-If the installation covers 2 zones, set "
2nd circuit kit
" to "
Yes
"
.
2nd circuit kit
No
Easy Start
-Choose the radiator type for each zone:
Low temp. radiator / Heat. floor system / Dynamic Radiators / Radiators.
Low temp. radiator
Easy Start
Emitters type
Area 1 (Direct circuit)
-
If the installation is fitted with cooling function, choose the zone(s)
:
None / Area 1 / Area 2 / Area 1 and 2
.
No
Cooling
Easy Start
-Appliance settings summary screen. Press the knob to accept.
-The appliance starts initialising.
Alféa xxxxxxxxx
x KW
Area 1
Low temp. radiator
3 KW
Electrical back-up
No
2nd circuit kit
Cooling
Area 1
Easy Start
Validate
-The welcome screen is displayed (screen varies depending on installed options).
15:23
12°
19,0°
21,5
ECO
OFF
7 September 2017
Upon commissioning, the electrical backup heaters or boiler are liable to start up even if the outdoor temperature at
the time is above the heaters’ trigger temperature.
The controller uses the initial average outdoor temperature of 0°C and needs time to update this temperature.
- 45 -
alfea Excellia HP Duo A.I. / Installation / 1945 - EN