Clear 33: Detection of compressor position error (permanent stoppage)
LED
Hydraulic Unit
Outdoor Unit
Green
Red
ÀDVKHV
ÀDVKHV
ÀDVKHV
Probable causes:
Misconnection.
Main PCB failure.
Check:
Clear 33:
1.
&
KHFNFRQQHFWLRQVFRQGLWLRQLQFRQWUROXQLW
:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
OK
2. Replace the electronic board :
-
If steps 1 does not solve the problem, replace Main PCB.
Maintenance document "1546 - EN"
Outoor unit - excellia (duo)
WOYGxxxLCT_WOYKxxxLCT