      400-112-006-C                    26/2/07                    1/1

n

One (1) power base

o

Two (2) screws 

p

Four (4) solderless connectors for copper wires 

NOTE: 

Special CO/ALR solderless connectors must be used for connecting

aluminum conductors.

Option

q

One (1) AC112-01 floor sensor (ordered separately; required for floor 
heating applications only)

Turn off power to the heating system at the main electrical panel to
avoid electrical shock. The installation should be carried out by an elec-
trician.

 

NOTE

: This power base must be used with thermostat operating on

15-minute 

cycles.

High voltage thermostats must be installed onto an electrical box.

The following guidelines are not necessary for floor heating applica-
tions:

For a new installation, choose a location about 1.5 m (5 ft) above the
floor and on an inside wall.

The thermostat must be installed on an inside wall facing the heating
system.

Avoid locations where there are air drafts (top of staircase, air outlet),
dead air spots (behind a door), direct sunlight or concealed chimneys or
stove pipes.

n

Connect the power base wires to the power supply and load using sold-
erless connectors for copper wires (figure 1). 

o

For floor heating applications, insert the floor sensor wires through one 
of the two holes below the terminals (figure 2) and connect the wires to 
terminals 3 and 4 (no polarity).

NOTE

: The wires must run alongside the terminals and not go over 

them. The wire must not cross any heating wires nor be placed directly 
on a heating wire or adjacent to it. For best performance, the sensor 
probe should be centered between the wires in the mat. 

WARNING

: This power base does not have a built-in ground protection 

device. Therefore, for floor heating applications, you must install a sepa-
rate ground protection device at the main electrical panel. Contact your 
Aube authorized representative if you need a thermostat with built-in 
ground protection device.

p

If you wish to use a remote controller such as the CT240 or CT241, 
insert the cable (use 18 to 22 gauge flexible wires) into one of the two 
holes available below the terminal board and connect to terminals 1 and 
2 of the base (figure 2).

q

Push the excess length of the high-voltage wires back into the electrical 
box.

r

Secure the power base to the electrical box using the provided screws. 

s

If necessary, set the configuration switches on the control module (refer 
to the control module user guide).

t

Install the control module onto the base.

u

Apply power to heating system.

Storage

: -4°F to 120°F (-20°C to 50°C)

Remote controller input (ECONO)

: requires a dry contact

Size  (H • W • D)

: 4.89 x 2.76 x 0.91 in. (124 x 70 x 23 mm)

Certifications

n

Parts

1.

o

Guidelines

2.

p

Procedure

3.

q

Technical Specifications

4.

Model

Supply

Max. Load

Power

Wiring

120S

120 VAC, 50/60Hz

16.7 A

2000 W

4 wires / single pole

240S

240 VAC, 50/60Hz
208 VAC, 50/60Hz

16.7 A

4000 W
3475 W

4 wires / single pole

240D

240 VAC, 50/60Hz
208 VAC, 50/60Hz

15 A

3600 W
3120 W

4 wires / double pole

Power

Load

Figure 1

Figure 2

PB112

Installation Instructions

For models: 120S / 240S / 240D

400-112-006-C (PB112-120-240) ENG.fm  Page 1  Monday, February 26, 2007  1:32 PM

 

 

 