ACCUMULATION TANKS

on the heat-exchange surfaces of device. Quality of the heating water depends on the quality of the 
water filled into the system by starting the operation and quality and amount of the water additionally 
filled into the system. Quality of the water additionally filled into the system is defined in the STN 07 7401.

To prepare the D.H.W. in a built-in tank or an instantaneous system, it is necessary to install the 

safety valve of 6 bar on the cold water inlet. It is also necessary to ensure the treatment of the 
D.H.W. against the limescale and dirts from the water distribution network.

Hardness of water cannot exceed 5 mval / l. Warranty does not relate to the blockage of the tank 

or the flow copper exchanger by a limescale.

7. MAINTENANCE

To clean the external parts of the tank you need a wet cloth and a suitable detergent. Never use 

abrasive cleaners, diluents, petroleum-based cleaners, etc.

Check the tightness of joints on the flange of the HR, HRS tank at least once a year, eventually 

fix the nuts. If there is untightness even after fixing the nuts, replace the sealing under the flange.

Maintenance of the accumulation tank HR, HRS concerns test and replacement of the anode rod. 

The magnesium anode adjusts the electric potential inside the tank to the value preventing cor-
rosion of the tank. Theoretical life-time of the anode takes 2 years of operation, but it changes ac-
cording to the callosity and the chemical composition of water at the place, where the tank is used. 
It is recommended to make a test every 6 months and in the case of need, to replace the anode rod. 
This additional protection element should be considered as important.

Procedure of replacement of the anode rod:

1. Discharge approximately 1/3 of the water in the tank 

Procedure: close the valve at the water inlet into the tank, 
open the valve of hot water on the mixing tap, 
open the discharge valve of the tank.

2. Undo the upper cover of the accumulation tank.
3. Use a suitable tool to screw the anode out.
4. Install a new anode and mount the dismantled parts back.
5. Fill the tank with water, pressurize it and check the tightness.

The anode must be replaced only by a specialized service company!

8. DISPOSAL

Packaging must be disposed following the valid prescriptions.
After expiration of the lifetime it is necessary to dispose the product in conformity with the legal 

prescriptions.

Содержание AK1000K

Страница 1: ...THE ACCUMULATION TANKS ATTACK AK AS HR HRS TUV TUVS S SS INSTRUCTION MANUAL W W W A T T A C K S K...

Страница 2: ...appliance is constructed for accumulation and subsequent distribution of the heat energy from the heat sourc es as well as for preparation of the D H W It is forbidden to use this appliance for other...

Страница 3: ...he S and SS is a line of a stratified storage tanks with the volume up to 2 000 l and option to install the electrical heating body 2 2 Thermal insulation The accumulation tanks are supplied with 100...

Страница 4: ...D2 1 AS RS 1 1 90 45 45 4 ATTACK AK ATTACK AS ACCUMULATION TANKS ATTACK AK AS...

Страница 5: ...621 230 700 650 850 1 660 1 710 1 678 3 94 95 488 81 AK800K 1 545 1 135 725 315 840 790 990 1 840 1 890 1 864 3 108 95 732 109 AK1000K 1 735 1 255 775 295 840 790 990 2 030 2 080 2 052 3 127 95 915 1...

Страница 6: ...1 2 3 EL EL 4 5 6 7 8 9 6 7 8 9 10 10 10 RS AS 10 10 10 10 10 1 2 3 4 5 AF AC MA CN 1 4 D2 D1 D1 R R 100 28 17 17 EL 28 6 ACCUMULATION TANKS ATTACK HR HRS ATTACK HRS ATTACK HR...

Страница 7: ...4 8 Position 5 9 Position RS Position AS D1 Diameter without insulation D2 Diameter with insula tion of 100 mm Height Height with insulation of 100 mm R Slope dimension without insulation Max operatin...

Страница 8: ...12 AC AF D2 8 ACCUMULATION TANKS ATTACK TUV TUVS TECHNICAL PARAMETERS OF THE D H W EXCHANGER Material Stainless steel Heated area 3 9 m2 Volume 13 l Connection 3 4 Max operating pressure 10 bar ATTACK...

Страница 9: ...loss W Max operating pressure bar Area of exchanger m Volume of exchanger l Max operating pressure bar Max operatind tempera ture C Area of D H W exchanger m Volume l Weight kg TUV500K C 1 405 1 013 7...

Страница 10: ...D2 1 1 1 90 10 10 45 45 10 ATTACK S ATTACK SS STRATIFIED STORAGE TANKS ATTACK S SS...

Страница 11: ...insulation D2 Diameter with insulation of 100 mm Height Height with insulation of 100 mm R Slope dimension without insulation Max operating temperature C Static loss W Max operating pressure bar Area...

Страница 12: ...to all inlets and outlets as it is given in the table in the chapter 3 Mount the deaeration valve at the highest place of the system and insulate all the connection distributions 5 2 Connection of th...

Страница 13: ...ealing under the flange Maintenance of the accumulation tank HR HRS concerns test and replacement of the anode rod The magnesium anode adjusts the electric potential inside the tank to the value preve...

Страница 14: ...and a suitable detergent Never use abrasive cleaners diluents petroleum based cleaners etc It is not necessary to clean the internal side of the tank because it is connected to the closed heating cir...

Страница 15: ...15 ACCUMULATION TANKS Notes...

Страница 16: ...8 61 Vr tky Slovakia Tel 421 43 4003 101 Fax 421 43 3241 129 E mail kotle attack sk Export tel 421 43 4003 103 Fax 421 43 3241 129 E mail export attack sk V robca ATTACK s r o si vyhradzuje pr vo tech...

Отзывы: