- 18 -
Qc1002™ Menu Description
Status Display (pop-up window)
In case special statuses are entered, a pop-up window will
automatically be entered for as long as the status is active.
The background screen is not updated when the status
pop-up window is active.
These special statuses are:
If a special status has elapsed, the active view will be
entered again automatically.
If an Alarm comes up, the Alarm Display is shown.
Parameter list
The Parameter Menu's are pre-programmed!
A password will be asked for when an attempt to change a
setting is about to be done (user password = 2003).
Menu's shown on the Parameter list LCD:
– Running hours adjust
This menu is used to adjust the amount of running hours. The
running hours can only be highered, not lowered.
– Unit Type
– Service Timer 2 reset
– Service Timer 1 reset
These menus are used to reset the service timers. When a
service timer alarm occurs and is acknowledged, the service
timer will be reset automatically.
– Diagnostic Menu
This menu is used to power up the engine electronics without
starting the engine. When this setting is switched on, electric
power will be supplied to the engine electronics after half a
minute delay. The unit can not be started as long as this
parameter is switched on.
– Unit Menu
This menu is used to select whether tempreature and pressure
should appear in °C/bar or °F/psi.
– Language selection
Icons is the default factory set language, but 6 other languages
can be selected: English, French, German, Italian, Spanish
and Cyrillic (Russian). All information in the Parameter List
display is always in English.
– Generator Underfrequency: failclass, enable, delay,
setpoint
– Generator Overfrequency: failclass, enable, delay,
setpoint
– Generator Undervoltage: failclass, enable, delay, setpoint
– Generator Overvoltage: failclass, enable, delay, setpoint
– Engine CAN communication
This menu is used to select the type of engine electronics, the
Qc1002™ controller should communicate with via the
Canbus.
It's possible to scroll between configuration menu's by
using the pushbuttons UP and DOWN.
Pushing the ENTER button activates the configuration
menu which is shown at the display.
PREHEAT
START OFF/
EXTENDED
STOP TIMER
COOLDOWN
DIAGNOSTIC
Unit type 6 for QAS 250-330 John Deere!
Содержание QAS 250-330 JD T4i
Страница 1: ...QAS 250 330 JD T4i Instruction Manual for AC Generators English ...
Страница 2: ......
Страница 19: ... 19 This is the described menu flow for changing the unit type ...
Страница 63: ... 63 Dataplate ...
Страница 65: ... 65 Circuit diagrams ...
Страница 66: ... 66 1310 3200 12 00 Applicable for QAS 250 330 Qc1002 Engine Circuit ...
Страница 67: ... 67 ...
Страница 69: ... 69 1310 3200 11 00 Applicable for QAS 250 330 Qc2002 Power Circuit ...
Страница 70: ... 70 ...
Страница 72: ... 72 1310 3200 13 00 Applicable for QAS 250 330 Wiring Diagram Control panel wiring ...
Страница 74: ......
Страница 75: ......
Страница 76: ...www atlascopco com ...