background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2021.05                                                                    

   

                                                       P2/7 

 

4.1 Sensor connection 
4.1.1 Thermocouple 

The thermocouple should be connected to terminals  9 and 10. Make sure that 
polarity  is  correct.  There  are  two  commonly  used  color  codes  for  the  K  type 
thermocouple. US color code uses yellow (positive) and red (negative). Imported 
DIN color code uses red (positive) and green/blue (negative). The temperature 
reading will decrease as temperature increases if the connection is reversed.  
 

4.1.2 RTD sensor 

For a three-wire RTD with standard DIN color code, the two red wires should be 
connected to the terminals 9 and 10. The white wire should be connected to 
terminal 8. For a two-wire RTD, the wires should be connected to terminals 8 and 
9. Jump a wire between terminals 9 and 10.  
 
For PT100 sensor, set Input Sensor Type, 

Inty

, to 

P100

 (1 degree resolution) 

or 

P10.0

 (0.1 degree resolution). 

 
4.2 Power to the controller 

The power cables should be connected to terminals 1 and 2. Polarity does not 
matter. It can be powered by 85 - 260 V AC or DC power source. Neither a 
transformer nor jumper is needed to wire it up. For the sake of consistency with 
the wiring example described later, we suggest you connect the hot wire to 
terminal 2 and neutral to 1. Since the controller is in a plastic shell, ground wire is 
unnecessary. 

 
4.3 Output connection 

Three control output options are offered by this controller: (1) Linear current 
output provides 0 ~ 20 mA or 4 ~ 20mA current output. (2) J1 relay output can be 
used to turn on a contactor or a solenoid valve. It can also drive a small heater 
directly if the heater draws less 3 Ampere. 
 

4.3.1 Drive the load through linear current output (mA) 

Connect terminal 7 to the negative input and terminal 6 to the positive input of the  
loads which takes linear input (like linear controlled valve). Set the Control Output 
Mode (

outy

) to 1, 2, or 5 depending on the control mode to be used. Then set 

the Main Output Mode (

Coty

) to “0

-

20” or “4

-

20”. 

See Figure

 

12 for an example. 

Please note that the SSR output is not available on this model. 

 

4.3.2 Drive the load through J1 relay 

Assuming the controller is powered by a 120 V AC source and the contactor has 
a 120 V AC coil, jump a wire between terminal 2 and 4. Connect terminal 5 to one 
lead of the coil and terminal 1 to the other lead of the coil. Set the system Control 
Output Mode (

outy

) to 3 or 4 depending on the control mode to be used. Please 

see Figure 10 for an example. 
 

4.4 Note for first time users 

For  first  time  users  with  no  prior  experience  with  PID  controllers,  the 
following notes may prevent you from making a few common mistakes. 

4.4.1

 Power to the heater does not flow through terminal 4 and 5 of the controller. 

The controller consumes less than  2 watts of power. It only provides a control 
signal to the relay. Therefore, 20 gauge wires are sufficient for providing power to 
terminal 1 and 2. Thicker wires may be more difficult to install. 
 

4.4.2

 The J1 relay is 

“dry single pole switch”. 

It does not provide power by itself. 

Figure 11 shows how the J1 relay is wired to pass the 120 V AC power to drive an 
external contactor which requires 120 V AC for its coil. If the coil of the contactor 
requires a different voltage than the power supplied to the controller, an additional 
power source will be needed (Please see Figure 11 for an example). 
 
 

5. Parameter Settings  

For safety reasons, control parameters are divided into three groups with different 
pass codes. You should only give the code to those who have the responsibility 
and knowledge of how to properly change it. Code 0089 contains parameters for 
system configuration that may need to be changed during the initial set up. Code 
0036 contains parameters for tuning the control performance. Code 0001 is for 
changing set temperature and alarm settings. 
 

5.1 System configuration parameters (accessed by code 0089)

 

The system configuration parameters are listed in Table 1.

 

To change the 

parameters, press SET key briefly, enter the 

code “0089” 

and press SET key 

again. The procedures to change system parameters are shown in the flow chart 
in Figure 3. 
 

               

Operation Mode

0089

Enter Code

Parameter Display

Control output mode

inty

X

    

XXXX

X

XXXX

outy

hy

psb

Main output mode

Input offset

SET

SET

SET

SET

SET

SET

SET

X

rd

Control function

SET

X

corf

Display unit(C/F)

end

SET

SET

SET

SET

SET

Input sensor type

XXXX

SET

SET

XXXX

coty

SET

Hysteresis band

SET

SET

XX

id

Unit ID

SET

SET

XXXX

baud

Baud rate

SET

Figure 3. System parameters setup flow chart. 

 

 
(1) Press SET key to enter setting mode;  
(2) Press >, V, or   key to adjust parameters;  
(3) Press SET key to confirm; 
(4) Press V or 

key to select the new parameter and repeat step 2 and 3. 

(5) Go to “End”, press SET key to exit parameter setting mode.

 

 
 
 
 
 
 

Содержание SYL-2381-mA

Страница 1: ...ommonly used temperature sensor inputs 2 Specifications Input type Thermocouple TC K E S R J T B WRe3 25 RTD Resistance temperature detector Pt100 Cu50 Input range See Table 2 Display Dual lines four...

Страница 2: ...l and terminal 1 to the other lead of the coil Set the system Control Output Mode outy to 3 or 4 depending on the control mode to be used Please see Figure 10 for an example 4 4 Note for first time us...

Страница 3: ...setting PSb 3 will make the controller display 0 C To set a negative value use Shift key to go to the very left digit then press Down key V until the first digit change to Note 6 Parameter ID and bAud...

Страница 4: ...T key again The procedures to change control parameters are similar to what is shown in Figure 3 Table 5 Set temperature and alarm parameters Symbol Description Initial Setting Note SV SV Target tempe...

Страница 5: ...the Note 4 in 5 1 for details On this controller only J1 relay can be used for on off control To use the on off mode set outy 4 Then set Hy to a desired value based on the requirements of the control...

Страница 6: ...Note if this is to control a contactor with 24 V coil PID mode can be used Then the setting should be the same as example 10 1 except the SV value 10 3 Drive a proportional control valve directly in...

Страница 7: ...t When outy is set to 3 or 4 the control output is sent through J1 relay The J1 relay action is synchronized with the AL1 indicator When AL1 is on J1 relay should pull in when AL1 is off J1 relay shou...

Отзывы: