6.2.4. Static pressure monitoring 

If the water pressure is less than 0.2 bar, the regulation locks 
with a ‘P’ + ‘pressure’ on the display. 
This lock is removed when the water pressure goes above 1.3 
bar. 
With a water pressure between 0.5 and 0.2 bar, the burner is 
limited to low load. 
The display shows alternately the ‘P’ and the normal status 
display. 
If the water pressure is greater than 3.0 bar, the regulation 
locks with a ‘P’ + ‘pressure’ on the display. 
This lock is removed when the water pressure goes below 2.9 
bar. 
 

6.2.5. Difference in temperature 

If the temperature difference between flow and return is 
greater than 45°C, the regulation locks. The lock is removed 
with a difference of less than 20°C. 
If the temperature difference between flow and return is less 
than –5°C, the regulation will lock immediately during central 
heating and 20 seconds after ignition during tapping. 
 

6.2.6. Maximum temperature limitation 

If the flow temperature goes above 105°C, when the burner is 
off, the regulation will lock with a continuous ‘H’ (hysteresis 
5°C). 
If the flow temperature goes above 105°C, when the burner is 
on, the regulation will lock with a flashing ‘H’. Only a reset will 
remove the interlock. 
If the flow or return temperature goes above 97°C, the 
regulation will lock. 
 

6.2.7. Flue gas temperature limitation 

If, after switching the supply voltage on, a flue gas 
temperature of greater than –25°C is measured, the flue gas 
sensor is present. If a temperature below –25°C is measured 
afterwards, the regulation locks with the message flue gas 
sensor interruption (‘4’).   
If the flue gas temperature goes above 80°C, the burner is 
limited to low load. 
If the flue gas temperature goes above 90°C, the regulation 
locks with ‘A’. 
If the flue gas temperature goes below 70°C, both locks are 
removed. 
If the flue gas temperature goes above 95°C, the regulation 
locks with ‘A’. 
 

6.2.8. Flow sensor protection 

The difference between flow and return temperatures must be 
less than 20°C before each burner start. The difference 
between flow and return temperatures must be raised by 3°C 
within 10 seconds after each burner start. However, if the 
difference is less than the previous temperature difference, 
the burner is started again after 10 seconds. 
During this time, the capacity supplied by one of the hot water 
Combi-boilers during tapping is the desired capacity and in all 
other cases the initial capacity. 
 
If the difference is not detected, the regulation locks with a ‘P’. 
This lock is removed when the flow temperature goes below 
65°C and the minimum locking time (30 s) has elapsed. 
If this lock occurs more than three times within a heat 
demand, the regulation locks with ‘1’. 
If the difference between flow and return temperatures 
becomes less than –5°C during burning, the regulation locks. 
 
Once per hour, if there is no heat demand, the difference 
between flow and return temperatures must be less than ± 
5°C. If this is not the case, the pump will be switched on and a 

check will be made for a maximum of 10 minutes to see 
whether the temperature difference goes to within ± 5°C. 
 

6.2.9. Frost protection 

When the flow temperature goes below 8°C (if there is no 
heat demand), the pump goes over to the central heating 
circuit and the display shows ‘o’. 
If the flow temperature goes below 3°C, the burner goes to 
low load. 
When the return temperature goes above 15°C, the frost 
protection is finished. 
When an external sensor is connected and the outside 
temperature goes below –4°C, the pump goes to central 
heating. This situation is removed at an outside temperature 
of –2 °C.

 

 

6.2.10. Monitoring the fan speed 

When the measured fan speed deviates from the desired 
speed, this is masked in operation for 10 seconds. After these 
10 seconds, the burner will go out of operation and the post-
ventilation program will be performed.  
When the measured fan speed deviates from the desired 
speed during pre- or post-ventilation, the regulation locks. If 
this lock lasts for longer than 60 seconds, the regulation locks 
with ‘5’. 
When the measured fan speed goes above a maximum value 
during the rest state, the regulation locks. If this lock lasts for 
longer than 60 seconds, the regulation locks with ‘5’. 
 

6.2.11. Glow plug protection 

The glow plug protection counter is incremented at each 
ignition. This counter is decremented per minute. If this 
counter is too high, the burner demand is blocked. 
 

Содержание Coopra

Страница 1: ...MV030204 manual Atmos EN 35_40 E000129013 w pump connection Installation and User Manual Central Heating Boiler 35C Central Heating Boiler 40C Wall hung fan flue room sealed gas boilers E000129013 ...

Страница 2: ...o the Combi boiler 14 2 3 4 Hot water connection to boiler with external storage HWS cylinder 14 2 4 Seal on the waterside 14 2 5 Draconin connection 14 2 6 Electricity connection 14 CHAPTER 3 SUSPENDING THE UNTI 15 3 1 The unit 15 3 2 Suspension 15 3 3 Fitting the flue tube and air supply 15 3 3 1 Connenting the eccentric flue and air supply 2 pipe system 15 3 3 2 Connecting the concentric flue t...

Страница 3: ... without modulating space unit 23 5 2 4 HWS cylinder with thermostat with modulating space unit 23 CHAPTER 6 BURNER STATES and MONITORING 24 6 1 Burner states 24 6 1 1 Rest state 24 6 1 2 Purging Prestart 24 6 1 3 Ignition 24 6 1 4 Operation 24 6 1 5 Post ventilation 24 6 1 6 Functional locking 24 6 2 Monitoring 24 6 2 1 Monitoring the pump circulation 24 6 2 2 Pump programm 24 6 2 3 Pump test pro...

Страница 4: ... 28 8 11 3 Gas control will not open coils defective 28 8 11 4 Gas Air mixture is not correctly adjusted 28 8 11 5 Check glow plug 28 8 11 6 Check ionisation current 28 8 11 7 inspection cleaning replacement of the ionisation probe 29 User manual 30 General 30 Cleaning the unit 30 Holidays 30 Brrrr the central heating is not working 30 Electricity and gas 30 Water and air 30 Other causes 30 Displa...

Страница 5: ...hanger Max Water pressure 3 bar Pump high 40 dB A Sound level Pump low 30 dB A Certification CE Identification number CE0063 AT3070 Boiler type 35 Gas type natural gas G20 natural gas G25 LPG gas G30 G31 Nominal gas pressure 20 mbar 25 mbar 37 50 mbar Heat input CH gross 8 1 38 5 kW Heat input CH net 7 3 34 7 kW Nominal output CH at 80 60ºC 7 2 33 7 kW Nominal output CH at 50 30ºC 7 9 36 1 kW Effi...

Страница 6: ...the top and bottom to be able to suspend the unit and to be able to connect all feed and drain pipes Normally roughly 300 mm is required It is recommended to leave a free space of 150 mm on the left for servicing reasons and 50 mm on the right of the unit The front of the unit must be easily accessible for servicing at all times ...

Страница 7: ... Vapour tray Coopra N00S020015 10 Gas valve Honeywell N00S020009 11 Fan Vibo N00S020006 12 Venturi type 40 Honeywell N00S020008 13 Water pressure sensor Huba N00S080028 14 Return sensor Honeywell N00S070008 15 Flow sensor Honeywell N00S07008 16 Safety device Emmeti xxxxxxxx 17 Float vent Emmeti xxxxxxxx 18 19 Flue gas temperature sensor Tasseron N00S070017 20 Type plate Coopra n a 21 Condensation ...

Страница 8: ...1 1 X16 7 X16 6 X16 3 X16 2 X15 2 X15 1 X15 3 X18 1 X18 3 X17 5 X19 1 X17 2 X19 2 X17 3 ROOM THERMOSTAT 24VAC ROOM THERMOSTAT 230VAC EbV THERMOSTAT OPENTHERM THERMOSTAT PC CONNECTION FLUE GAS OUTSIDE WATER PRESSURE P RETURN DHW INLET EXTERNAL TANK TANK THERMOSTAT GLOW IGNITER L N IONISATION GAS VALVE 230 VRAC COMBUSTION FAN 325 VDC ALARM CONTACT MAXIMAL THERMOSTAT OPTIONAL DISPLAY PE 230V 50 Hz N ...

Страница 9: ...Atmos Heating Systems Installation and user manual EN_FMT 9 1 4 2 Wiring diagram ...

Страница 10: ...to the sewer 1 6 Boiler types Atmos 40C High efficiency boiler for central heating only The Atmos boiler is a heating unit with compact dimensions and a very high efficiency with versions for domestic and small commercial use for central heating The type plate which specifies the type of gas etc to be used for which the unit is set is on the left side of the unit The unit is fixed to the wall with...

Страница 11: ...ogether may not be greater than 125 Pa Indication for the resistance values given in table below apply to a flow rate of 60 m 3 hour dia 80 mm Tube per metre 5 0 Pa Bend 90 R 1 5 D 6 5 Pa Bend 90 R 0 5 D 15 0 Pa Bend 45 R 1 5 D 4 0 Pa Bend 45 R 0 5 D 5 5 Pa Roof duct concentric 1 25 m 30 0 Pa 1 11 Heating of central heating water If the room thermostat or space unit indicates that heat is required...

Страница 12: ...s Regulations applicable to HWS water Ask for the locally applicable regulations at the local water company as they are different in some areas 1 15 General safety regulations The installation may only be performed by a recognised installer Take note that internal parts of the unit can carry a dangerous electrical voltage 230 Volt Take note that the unit the various pipes and the flue gas exhauste...

Страница 13: ...e hole in the wall and fit one of the screws supplied through the assembly bracket in the hole 4 Align the assembly bracket with the aid of a spirit level 5 Use a masonry drill of 8 mm diameter to drill holes with a sufficient depth in the wall through the two bottom holes 2 in the assembly bracket 6 Fit two of the screws supplied in the bottom holes 7 When using assembly brackets with ac lamping ...

Страница 14: ...mined on the basis of the central heating water temperature and the total water content the installation contains If it may be expected that the central heating water will be severely contaminated by under floor heating fitting is a 2 kg dirt filter in the return pipe is recommended Atmos cannot give a guarantee for damage to the unit that is caused by dirt in the system Before connecting the boil...

Страница 15: ...ncentric flue tube and air supply 80 125 mm adapter When the flue tube and air supply are connected concentrically proceed as follows 1 Fit the 80 125 mm adapter on the unit before you place the unit 2 After you have placed the unit fit the concentric pipes on the 80 125 mm adapter 3 3 3 Connecting the concentric flue tube and air supply 60 100 mm adapter When the flue tube and air supply are conn...

Страница 16: ...perature sensor if applicable Connect to terminals 3 and 4 If an external sensor is connected this temperature sensor must be an NTC with a resistance of 12 kOhm at 25 C Strip about 5 mm off the insulation of the wires of the sensor Stick the stripped ends of the wires into connections 3 and 4 of the connection block see figure 8 Make sure that the wires do not make a short circuit Firmly tighten ...

Страница 17: ...o read the water pressure directly from the display To do this press the button of the display for a minimum of 5 seconds The unit switches out of the menu back to normal operation automatically after about 5 minutes or if you press the button of the display shortly 4 5 Venting After filling the heating installation must be vented Proceed as follows Follow the instructions from the manufacturer in...

Страница 18: ...load Activate the chimney sweeper function on low load Read the CO2 value on the analyser If the value does not correspond with the value in the CO2 setting table carefully adjust the gas control adjusting screw 2 To do this temporarily remove the cap 3 with the aid of a Torx screwdriver Turn the screw anti clockwise to decrease the CO2 value on low load clockwise to increase it At the end of the ...

Страница 19: ...nected 1 Flow sensor open circuit Faulty flow sensor Wiring interrupted or not correctly connected 1 Flow sensor short circuit Faulty flow sensor Faulty wiring 2 Return sensor open circuit Faulty return sensor Wiring interrupted or not correctly connected 2 Return sensor short circuited Faulty return sensor Faulty wiring 4 Flue gas sensor open circuit Faulty flue gas sensor Wiring interrupted or n...

Страница 20: ...cked unit dependent unit dependent d t b Set point for storage HWS cylinder 40 C 70 C 60 C external storage vessel O b Basic temperature External characteristic 10 70 C 20 C O S Slope External characteristic 1 100 20 O d Day reference temperature 0 C 70 C 20 C These three settings are only active when an external sensor is connected r Factory setting Factory setting Changed factory setting If you ...

Страница 21: ... to run over the central heating circuit in low load 5 1 2 Central heating temperature regulation with on off thermostat with outside temperature sensor Set point The desired central heating flow temperature set point is calculated on the basis of the measured outside temperature and the O S O d O b parameters set in the menu In formula form Set point of central heating 20 C outside temperature O ...

Страница 22: ...nal temperature of the HWS cylinder There is a burner demand when the flow temperature is lower than 85 C and the return temperature is lower than the desired HWS cylinder temperature With HWS cylinder heat demand the pump state is high 5 2 2 2 HWS cylinder with external sensor with modulating space unit The modulating thermostat will generate a desired HWS temperature value The unit switches the ...

Страница 23: ...on locks with With end of post ventilation purging after the end of the burner demand a start test is run through 6 1 6 Functional locking Fan on off Gas valve off Igniter off Ionisation off Alarm contact on During functional locking the pump is on the central heating circuit At the beginning of the interlock in the fault table is updated With some instances of interlock the fan will post ventilat...

Страница 24: ...e raised by 3 C within 10 seconds after each burner start However if the difference is less than the previous temperature difference the burner is started again after 10 seconds During this time the capacity supplied by one of the hot water Combi boilers during tapping is the desired capacity and in all other cases the initial capacity If the difference is not detected the regulation locks with a ...

Страница 25: ... is no more than 15 of the nominal value the flue gases can be sufficiently exhausted and there is no clogging At the end of the check reset the central heating capacity P in the menu to its customer specific value 7 1 3 Checking the condensation water drain There is an opening for this purpose on the top of the vapour tray First remove the rubber sealing plug rinse the vapour tray and drain with ...

Страница 26: ...exchanged or when no Earth is present Reverse the plug so that the Live is connected to Live and Neutral to Neutral 8 4 Unit does not respond to central heating heat demand Is the parameter for the type of unit correctly set in the menu Parameter H 1 is not active no heating Parameter H 4 is not active no heating Parameter H 5 is not active no heating Check for correct assembly and or cable fractu...

Страница 27: ...gas valve should be measured for resistance the value that the multimeter shows should be about 4 1 kOhm at ambient temperature 8 11 4 Gas air mixture is not correctly adjusted see Chapter 4 Adjustment full load and low load 8 11 5 Check glow plug The 230 volt glow plug is in order if the measured resistance at room temperature is about 1 0 1 4 kOhm remove the connection of the glow plug 230 V con...

Страница 28: ...le makes short circuit with earth The negatively charged ions created by the burner form the ionisation current to earth if there is short circuit to earth the Manager cannot measure any current Repair short circuit 8 11 9 Boiler pump The boiler pump transports the system water through the primary heat exchanger for heating the system If the temperature difference between flow and return is greate...

Страница 29: ...nusual interruption in the gas supply Check by seeing whether a gas cooker in the kitchen is working If it is now working call the gas company The gas flow can also be blocked because the gas filter of the boiler is contaminated this is a problem for the service man The unit also lets the pump regularly run outside the heating season to prevent it from sticking If the mains supply outside is inter...

Страница 30: ...Central heating pump post running d Heat HWS burner off d Heat HWS burner on b Heat external storage vessel burner off b Heat external storage vessel burner on o Frost protection burner off o Frost protection burner on Display of blocks permanent 1 Flow sensor interrupted 1 Flow sensor short circuited 2 Return sensor interrupted 2 Return sensor short circuited 4 Flue gas sensor interrupted 6 Cold ...

Страница 31: ...Atmos Heating Systems Installation and user manual EN_FMT 31 ...

Страница 32: ...o make changes without notification For this reason the instructions given serve only as a guideline for the installation use and maintenance of the unit shown on the cover of this document This document is valid for the unit in its standard version Therefore the manufacturer cannot be held liable for any damage arising from specifications that deviate from the standard version of the unit deliver...

Отзывы: