Version  number:  2026100811 

  Instruction Manual of ATL-991 Addressable Horn/strobe   

------ Please read this Manual carefully before installing and using the product.    ----- 

I. Product overview

 

The ATL-991 addressable horn/strobe(horn/strobe for short) is a kind of product manufactured by our company to be used 
with bus-type fire alarm control units. Controlled by a microprocessor, the  horn/strobe can realize real-time communication 
with a bus-type fire alarm control unit and receive the control commands sent by it. When in a routing  inspection, the red 
status  indicator  will  blink;  after  an  accident  happens,  the  horn/strobe  will  start  to 
operate  after  receiving  a  startup  command  from  the  bus-type  fire  alarm  control  unit. 
The  red  status  indicator  will  remain  lit  and  the  horn/strobe  will  give  a  flashing  signal 
and an audible alarm signal to notify the persons on the scene of the accident that a 
fire has occurred on the site and of the necessity to take related evacuation measures, 
thus preventing the fire accident from becoming a major one. The horn/strobe may be 
restored to the monitoring status after the MUTE or RESET key on the bus-type fire 
alarm control unit is pressed.   
The  horn/strobe  may  be  used  to  give  audible  alarms  and  flashing  alarms  on  the 
scenes of accidents. It is suitable for places like high-rise residential buildings, public 
places, hotels, amusement buildings, factories, shopping centers, hospitals, schools, 
office  buildings  and  stock  exchanges,  particularly  places  with  low  visibility  or  the 
possibility of generation of smoke. 

II. Product features

 

 

It can realize complete electronic coding and in situ rewriting with the help of a coder. 

 

The audible alarm and flashing alarm may be set freely. In other words, the  horn/strobe may give an audible alarm 

and a flashing alarm at the same time or separately and it can be adapted to different working environments.   

 

  Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently.   

 

It uses multiple super bright red LEDs as light sources for visual display, ensuring a striking display, a longer service 

life and low power consumption. 

III. Technical parameters

 

1. 

Executive standard: GA385- 2002 

2. 

  Operating voltage: DC24V (pulse modulation) 

3. 

Operating current: quiescent current: ≤1mA (the current consumed by the bus); alarm current: ≤120mA@DC24V   

4. 

Operating environment: Temperature: 

10

+55

; relative humidity: ≤95% (40

, without condensation) 

5. 

Flushing rate: one time/s 

6. 

Alarm volume: 

85dB (measured at a place 3m in front of the horn/strobe) 

7. 

Coding method: Electronic coding 

8. 

Wiring method: Four-wire system, non-polarity two signal buses (L1, L2) and power lines (+24V, GND) 

9. 

Matched host machine: 

fire alarm control panel (such as ATL-MN300)

 

IV. Appearance and dimensions (see Fig.1)

 

     

Fig.1 