background image

5

3.  A. When set for LP and NAT is required:

Rotate plug and replace into valve tower. 

NAT 

SHOULD NOW BE VISIBLE

FIG

5

B. When set for NAT and LP is required:

Rotate plug and replace into valve tower. 

LP 

SHOULD NOW BE VISIBLE

FIG

5

4. Check rod for proper positioning while tightening plug into tower.

The plug, which has been factory calibrated for this valve only,
should be reinstalled finger tight. 

DO NOT USE PLUG ON ANY OTHER VALVE

.

INSTALL ONLY THE CORRECT MAIN BURNER ORIFICE FOR TYPE OF GAS BEING USED

.

ORIFICE REPLACEMENT

1. Remove rain shield by tilting as depicted in 

FIG

9 insert.

2. Remove burner assembly from control box.
3. Remove two screws holding burner head in place.
4. Use a 7/16˝ socket to remove orifice and replace correct orifice cor-

responding to type of gas required, which corresponds to regulator
plug setting 

FIG

5.

5. Replace burner head with two screws.
6. Reinstall burner assembly. Burner assembly must seal tight against

control box.

7. Replace rain shield and four screws.
8. After converting furnace, 

IN PLAIN SIGHT

, put “

CONVERTED

” sticker (pro-

vided in your conversion packet) on rating label.

SYSTEM CHECKS

WARNING

FIRE OR EXPLOSION

• Never check for leaks with an open flame.

DIAGNOSTIC CHART

FAULT

LED INDICATION

Internal Circuit Board Failure

Steady on, no flashing

Limit switch/Airflow problems

1 flash with 3-second pause

Flame Sense Fault

2 flashes with 3-second pause

Ignition Lockout Fault

3 flashes with 3-second pause

PROPANE GAS PRESSURE TEST

The furnace and any individual shut-off valve must be disconnected
from gas supply piping system during any pressure testing of system
at test pressures of more than 1/2 PSI.

Before furnace is connected, piping systems must be tested to be leak
free. The test must maintain air pressure of at least 6˝ of mercury or 3
PSI for at least 10 minutes.

The entire piping system must be maintained within a range of 10-14˝
W.C. when all appliances are in operation. Test the gas connections for
leakage with a leak test solution.

STATIC PRESSURE TEST   

(

FIG

.

1)

CASING STATIC PRESSURE TABLE

If duct static pressure cannot be set, casing static pressure should not exceed
the values listed below when taken cold.

DUCTING SYSTEM

OPERATING VOLTS

FLEXIBLE

HARD

DC 

MODELS

12

0.25˝  W.C.

0.35˝ W.C.

AC 

MODELS

120

0.25˝  W.C.

0.35˝ W.C.

NOTE

: For maximum performance and reliability refer to Installation Addendum

for manufacturer’s recommendations and specifications.

Voltage greater than indicated will cause higher static readings.
Reducing the number of duct turns and stretching ducts will increase
air flow and reduce static pressure. Adding ducts or increasing dis-
charge system (hard ducting) will also reduce static pressure.

1. With door open, locate static pressure tap or use location on back of

casing 

FIG

1.

2. Shut off gas supply to furnace.
3. Insert static pressure tube onto tap and attach an incline manometer.

With door closed, pressure should not exceed values specified in

CASING STATIC PRESSURE TABLE

.

4. Remove pressure tube when finished. Close door or reinstall cover.

12V DC  

SUPPLY 

IMPORTANT:

 If any original wire has to be replaced, it must be replaced with type 105 C or its equivalent. 

                       Terminal Block on 85 Models only. 

BLACK 

BLUE 

RED 

YELLOW 

HIGH TENSION 

+ 12V DC 

NEG 

RED 

YELLOW 

ELECTRODE 

YELLOW 

VALVE 

RED 

+THERMO 

MOTOR 

CIRCUIT 

BREAKER 

IGNITION 

BOARD 

BLW PWR 

SAIL 

SWITCH 

BLUE 

BLUE 

LIMIT 

SWITCH 

WHITE 

BLUE 

YELLOW 

RED 

GROUND 

THERMOSTAT 

ON 

OFF 

ON/OFF 

SWITCH 

  THERMO 

DC Wiring Diagram 

AC Wiring Diagram

RED 

11 

12

CUSTOMER SUPPLIED WIRING 

PICTORIAL DIAGRAM

Off

On

Valve

Electrode

Green

Sail
Switch

Green

Yellow

3 3

2 2

1 1

White

Black

Yellow

Black

Black

Yellow

Red

Blue

Blue

Limit Switch

Blue

Red

Green

Yellow

Transformer

Ignition Control

Black

Brown

Motor

120 VAC Green

120 VAC Black

120 VAC White

White

Thermo Blue

AC Capacitor Motor Run

+Thermo Blue

HIGH TENSION

DO NOT

GRIP

HERE

1

4

2

3

+

+

1 2 3 4 5 6

 

NOTE: Circuit Breaker and ON/OFF Switch may be
separate or combined components.

Содержание 8935

Страница 1: ...5 ILLUSTRATIONS 6 REPLACEMENT PARTS LIST DRAWING 7 SPECIFICATIONS W C Water Column MODEL 8935 8940 8935 8940 DCLP III DCLP III ACLC III ACLC III BTU Input 35 000 40 000 35 000 40 000 Output BTU HR 27...

Страница 2: ...dard Title 24 CFR part 3280 or when this Standard is not applicable the Standard for Manufactured Home Installations Manufactured Home Sites Communities and Set Ups ANSI A255 1 and or CAN CSA Z240 MH...

Страница 3: ...urnace on gasket gasket must remains in position Use additional ducting to maintain correct static pressure VERTICAL The only ducting option when using vertical installation are the top two ducts and...

Страница 4: ...against inner flange of bezel bending tabs over fill tabs slots with caulking securing with screws VERTICAL INSTALLATION YOU MUST CAULK around red gas inlet plug slide plate and casing bottom intersec...

Страница 5: ...10 14 W C when all appliances are in operation Test the gas connections for leakage with a leak test solution STATIC PRESSURE TEST FIG 1 CASING STATIC PRESSURE TABLE If duct static pressure cannot be...

Страница 6: ...C D 3 4 A B D C 10 1 D B A C G F E 5 1 1 4 1 1 4 AVANT DU VEHICULE Access to Static Pressure Tap Acc s l orifice Statique OR 6 7 8 8 1 A OR 8 7 6 8 OR 3 A MUST USE MUST USE A 1 2 B 9 MUST USE MUST US...

Страница 7: ...ES PI CES 1 Relais 2 Thermostat sp cifiez la couleur 3 Couvercle de l ouverture de branchement du conduit 4 Adaptateur de conduit 5 Lumi re PRECISEZ LE CALIBRE 6 Ventilateur d air de combustion 7 Join...

Отзывы: