Liquid
valve
Flare
nut
Flare
nut
Flare
nut
“Liquid” refrigeration connection
diameter D2
“Gas” refrigeration connection
diameter D1
Gas
valve
Flare
nut
Outdoor
unit
Hydraulic
unit
figure 21 - connection of thre refrigerating connectors (authorised diameters and lengths - in metres)
2 .7 .5
Connecting the flare connections
"
The connections must be made the day the gas
is connected to the installation (see §
"
Pay special attention to the position of the tube
aligned with its connector to avoid damaging
the thread . A correctly aligned connector can be
fitted easily by hand without much force being
required .
"
The refrigerating circuit is very sensitive to dust
and humidity, check that the zone around the
connection is dry and clean before removing the
plugs that protect the refrigerating connectors .
-
Remove the plugs from the pipes and refrigerating
connections
-
Place the tube in front of the flare connector and
screw on the nut by hand, holding the connector with a
spanner, until contact is made.
-
Respect the tightening torques stated (see
D
L
PAC Model
alféa hybrid duo oil single phase and three phase
Gas
Liquid
Outdoor unit connectors
5/8"
3/8"
Refrigerating
connections
Diameter
(D1) 5/8"
(D2) 3/8"
Minimum length (L)
5
Maximum * length (L)
15
Maximum * length (L)
20
Maximum ** height difference (D)
20
Hydraulic module connectors
5/8"
3/8"
*
: without additional volume of R410A
**
: take into account any additional volume (see
§
Installation and operating manual
"
1605 - EN
"
alfea hybrid duo heat pump oil low NOx CH
- 20 -