Proper duct installation is critical to operation of furnace. When 
installing ducts, use materials rated for continuous use at 200°F. 

 

See minimum clearance to floorboards, walls & similar combustible 
building materials. 

 

Each 4-inch duct opening provides 12 in

2

 of discharge area. Minimum 

for this furnace is 24 in

2

If closeable registers or a 2” duct is used unit 

must be provide with a front grill system. 

 

Ducting in dead air space with no return air, such as holding tank 
areas, does not count toward achieving minimum discharge 
requirements. 

 

Adjust ducting installation to obtain air rise of 100°F-130°F for optimum 
performance. 

 

FLEXIBLE DUCTING SYSTEMS 

 

When designing flexible duct systems: 

 

Follow ducting configuration show in Table 2.  

 

Avoid sharp bends or crushed ducts. 

 

Stretch all ducts and run them directly to outlets, keeping quantity and 
angles of bends to a minimum. 

 
1. 

Remove knockout plate from desired outlets. See Figure  6. If both 

4” 

outlets are not being used leave in place, if removed a cover plate can 
be purchased. 

2. 

Attach a duct adapter by inserting flange over casing hole, locking the 
tab into casing slot and turning adapter 90°. 

3. 

Attach and secure four-inch flexible duct to adapter(s). 

4. 

Run duct(s) to desired location within RV, secure to register(s). 

 

AIR FLOW CHECK 

Appliances are tested to a temperature rise as specified on the Rating 
Plate. After installation of the furnace and duct system is completed, 
adjustments to be made to obtain a temperature rise as specified on 
the Rating Plate.  
 
The table below is used as reference to maintain maximum operation 
of the appliance. If checking temperature rise is not possible, air flow 
measurements at each registers added together and divide by total 
registers will give you air flow reading. This reading should not be less 
than the minimum in the table under your BTU appliance size. 
 
If readings are below table values, air flow can be improved by adding 
ductwork. Check to make sure restrictions in the system are not 
present. 
 

12,000 

16,000 

20,000 

1650* 

1650* 

1800* 

*FPM= feet per minute reading 

 

 WARNING 

FIRE OR EXPLOSION 

Never check for leaks with an open flame. Turn on the gas and apply 
soapy water to all joints to see if bubbles are formed. 

 
 

 
PROPANE GAS CONNECTION 
Propane Gas Pressure Test 

The furnace and any individual shut-off valve must be 
disconnected from gas supply piping system during and 
pressure testing of system at test pressures of more than 1//2” 
PSI. 
Before furnace is, connected piping systems are to be tested to 
be leak free. The test must maintain air pressure of a least 6” 
of mercury or 3 PSI for at least 10 minutes. 
The entire piping system is to be maintained for a pressure of 
10” to 13” W.C. when all appliances are in operation. Test gas 
connections for leakage with soapy water or a leak test 
solution. 

 

Figure 7

 

1. 

Connect gas line to the fitting located on top right side of furnace or if is 
supplied with an extended manifold at the rear of the furnace.  

2. 

Be sure all male pipe threads, other than flare fittings, are treated with 
a sealing compound resistant to the action of propane (LP) gas. DO 
NOT put sealing compound on flare fittings. 

3. 

Use two wrenches to hold nut when tightening gas lines. DO NOT twist 
valve assembly. See Figure 7. 
 

 

A 1/8” N.P.T. plug is accessible for test gauge connection on gas valve 
assembly for pressure testing. 

 

A 3/8” flared fitting connection provided at gas control valve inlet for 
gas supply connection to furnace. The gas supply line of the furnace 
must be of adequate size to provide 11” W.C. gas pressure. This 
pressure to be maintained under maximum flow conditions with all gas 
appliances in operation. 

 

If local codes allow the use of a flexible gas appliance connector, 
always use a new listed connector. Do not use a connector, which has 
previously serviced another gas appliance. 
 
1. 

Remove grommet plug from furnace. 

2. 

Insert gas line through grommet plug (DO NOT CUT). 

3. 

Connect gas line inside furnace casing immediately ahead of gas 
control valve. 

4. 

Connect gas line to brass fitting located on top or right side of 
furnace. 

5. 

Some models will have fittings at the rear outside of the casing.  

6. 

Use two wrenches to hold brass fitting and flare nut when 
tightening gas line to brass fitting. DO NOT twist valve assembly 

 

ELECTRICAL CONNECTIONS 

 

 WARNING 

INJURY OR PROPERTY DAMAGE 

 Label  all  wires  before  disconnecting  for  servicing.  Wiring  errors  can 

cause  improper  and  dangerous  operation.  Verify  proper  operation 
after servicing. 

 Disconnect electrical power before servicing.

 

 

 CAUTION 

PROPERTY DAMAGE

 

This connection is for low-voltage battery or direct current only. Do not 
connect to 120 or 240 volts AC. 

 

Содержание AFSAD12111

Страница 1: ...DO NOT use furnace cabinet area as a storage compartment DO NOT vent furnace with venting system serving another appliance DO NOT vent furnace to an outside enclosed porch area DO NOT use for temporary heating of buildings or structures under construction Protect building materials from degrading from flue gas exhaust Protect furnace electrical components from water Compartments must be closed whe...

Страница 2: ...cted 12 Volt Amperage AMPS 3 4 3 4 4 8 2 4 Power Supply Volt DC 12 12 12 12 Watts 41 41 56 34 Minimum Return Air 35 in2 35 in2 35 in2 35 in2 WC WATER COLUMN DUCTING CONFIGURATION Table 2 Models AFSD12 AFSD16 AFSD20 AFSAD12 Side Ducting 2 Ducts 2 Ducts 2 Ducts N A Front with Side Ducting 1 or 2 Ducts 1 or 2 Ducts 1 or 2 Ducts N A Front Only no Side Ducts Front Front Front Front DIMENSION Table 3 Ap...

Страница 3: ...ition CAUTION Due to the differences in vinyl siding materials this appliance should not be installed without first consulting with the manufacturer of the siding or cutting the siding away from the area around the appliance vent A gas fired furnace for installation in a residential garage must be installed so the burner s and the ignition source are located not less than 18 in 457mm above the flo...

Страница 4: ...h cutout about a 1 inch slip bezel around casing and flush inner flange with casing 4 Secure bezel to furnace casing with 6 screws 5 Push furnace and bezel back tight against side wall and secure with 14 screws 6 When installing screws DO NOT deform bezel 7 Connect the gas line to the valve and push the gas line plug into casing opening 8 Remove excess sealant from around bezel and visually inspec...

Страница 5: ...d PROPANE GAS CONNECTION Propane Gas Pressure Test The furnace and any individual shut off valve must be disconnected from gas supply piping system during and pressure testing of system at test pressures of more than 1 2 PSI Before furnace is connected piping systems are to be tested to be leak free The test must maintain air pressure of a least 6 of mercury or 3 PSI for at least 10 minutes The en...

Страница 6: ... and remain off until unit is reset by reactivating the thermostat Stop Read Users Information Manual supplied with furnace 1 Turn the manual valve if so equipped or the valve at the outside LP tank to the OFF position Do NOT force NOTE This furnace is equipped with a valve shut off switch with switch in OFF position Gas will not flow to burner nor will the furnace operate Turn switch to ON positi...

Страница 7: ...7 WIRING AND LADDER DIAGRAM ...

Страница 8: ...8 PART DRAWINGS PART LISTS ...

Страница 9: ...9 ...

Страница 10: ...10 ...

Страница 11: ...lorsque vous effectuez le test NE PAS utiliser un courant alternatif de 120 V avec les modèles à courant continu NE PAS utiliser la zone du cabinet de fournaise comme compartiment de rangement NE PAS aérer la fournaise avec un système de ventilation pour entretenir un autre appareil NE PAS aérer la fournaise à un endroit extérieur fermé comme une véranda NE PAS utiliser pour le chauffage temporair...

Страница 12: ...S ÉLECTRIQUES 6 INSTALLATION DU THERMOSTAT 6 INSTRUCTIONS D UTILISATION 6 POUR METTRE HORS TENSION 7 VÉRIFICATIONS DU SYSTÈME 7 SPÉCIFICATIONS MODÈLE Tableau 1 Nos de modèles AFSD12 AFSD16 AFSD20 AFSAD12 Type de gaz LP Propane LP Propane LP Propane LP Propane BTU en entrée 12 000 16 000 18 000 12 000 BTU en sortie 9 120 12 160 13 680 9 120 Conduit de pression statique 0 10 po WC 0 10 po WC 0 10 po...

Страница 13: ...souples installez la fournaise sur des taquets ou sur un panneau de bois ou de métal s étendant de la largeur et profondeur complète de la fournaise plus un dégagement minimal pour les combustibles NE PAS utiliser de nettoyant à base de pétrole ou de type citron sur les pièces de plastique vous pourriez les endommager ATTENTION À cause des différences dans les matériaux de revêtement en vinyle cet...

Страница 14: ...e dans le calfeutrage et inspectez visuellement le conduit pour vous assurer qu il est bien scellé fixez avec deux conduits et deux vis et retirez l excès de calfeutrage INSTALLATION STANDARD DE LA PORTE Figure 3 Toutes les surfaces en contact avec l extérieur du mur latéral doivent être étanches et scellées avec un scellant RTV Les conduits sont conçus pour permettre l évacuation d eau lorsqu ins...

Страница 15: ...s de tuyauterie flexible Suivez les configurations de tuyauterie dans le tableau 2 Évitez des extrémités tranchantes ou des conduits écrasés Étirez tous les conduits et branchez les directement aux sorties gardant la quantité et les angles de tuyaux pliés au minimum 1 Retirez le plateau de déboucheur des sorties désirées See Figure 6 Si les deux sorties de 4 po ne sont pas utilisées laissez les en...

Страница 16: ...19 17 11 16 87 65 52 43 37 33 29 26 17 Cette fournaise est conçue pour une mise à la terre négative de 12 V à courant continu seulement NE PAS essayer de modifier la fournaise pour un système de mise à la terre positif ou connecter la fournaise directement à un courant alternatif de 120 V Les dommages sur les composantes de la fournaise se produiront et la garantie sera annulée Utilisez un fil de ...

Страница 17: ... éteignez l unité et contactez votre revendeur ou une agence locale de véhicules récréatifs Ne pas continuer faire fonctionner la fournaise par le thermostat espérant avoir une ignition POUR METTRE HORS TENSION 1 Mettez le thermostat au réglage le plus bas puis déplacez le levier dans la position ARRÊT 2 Tournez la valve manuelle d arrêt si équipé à la position ARRÊT Ne pas forcer VÉRIFICATIONS DU...

Отзывы: