AVOIDING DAMAGE
Page 8
CSX Series
710-02696-00C
1 Soft starter output relay
2 Slave relay coil
3 Contactor coil
2.
If the contactor has a volt free electronic input (low voltage/low current), the soft starter's output relay can be
wired directly into this input for contactor control.
1 Soft starter output relay
2 Contactor coil
3.3
Control Inputs
CSX Series soft starters can be operated by external two wire or three wire control signals. External switches are
configured and wired into control input terminals 01, 02.
•
External switches operating the control inputs must be rated for the control voltage being used and a
continuous current of 100 mA.
•
Incorrect configuration and wiring of the external contacts/switches to the control input terminals may cause
damage.
•
If long cable runs are used, wiring must be twisted pair or shielded cable and must be separated from AC
power cables by at least 300 mm.
NOTE
Applying voltage to the control inputs will damage the soft starter. Damage to the control inputs is not
covered by warranty.