GSCM-mini-d                                                       Automatic Starting for Battery Charging 

 

The GSCM-mini-d can monitor either the generator battery voltage or a battery bank voltage and automatically start/stop the 

generator based on battery voltage. This is accomplished by connecting the battery voltage to the battery sense input 

(terminal 4). The GSCM-mini-d monitors a battery voltage range of 0 to 60VDC and automatically determines the start and 

stop set point based on battery voltage (12, 24, or 48VDC).  Below 16VDC uses 12V thresholds, between 16 to 32V -uses 24V 

thresholds, above 32V - uses 48V thresholds.  This mode is disabled if the voltage on terminal 4 is less than 6V, (no 

connection). 

 

1.

 

The GSCM-mini monitors the battery sense input and when the battery voltage drops below the start threshold the 
Start LED begins blinking every second. When the battery voltage has remained below the start threshold for 5 
continuous minutes the auto start sequence begins. If the battery voltage rises above the start threshold during the 5 
minute period the 5 minute timing cycle starts over. (Temporary battery voltage fluctuations such as instantaneous 
inverter loads will not start the GSCM). The start LED blinks every 3 seconds while the GSCM-mini is running the 
generator in auto-start mode. 

2.

 

The GSCM-mini starts the generator as described on page 3-1: momentary start, 2: maintained start, or 3: ignition 
start. 

3.

 

The GSCM-mini shuts down the generator (as described in relay options 1, 2, or 3) whenever the battery voltage 
exceeds the stop threshold for 10 minutes. The Start LED blinks (every second) during this 10 minute period. The 
GSCM-mini will exit the 10 minute period and shutdown the generator if the battery voltage exceeds the stop 
threshold by +1.0V for a 12V system, 2V for 24V system and 4V for a 48V system. The generator remains off until the 
battery voltage drops below the start threshold voltage. 

4.

 

The GSCM-mini will shut down the generator when it has run in auto-start battery charging mode for 6 hours and has 
not charge the battery above the shutdown threshold. The GSCM-mini then returns to ready mode looking for a start 
command. If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down 
the GSCM-mini will enter a max run time fault condition and lock out the start sequence and requires a power down 
reset. The generator Hz LED will blink 3 quick blinks every 5 seconds and the fault LED is on continuously. 

5.

 

If the user wishes to manual-start the generator from a separate pressure switch, level switch, thermostat or inverter 
start contact, etc., the battery voltage is fed through the switch (pressure switch etc.) contact to manual start 
terminal 5. Closing the contact will cause the GSCM-mini to start the generator. Some inverters provide a switch 
12VDC signal to start the generator. This switched voltage can be connected directly to the manual start terminal 5 
and ground terminal 7.  

 

GSCM-mini-d                                                                   Generator Emergency Shutdown 

 

The GSCM-mini-d Generator Start Stop module is 

NOT AN EMERGENCY SHUTDOWN DEVICE!

 

If the manual start signal is 

removed the generator will go through a normal shutdown which may take up to 15 seconds to completely shut down the 

generator. 

 

A RECOMMENDED EMERGENCY SHUTDOWN SOLUTION is to install a separate kill switch and label it as such. The 

recommended wiring is shown on page-4 of these instructions and also in Option 1. Disconnecting the power to the GSCM-

mini module will force the relays to open. This will shut down generators that require a maintained run signal from K1 relay. 

However this also prevents the K2 relay from closing to shut down those generators requiring a momentary stop signal. Using 

a double pole kill switch and wiring the second pole in parallel with the K2 relay terminals will force the generator to stop in 

an emergency situation such as a fuel spill. (See note 1 on wiring diagram, page 4, for Ignition/ crank emergency shutdown 

option). 

 

Содержание GSCM-MINI

Страница 1: ... Module Part GSCM mini d ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 Contact cbdsales atkinsonel com for the proper hookup diagram Please include the generator make model inverter brand battery bank voltage ...

Страница 2: ... and optional battery charging thresholds Maximum auto start run time limit 6 hours Remote run and fault indication included ABS epoxy sealed for harsh environment operation Solving your generators 2 to 3 or 4 wire start stop problem Description The GSCM mini d is a micro processor based generator start stop module designed to auto start stop diesel generators that need a 3 or 4 wire connection fr...

Страница 3: ...ication Description The GSCM mini d has six indication LEDs The Start LED blinks once every 5 seconds to indicate it is ready for a start signal The LED will blink once every 2 5 seconds to indicate its running in auto start mode On continuously indicates running in manual start mode The Generator Hz LED blinks to indicate over under Hz fault and start failure due to maximum crank attempted A slow...

Страница 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 11 2020 GSCM mini d Wiring Diagram Example ...

Страница 5: ...lay provides a momentary stop signal until the generator AC Hz has dropped to zero For GSCM mini operational sequence details see page 7 option 2 A double pole kill switch wired and installed by the user stops the generator instantly in emergency situations such as a fuel spill One switch pole N C kills power to the GSCM mini opening all relays The other switch pole N O shorts out the magneto for ...

Страница 6: ...oes a double blink the fault LED turns on and the GSCM mini enters the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini wiring diagram page 4 This clears the lockout condition and the GSCM mini re enters ready mode with the start LED blinking every 5 second...

Страница 7: ...zed A valid run condition is determined by one of two conditions a 12V run status pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned on 4 If the generator starts but shuts down after a few seconds due to a fuel problem etc The GSCM mi...

Страница 8: ...on is determined by one of two conditions A 12V run pilot light signal provided by the generator connected to terminal 8 or by the generators AC output frequency exceeding the crank disconnect setting of 45Hz terminals 9 10 and is indicated by the run LED being turned ON 5 If the generator starts but shuts down after a few seconds due to a fuel problem etc the start sequence will revert to the rea...

Страница 9: ...blinks during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini monitors the generators output frequency and if it drops below the 55 Hz fixed threshold for 10 seconds the generator shuts down and the generator Hz shutdown LED blinks slowly The generator Hz LED blin...

Страница 10: ...y voltage drops below the start threshold voltage 4 The GSCM mini will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown threshold The GSCM mini then returns to ready mode looking for a start command If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down the GS...

Страница 11: ...ion and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescent current 10mA Relay current 25mA each Manual Input B 12VDC input on condition Open input off condition Battery Input 0 60VDC Auto Start Stop Threshold 12V System 11 5V 13 8V 24V System 23 0V 27 6V ...

Страница 12: ...te switch is turned on the GSCM mini starts the generator After the generator starts and comes up to speed the run LED lights on the GSCM mini and turns on the remote start switch lamp If the generator fails to start or fails while commanded to run the fault LED on the GSCM mini lights along with the remote fault 12VDC lamp Turning off the power to the GSCM mini resets the fault condition and it i...

Страница 13: ...ections to connect the GSCM mini d s start and stop pre heat contacts and the AC output makes for an easy installation When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay which energizes the two relays are used to isolate the glow plug circuit from the shut down circuit causing the glow plug to heat After 10 seconds it energizes the K1 relay to sta...

Страница 14: ...ators use a positive reference B for their control switch and remote terminal input The generators AC output is used as a run feedback signal to know when the generator has started and when it shutdown When the GSCM mini d receives a start run command from the Outback inverter it energizes the K2 relay to heat the glow plugs After 10 seconds K2 de energizes and K1 energizes to start the generator ...

Страница 15: ...s with an additional relay The GSCM mini monitors the generators AC output to know when to disengage the starter and when the generator has shutdown either by command or by fault When a start signal is received the GSCM mini starts the generator after the generator starts and comes up to speed the run LED lights on the mini If the generator fails to start after 3 starting attempts or fails while c...

Страница 16: ... from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to ma...

Отзывы: