to 4
0 =
Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay, restart temperature
check, run simulation, reset input is open)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Unintialised
1 = Initialised
7
Command source
0 = Remote Keypad, Digital Inputs, Clock
1 = Network
10
Modbus RTU Card (710-16499-00B)