TH146-P-U 

                                              8/8

Configuration Menu

Item

Parameters

Display

Default

Options

Description

1

Time format

24 Hr

12 Hr / 24 Hr

Select the time display format.

2

Early Start

OF

On / OF

• On: Heating or cooling starts in advance (as determined by the controller) so 

that the desired temperature is attained at the set times. 

• OF (Off): Heating or cooling starts at the set times.
NOTE: Early Start applies for periods 1 and 3 (P1 and P3) only. When this feature is 
enabled, heating or cooling will start in advance of the set time for P1 and P3 but will 
start at the set time for P2 and P4.

3

Automatic daylight 
savings adjustment

OF

OF / 1 / 2

• OF (Off): The function is deactivated.
• 1 : The controller switches to daylight savings time on the first Sunday of April 

and to normal time on the last Sunday of October.

• 2 : The controller switches to daylight savings time on the second Sunday of 

March and to normal time on the first Sunday of November.

4

Temperature format

°C

°C / °F

Select the temperature display format.

5

Balance point low 
(note 1)

-10°C

(14°F)

-30 to 10°C

(-22 to 50°F)

Set the bP L limit (see section 4.2).
NOTE: Lower bP L below its minimum (- -) if you do not wish to use this function.

6

Balance point high 
(note 1)

5°C

(41°F)

-5 to 30°C

(23 to 86°F)

Set the bP H limit (see section 4.2).
NOTE: Raise bP H above its maximum (- -) if you do not wish to use this function.

7

Defrost point 
(note 1)

10°C

(50°F)

-10 to 15°C

(14 to 59°F)

Set the defrost point temperature (see section 4.3).
NOTE: Raise the defrost point above its maximum (- -) if you do not wish to use this 
function.

8

Installation type 
(note 1)

Ad

Ad / nr

Set according to the type of heat pump installation (see section 4.4). 
• Ad (add-on): Use this setting when the indoor coils are located downstream of 

the auxiliary heat source. This is generally the case for add-on installations.

• nr (normal): Select this setting when the indoor coils are located upstream of 

the auxiliary heat source. This is generally the case for new installations.

9

Auxiliary interstage 
delay (note 1)

30 min.

5 to 90 min.

Set the interstage delay for the auxiliary stage (see section 4.5).

10

Low temperature 
limit (note 2)

- -

(disabled)

-10 to 20°C

(14 to 68°F)

Set the low temperature limit of the plenum (see section 4.6).
NOTE: The function is disabled when LLMT is set below its minimum (- -).

11

High temperature 
limit (note 2)

- -

(disabled)

30 to 90°C

(86 to 194°F)

Set the high temperature limit of the plenum (see section 4.6).
NOTE: The function is disabled if HLMT is set above its maximum (- -).

12

Cycles per hour

4

2 to 6

Select the number of heating/cooling cycles per hour. For optimal heating control, use 
the setting that matches your system as follows: 3=20 min (hot water, 90%+ high-
efficiency furnace), 4=15 min (gas or oil), 5=12 min (gas or oil), 6=10 min (electric).

13

Heat type

EL

GA / EL

This setting determines the fan operation in automatic mode when the system is in 
heating mode.
• EL (electric heating): The fan starts when heating starts and stops when 

heating stops.

• GA (gas or oil heating): The fan starts when the temperature inside the plenum 

rises above the Fan Limit (see item 14) and stops when the temperature drops 
12°C below the Fan Limit. 

NOTE: The fan will not start if the plenum 

temperature sensor is not connected to the controller.

14

Fan limit

80°C

(176°F)

38 to 90°C

(100 to 

194°F)

This parameter is available only when gas heating is selected (see item 13).
WARNING: FLMT can be used in parallel with an UL353-approved device but they do 
not replace such device.
NOTE: The fan will not start if you raise FLMT above its maximum (--).

15

Smart Fan

OF

On / OF

• On: Smart Fan is On (see section 4.7).
• OF: Smart Fan is Off.

16

Temperature 
setback

0°C

(0°F)

0 to 9°C

(0 to 16°F)

Set the amount of temperature setback when the controller is placed in Unoccupied 
mode (see user guide).

17

Humidifier 
operating mode

HE

Co / HE / Fn

• Co (conventional): The humidifier will operate if the humidity is too low. If the 

fan is not already On, it will turn On at the same time as the humidifier. 

• HE (heat): The humidifier can operate only when heating is activated.
• Fn (fan): The humidifier can operate as long as the fan is running, whether 

heating is activated or not.

NOTE: The humidifier is disabled when cooling is activated.

18

Dehumidifier type

Co

Co / AE / dr

Set according to the type of dehumidifier used.
• Co (conventional): Select this setting when using a dehumidifier (except an air 

exchanger) or when you do not wish to dehumidify.

• AE (air exchanger): Select this setting when using an air exchanger (see 

section 4.10).

• dr (droop): Select this setting to dehumidify by droop (see section 4.9).

19

Minimum air 
exchange time

0

0 - 60 min.

This parameter is available only if the controller is configured for using an air 
exchanger (see item 18). Use it to set the minimum air exchange time (see user 
guide). 

Note 1: Parameters 5 to 9 are not available when the controller is configured for HVAC or 1H1C, 2H2C or 3H3C heat pump.
Note 2: Parameters 10 and 11 are not available when the controller is configured for heat pump.

Printed in USA

 02-2013

Содержание CT280-3H3C

Страница 1: ...ule Install the control module near the heating cooling system away from any heat source Install the console in a central location Avoid locations with air drafts e g top of staircase or air outlet or...

Страница 2: ...ed for add on installations only It is not needed if the heat pump is not connected to the controller terminal WW Install the sensor on the side of the plenum and position it such that its aperture fa...

Страница 3: ...nace the auxiliary heat source is installed at the same time as the heat pump In this type of installation the indoor coils are located upstream of the auxiliary heat When the controller is configured...

Страница 4: ...ry heat 2 24 Vac 1 A W3 O B Reversing valve 24 Vac 1 A G Fan 24 Vac 1A L Fault 24 Vac 5 mA WW Defrost 24 Vac 5 mA NOTE Requires a dry contact do not connect to a solid state relay such as a triac NC N...

Страница 5: ...TH146 P U 5 8 Wiring Diagram 2H1C Heat Pump New Installation AC146 410 AC144 03 CT241 Humidifier Dehumidifier Compressor Auxiliary Heat Reversing Valve Fan Fault Defrost Dual Energy...

Страница 6: ...TH146 P U 6 8 Wiring Diagram 3H2C Heat Pump Add on Installation AC146 410 AC144 03 CT241 Fault Defrost Reversing Valve Compressor 1 Compressor 2 Furnace Fan Limit Humidifier Dehumidifier Dual Energy...

Страница 7: ...TH146 P U 7 8 Wiring Diagram 3H2C HVAC AC146 410 AC144 03 CT241 Cooling Unit 1 Cooling Unit 2 Heating Unit 1 Heating Unit 2 Fan Heating Unit 3 Humidifier Dehumidifier...

Страница 8: ...on 4 6 NOTE The function is disabled if HLMT is set above its maximum 12 Cycles per hour 4 2 to 6 Select the number of heating cooling cycles per hour For optimal heating control use the setting that...

Страница 9: ...ule Installer le module de contr le pr s du syst me de chauffage et climatisation loin des sources de chaleur Installer la console un endroit central viter les endroits o il y a des courants d air ex...

Страница 10: ...u pl num et la positionner de sorte que l ouverture de lecture soit face au courant d air Raccorder la sonde aux bornes PS et CS du contr leur aucune polarit Pour plus d information se r f rer aux ins...

Страница 11: ...mont du chauffage d appoint Lorsque le contr leur est configur pour une nouvelle installation la thermopompe et le chauffage d appoint peuvent fonctionner en m me temps Le d lai d activation est le te...

Страница 12: ...ca 1 A W3 O B Valve d inversion 24 Vca 1 A G Ventilateur soufflerie 24 Vca 1A L D faut 24 Vca 5 mA WW D givrage 24 Vca 5 mA NOTA Exige un contact sec ne pas relier un relais semi conducteur tel un tri...

Страница 13: ...8 Sch ma de branchement thermopompe 2H1C nouvelle installation Compresseur Valve d inversion Ventilateur D faut D givrage Chauffage d appoint AC146 410 AC144 03 Humidificateur D shumidificateur CT241...

Страница 14: ...hement thermopompe 3H2C installation add on installation modifi e Fournaise Thermostat ventilateur D faut D givrage Valve d inversion Compresseur 1 Compresseur 2 AC146 410 AC144 03 Humidificateur D sh...

Страница 15: ...TH146 P U 7 8 Sch ma de branchement CVAC 3H2C Refroidissement 1 Chauffage 1 Chauffage 2 Ventilateur Chauffage 3 AC146 410 AC144 03 Humidificateur D shumidificateur CT241 Refroidissement 2...

Страница 16: ...ctiv e lorsque HLMT est plac au dessus du maximum 12 Cycles par heure 4 2 6 Permet de s lectionner le nombre de cycles par heure Pour un contr le optimal du chauffage choisir le r glage qui correspond...

Отзывы: