GENERATOR EMERGENCY SHUTDOWN WITH THE GSCM-mini-D

SECTION - 7  

  

The GSCM-mini-D Generator Start Stop module is 

 NOT AN EMERGENCY SHUTDOWN DEVICE!!

  If  the manual start signal is

removed the generator will go through a normal shutdown which may take up to 15 seconds to completely shutdown the generator.

  

A RECOMMENDED  EMERGENCY SHUTDOWN SOLUTION is to install a separate “Kill” switch and label it as such.  The
recommended wiring is shown on page-2 of these instructions and also in Application 1.  Disconnecting the power to the GSCM-mini-D
module will force the relays to open.  This will shutdown generators that require a maintained run signal from K1  relay.  However this
also prevents the K2  relay from closing to shutdown those generators requiring a momentary stop signal.  Using a double pole “Kill”
switch and wiring the second pole in parallel with the K2  relay terminals will force the generator to stop in an emergency situation such
as a fuel spill. (see note 1 on wiring diagram, page 2, for Ignition/crank  emergency shutdown option). 

 

LED DESCRIPTION (WHAT THEY MEAN)

SECTION - 8

  

1.

Start:

one blink every 5 seconds = Ready mode, looking for a start signal;
one blink every 2.5 seconds = auto start mode operation;
one blink every other second= auto start/stop period,
continuous = manual start signal received;
fast blink = 60 second delay after start signal removed before generator started;

  

2.

Generator

 

Hz

fast blink = over speed condition;

Shutdown:

slow blink = under speed condition;
double blink = Maximum Crank attempts reached, Failed to Start;
triple blink = Auto start attempted with-in 30 minutes of a Max run time (6 hour ) shutdown;
Four blinks every 2 seconds = Ac Hz or 12v run status signal lost during run mode;  
continuous = start function disabled, AC Hz detected while in ready mode;

  

3.

Run:

continuous = GSCM has a valid run signal from generator;

4.

Fault:

 

continuous = GSCM is in a fault condition and requires a reset;

5.

K1 & K2:

continuous = Status of K1 and K2 Relays “ON”

  

SPECIFICATIONS

 

SECTION - 9

  

SIZE & WEIGHT:

5.13" L x 2.853" W x 1.35" H, 20oz.

  

MOUNTING:

2 screws through tabs

  

POWER:

12VDC Battery (9.5 to 15VDC)  
Quiescent current < 10mA
Relay current < 25mA ea. 

  

MANUAL INPUT

:

B+ (12VDC) input = on condition
Open input = off condition

  

BATTERY INPUT:

0-60V DC

  

AUTO START/

 Start

 Stop

STOP THRESHOLD:

12V System

 11.5V,  13.8V

24V System

 23.0V,  27.6V

48V System

 46.0V,  55.2V

  

  

RELAY CONFIG.:

Open input = Momentary Crank

(Terminal 6)

Grounded input = Maintained Crank
B+ (12VDC) input = Ignition & Crank

  

Gen. Hz Enable:

Open input = Gen. Hz shutdown not active

(Terminal 8)

Grounded input = Gen. Hz shutdown active
12VDC input = Generator run Status input,
Over/Under Hz shutdown not active

   

FREQUENCY INPUT

: 24VAC, 120VAC & 240VAC  0-100 Hz

(Terminals 9 & 10)

   

OUTPUT RATINGS:

Qty.  (2) 10 Amp 28V DC relay
contacts,  K1 has 38vdc MOV
across contact
Qty. (2) Open collector NPN
transistors, Max. 300mA each

   

FAULT DETECTION:

Start Failure, (3 attempts) 
Over Hz condition (10 seconds)
Under Hz condition (10 seconds)
Max Run time (6 hours)
Loss of AC Hz or 12V run status
signal

  

AMBIENT TEMP

:

-40 to 85

8

C  

Содержание GSCM-MINI-D

Страница 1: ...Section 1 for operation description Maintained Start Contact Option 2 terminal 6 is grounded The GSCM mini D changes to a maintained start operation for generators that use a maintained closed contac...

Страница 2: ...RATOR START CONTROL MODULE MINI 2 Wire to 3 Wire GSCM MINI D ATKINSON ELECTRONICS INC REV 07 08 Web Site www atkinsonelectronics com Distributed by GSCM mini D WIRING DIAGRAM AND CONTROLLER CONFIGURAT...

Страница 3: ...wired and installed by the user stops requiring a maintained start signal The K2 relay provides a the generator instantly in emergency situations such as a fuel momentary stop signal until the genera...

Страница 4: ...fuel problem etc the start sequence will revert to the Ready mode after a 60 second delay During this delay the start LED will blink rapidly The GSCM mini D will then try to start the generator again...

Страница 5: ...remains closed until either the generator starts or the maximum cranking time period 20 seconds is reached 2 If the generator fails to start after the 20 seconds cranking period K1 relay opens for a...

Страница 6: ...RTING FOR BATTERY CHARGING SECTION 6 The GSCM mini D can monitor either the generator battery voltage or a battery bank voltage and Automatically start stop the generator based on battery voltage This...

Страница 7: ...elay after start signal removed before generator started 2 Generator Hz fast blink over speed condition Shutdown slow blink under speed condition double blink Maximum Crank attempts reached Failed to...

Страница 8: ...long with the remote fault 12vdc light Turning off the power to the GSCM mini resets the fault condition and it is ready to receive another start command APPLICATION 3 GenMate PC BOARD REPLACEMENT The...

Страница 9: ...ch appear within two 2 years from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option...

Отзывы: