13

To make the performances of your heater last for many years it is necessary to have the equipment inspected

every two years by a specialist, who shall proceed as follows :

3

Maintenance by a specialist

4

Switch off the electricity power supply to the

heater (protection) and disconnect the wires to
the thermostat terminals.

Remove the thermostat and its plastic base

after having disconnected the different wire
bundles.

Drain the tank and disassemble the heating

assembly.

Remove any deposits in the form of sludge or

scale on the bottom of the tank and clean the
ducts of the heating elements and the thermo-
stat. Do not scrape or tap scale stuck to the
walls, since this could damage the coating.

The anode is made of titanium and no inspec-

tion or replacement is necessary.

Reassemble the heating assembly using a new

seal, and tighten the nuts moderately and gra-
dually (crosswise).

Fill the water heater leaving a hot water tap

open; when water comes out of this tap, the
water heater is full.

Check waterproofness at the seal and then

and only then put back the thermostat and its
base and reconnect the electricity power supply.

Check again the next day to make sure that

the seal is not leaking, and retighten the nuts
again slightly if necessary.

Check the condition of accessories and wires.

Clean the sheath inside to remove scale.

In regions in which the water is very hard Th

> 20°F, the use of a softener does not make our
guarantee null and void provided that it is set in
accordance with standard practice, and that it is
regularly checked and maintained.

Proceed as follows when you want to drain

your water heater (operation necessary for des-
caling or if the heater must remain out of ope-
ration in a room in which frost is possible):
a) switch the electricity power supply off
b) close the cold water inlet
c) open a hot water tap
d) open the safety valve drain tap

If there is a problem ,no heating or steam

escapes when the valve is open, switch the elec-

tricity power supply off and inform your instal-
ler.
Note that the water storage temperature used
to be 80°C before.
For safety reasons it is now only 65°C +/- 5 in
the tank. Consequently, the amount of hot water
available with a heater of the same capacity may
be smaller.

To reduce the risk of scalding:
- In toilet facilities, the maximum temperature of
the hot water is restricted to 50°C at the outlet
points;
- In other facilities, the temperature of the hot
water is restricted to 60°C at the outlet points.

3

User recommendations

4

A water heater requires little maintenance for
the user : operating the safety valve regularly
(refer to the manufacturer's instructions).
Check periodically if the pilot light is on. If not,

contact your local installer.

3

Domestic maintenance

4

Содержание ACI Visio

Страница 1: ......

Страница 2: ...eau l abri du gel Le positionner le plus pr s possible des points d utilisation importants S il est plac en dehors du volume habitable cellier garage calorifuger les tuyauteries La temp rature ambian...

Страница 3: ...L L entr e d eau froide est rep r e par une collerette bleue la sortie d eau chaude par une col lerette rouge A l int rieur des tubulures sont ins r s des embouts rouge et bleu qui sont conserver imp...

Страница 4: ...ons de s curit Le raccordement lectrique devra tre conforme aux normes d installation NF C 15 100 ainsi qu aux pr coni sations en vigueur dans le pays o le chauffe eau sera install Label etc PROCEDURE...

Страница 5: ...e certaine quantit d eau afin que la pression interne dans la cuve ne d passe pas 7 bar Cet coulement peut repr senter 2 3 de la capa cit du ballon pendant la chauffe compl te V rifier nouveau l tanch...

Страница 6: ...int rieur du fourreau pour liminer la calamine Pour les r gions o l eau est tr s calcaire Th 20 F l utilisation d un adoucisseur n entra ne pas de d rogation notre garantie sous r serve que celui ci s...

Страница 7: ...p bas Tourner le potentiom tre voir l tiquette de raccor dement dans le capot du chauffe eau Dur e d alimentation lectrique du chauffe eau insuffisante contacteur jour nuit hors service V rifier le bo...

Страница 8: ...ions de garantie4 3Service apr s vente4 Les pi ces du chauffe eau qui peuvent tre rempla c es sont les suivantes le joint de porte l ensemble thermostat lectronique les l ments chauffants fourreau pou...

Страница 9: ...dapt s aux diam tres de ceux ci RISQUES HYDRAULIQUES Pression Les appareils doivent tre utilis s dans la gamme de pressions pour lesquelles ils ont t con us Raccordement vacuation Installer obligatoir...

Страница 10: ...as close as possible to the most fre quently used taps If it is installed in an uninhabited room storeroom cellar garage the pipes should be insulated The conti nuous ambient temperature around the w...

Страница 11: ...ed end The cold water inlet is marked by a blue collar and the hot water outlet is marked by a red collar Red and blue end pieces are inserted in the connecting tubes and must be kept when connecting...

Страница 12: ...the country in which the water heater will be installed Certifying Label etc CONNECTION PROCEDURE Unscrew the locking screw and remove the protective cover which contains the electrical connection dia...

Страница 13: ...certain amount of water to escape so that internal pressure in the tank does not exceed 7 bars This flow may be about 2 to 3 of the capacity of the t a n k when it warms up from cold Check the tightn...

Страница 14: ...ndition of accessories and wires Clean the sheath inside to remove scale In regions in which the water is very hard Th 20 F the use of a softener does not make our guarantee null and void provided tha...

Страница 15: ...e sensor Water not warm enough Thermostat setting too low Turn the potentiometer refer to the connection label inside the cover Power supply time of the water heater insuf ficient day night contact ou...

Страница 16: ...rantee conditions4 3After sales service4 The following water heater parts can be replaced the door seal the electronic thermostat assembly heating elements sheath for ceramic element Please call us fo...

Страница 17: ...sages must be adapted to the diameter of these cables HYDRAULIC HAZARDS Pressure The water heater must be used with the pressure range that it was designed for Connection draining The installation of...

Страница 18: ...t 27 100 st atite 1200 510 865 750 5h40 1 30 1 87 x Capacit 30 150 230V monophas transformable en 400V triphas avec le kit code 100000 ou 230V triphas avec le kit adapt 2 st atite 1800 530 1165 1050 5...