Table 3. Code for Sn and its range. 

Sn Code 

Input Device 

Display Range (

˚

C) 

Display Range (

˚

F) 

Cu50 

Cu50 (RTD) 

-49 ~160 

-56 ~ 302 

Pt 

Pt100 (RTD) 

-199 ~610 

-198 ~1111 

K (thermocouple) 

-30 ~ 1300 

-20 ~ 2370 

E (thermocouple) 

-29 ~ 719 

-20 ~ 1292 

J (thermocouple) 

-29 ~ 905 

-20 ~ 1651 

T (thermocouple) 

-198 ~ 400 

-190 ~ 750 

S (thermocouple) 

-29 ~ 1619 

-20 ~ 2912 

0 - 5 

0 ~5V (0 ~10mA) 

Not available for this model. 

1 - 5 

1 ~5V (4 ~20mA) 

  

4.6 Decimal point setting 

dP

 

In case of thermocouple or RTD input, dP is used to define temperature display 
resolution. 
When dP = 0, temperature display resolution is 1º (C or F). 
When dP = 1, temperature display resolution is 0.1º (C or F). The temperature 
will be displayed at the resolution of 0.1º for input below 1000º and 1º for input 
over 1000º (C or F). 
 

4.7 Limiting the control range, 

DIL

 and 

DIH

 

 

1) For temperature sensor input, the “DIL”

 

and “DIH”

 define the set value range. 

DIL is the low limit, and DIH is the high limit. Sometimes, you may want to limit 
the temperature setting range so that the operator cannot set a very high 
temperature by accident. For example, if you set the DIL = 100 and DIH = 130, 
operator will only be able to set the temperature between 100 and 130. 
 
2) For linear input devices, 

DIL

 and 

DIH

 are used to define the display span. 

For example, if the input is 0 - 5V. DIL is the value to be displayed at 0V and 
DIH is the value at 5V. 
 

4.8 Input offset 

SC

  

SC is used to set an input offset to compensate the error produced by the 
sensor or input signal itself. For example, if the controller displays 5ºC when 
probe is in ice/water mixture, setting Pb = -5, will make the controller display 
0ºC. 

 

4.9 Output definition 

OPA

  

This parameter should be kept at zero for this model. 
 

4.10 Heating, and Cooling Mode Selection 

COOL

  

When COOL = ON, the controller is set for cooling control.  
When COOL = OFF, the controller is set for heating control. 
 

4.11 Temperature Unit Selection, Celsius or Fahrenheit, 

C, F

  

This parameter sets temperature units, C for Celsius, F for Fahrenheit. When it 
is for current or voltage input, this parameter is voided. 

 

4.12 Output range high limit 

OUTH

 

OUTH allows you set the output range high limit.  
 
OUTH can be used when you have an overpowered heater to control a small 
subject. For example, if you set the OUTH = 50, the 5000W heater will be used 
as 2500W heater (50%) even when the PID wants to send 100% output. 
 

4.13 Lock up the settings, parameter 

LOCK

  

To prevent the operator from changing the settings by accident, you can lock 
the parameter settings after initial setup. Table 4 shows the privileges 
associated with each lock code. 
 
Table 4. LOCK parameter. 

LOCK value 

SV Adjustment 

Other Parameters 

Yes 

Yes 

Yes 

Locked 

2 and up to 50 

No 

Locked 

 
Note: to limit the control temperature range instead of completely locking it, 
please refer to section 4.7. 
 

4.14 Set Time for Timer 

TE1

 

and “TE2”

 

TE1

 is for setting value for the timer. Press 

 for 3 seconds and change the 

value directly.  

“TE2”

 is for setting time of timer 2, it is only valid for dual timer working mode. 

 

4.15 Time Unit and Timer Counting Mode 

UPT

 

UPT = 0, timer counting down in seconds. 
UPT = 1, timer counting down in minutes. 
UPT = 2, timer counting up in seconds. 
UPT = 3, timer counting up in minutes. 
 

4.16 Timer control mode 

INT

 * 

 
INT = 0. 

The timer is disabled.

 The controller functions as a regular dual 

display controller. The lower display shows the set temperature instead of time. 
INT = 1. The timer starts after the temperature reaches set point. When set time 

reaches, controller’s output stops and timer relay

 pulls in (turns on). It can be 

connected to a buzzer to warn the operator. 
INT = 2. The timer starts after the temperature reaches set point. When set time 

reached, relay pulls in. The controller’s output will continue to be on. 

 

INT = 3. The timer starts after the temperature reaches set point. When set time 

reaches, controller’s output stops. Relay pulls in when timer starts and drops 

out when it reaches the set time. 
INT = 4. Timer function is independent of temperature controller. After powered 
up (or reset), timer starts. The relay will pull in (close) when it reaches the set 
time. 
INT = 5. Timer function is independent of temperature controller. After powered 
up (or reset), timer starts and the relay pulls in (close). It will drop out (open) 
when it reaches the set time. 
INT = 6. Timer function is independent of temperature controller. After powered 
up (or reset), the relay drops out (open) for preset time TE1, then pulls in for 
preset time TE2. This process cycles (dual timer cycling mode). 
INT = 7. Timer function is independent of temperature controller. After powered 
up (or reset), the relay drops out (open) for preset time TE1, then pulls in for 
preset time TE2. The relay will remain drop out (open) until reset. After reset, 
the relay will keep open for preset time TE1 then pulls in for preset time TE2 
again (dual timer no cycling mode). 
INT = 8. Timer function is independent of temperature controller. After powered 
up (or reset), the relay pulls in for preset time TE1 then drops out (open) for 
preset time TE2. This process cycles (dual timer cycling mode). 
 

Note 

*: 

i). When INT value is greater than 0, timer is enabled. The bottom of the display 
is for time. In order to let the timer controls the Alarm 1 (AL1), ALP1 should be 
set to 0.  
ii). Terminal 11 and 12 must be jumped together to enable the timer. Timer can 
be started either at powering up of the controller if terminal 11 and 12 are 
shorted together, or at shorting terminal 11 and 12 if they are not shorted 
together.  
iii) While the timer is running, it can be reset by pressing a reset switch (a 
normally closed momentary switch) that is connected between terminal 11 and 
12. 
iv) When INT is set to 1, 2 or 3, after reset, timer starts counting again if 
temperature reaches SV. If the temperature is lower than SV in heating mode 
(or higher than 

SV in cooling mode), timer won’

t restart until temperature 

reaches SV again. 
 

 
 
 
 