Application
Note:
For detailed parameter explanation, please refer to the full manual.
10.1 Start and stop of panel control, and panel potentiometer setting frequency
10.1.1 Parameter setting:
According to transducer, drag the motor’s rated nameplate data and conduct parameter setting for parameters
P0.07 and P0.08. The parameters that must be set up are stated as follows:
[P0.01]=0
: parameter P0.01 is set up as 0; select the panel potentiometer setting frequency,
[P0.03]=0:
parameter P0.03 is set up as 0; select panel to start and stop control.
Figure 10-1 Panel Control Starting and Stopping, and Basic Wiring Diagram of Panel Potentiometer Setting Frequency
10.1.3 Operating instructions
Press FWD to start the transducer; rotate the panel potentiometer button in clockwise, set up the frequency
gradually, rotate the panel potentiometer button in anticlockwise, set up frequency to reduce gradually, and press
STOP to close down the transducer.
Tips:
External control terminal FWD determines the operation direction of the motor; if FWD-COM is disconnected, the
motor is forward; if FWD-COM is closed, the motor is reverse.