background image

 

 AUBER INSTRUMENTS

    

 

 

 

 

 

 

            

WWW.AUBERINS.COM 

 

2019.01             

 

 

               P6/6 

A. 240V heater with alarm buzzer (Oven/Smoker/Cooker) 

120VAC

L

TC

+

-

1

13 14

6

2

3
4
5

7

8
9

10

N

120V  Buzzer

11 12

SSR

240VAC

SWA-

2451A

L1

L2

3

4

1

2

Heater

Figure 6a. 240V heating element with 120V Buzzer

 

  

TC

+

-

1

13 14

6

2

3
4
5

7

8
9

10

240V  Buzzer

11 12

SSR

240VAC

SWA-

2451A

L1

L2

3

4

1

2

Heater

 

Figure 6b. 240V heating element with 240V Buzzer 

 
The heater is driven by a SSR. Sometimes user may want to use the oven for a 
preset time and use it multiple times. In this case a normally closed switch 
should be used. When controller is on, the cooker will be heated up to 135° F. 
The temperature will be hold for 20 minutes. Then the controller will turn off the 
heater and turn on the buzzer automatically. User can press the NC switch to 
reset the timer. When temperature is over 150° F, buzzer will be turned on 
automatically. 

The parameters that need to be changed from the initial 

value: SV = 135° F, ALP1 = 0, ALP2 = 1, AL2 = 150° F, UPT = 1, TE1 = 20, 
INT = 1.

 

 

B. Espresso machine 

Brew Pump

L

1

13 14

6

2
3

4
5

7
8

9

10

N

120V AC

SWA-

2451A

11 12

N. O. Switch

Heater

Fuse

RT

D

R

R

W

SSR

M

3

4

1

2

 

Figure. 7 Typical wiring for espresso machine with PID temperature control and 
timer for brew control.  
 
The heater is switched by a SSR. RTD sensor is used. For the brew control, a 
rocker switch, or a normally open switch on the espresso machine for brew 
should be used. When the switch turns on, the pump will run 25 second and 
stop automatically. User need to turn off and turn on the switch again to 

make 

another shot. The parameters need to be changed are: Sn = Pt, SV = 220, 
ALP1 = 0, UPT = 2, TE1 = 25, INT = 5.

 

 
 

6. Trouble Shooting 
 
6.1 Timer 

won’t start

 

Check the connection between terminal 11 and 12. These two terminals must 
be jumped together to enable the timer. A momentary NC switch on pin 11 and 
12 can serve as a timer-reset switch. 

 

 

6.2 No heating 

The OUT LED is synchronized with output relay. If there is no heat when it is 
supposed to, check the OUT first. If it is not lit, the controller parameter setting 
is wrong. If it is on, check external SSR (if the SSR

’s

 red LED is ON). If the SSR 

is ON, then the problem is either the SSR, its wiring, or the heater. If the 
external switching device is not on, then the problem is either the controller 
output, or the external switch device. 
 

6.3 Poor accuracy 

Please make sure calibration is done by immersing the probe in liquid. 
Comparing with reference in air is not recommended because response time of 
sensor depends on its mass. Some of our sensor has response time >10 
minutes in the air. When the error is larger than 5 ° F, the most common 
problem is improper connection between the thermocouple and the controller. 
The thermocouple needs to be connected directly to the controller unless 
thermocouple connector and extension wire is used. Copper wire or 
thermocouple extension wire with wrong polarity connected on the 
thermocouple will cause the reading drift more than 5 ° F.  
 

6.4 Under on/off control mode, although hysteresis is set to 0.3, unit is 
running 5 degrees above and below. 

If the Hy is very small and temperature change very fast, user needs to 
consider the delay of the cycle time (the parameter t). For example, if cycle time 
is 20 seconds, when the temperature passes the SV + Hy after the very 
beginning of 20 seconds, relay will not act until it starts the next cycle 20 
seconds later. The temperature could be much higher than the set point. User 
may change the cycle time to a smaller value, such as 2 seconds, to get a 
precise control. 
 

6.5 

Display “

HH

 

This is an input error message. The possible reasons are: the sensor is not 
connected or not connected correctly; the sensor input setting is wrong; or the 
sensor is defective. In this case, the instrument terminates its control function 
automatically. If this happens when using thermocouple sensor, you can short 
terminal 4 and 5 with a copper wire or paper clip. If the display shows ambient 
temperature, the thermocouple is de

fective. If it still displays “

HH

, check the 

input setting, Sn, to make sure it is set to the right thermocouple type. If the Sn 
setting is correct, the controller is defective. For RTD sensors, check the input 
setting first because most controllers are shipped with the input set for 
thermocouples. Then check the wiring. The two red wires should be connected 
to terminals 4 and 5. The white wire should be connected to terminal 3. 
 

6.6 Cannot change set temperature 

Please check parameter dIH and dIL. These two parameters limit the set 
temperature range. If you set dIH and dIL at the same value (like 100), the set 
temperature (SP) can only be set as 100, and user cannot adjust it.   
 
 
 
 
 
 
 
 

Auber Instruments 

5755 North Point Parkway, Suite 99 

Alpharetta, GA 30022, USA 

www.auberins.com

 

E-mail

[email protected]

 Tel: 770-569-8420 

 

Copyright 2007-2019, Auber Instruments All Rights Reserved. 

No part of this manual shall be copied, reproduced, or transmitted in any way 

without the prior, written consent of Auber Instruments. Auber Instruments 

retains the exclusive rights to all information included in this document. 

Отзывы: