Notice technique complète sur
www.atim.com
FRQIG_ARM-IOD-LP
Page3/4
The modbus mode is frequently used with a master
modbus automaton or with a supervisor connected to an
ARM-IOS or an ARM-SE.
The sensor mode works with master ARM-SE radio
modem, which can repatriate automatically and cyclically
the information (datalogging). Data are then searchable
in mdbus.
Vous pouvez utiliser les ARM-IO avec les autres modems
de la gamme ARM : ARM-SE, ARM-D, ARM-DA, ARM-X,
etc.
2.3.
Frequency table
Channel
Frequency (MHz)
Default powerful
Duty cycle
Range
1
868,075
25mW
1%
<1km
3
868,175
5
868,275
7
868,375
9
868,475
D (13)
869,475
25mW
10%
<1km
F (15)
869,575
3.
Technical characteristics
ARM-IOD-LP
Characteristics
Interface
2 digital inputs
Logical input
Negative logical
Max frequency counting: 100Hz
Delay
“Wake-up” delay : 1,55
Answer delay : 3,55
Operating modes
Modes : mirror, Modbus, sensor
Configuration
Automatic
Power supply
3,6V battery withdrawable
Max consumption
25mA (Rx) – 60mA to 25mW (Tx) – 15µA in sleep mode
Frequency radio
868,000 à 869,900MHz – Puissance max 25mW
Radio
Modulation FSK – Debit : 9600
Range
As far as 1km en outdoor
Connection
6 points bloc connector (screw thread : 2,54mm)
Box
ABS (IP65) : 65x60x40mm (without antenna)
Functioning/storage
temperature
-20°C to +55°C / -40°C to +70°C
Conformity
ETS300-220-3 v1.1.1 / EN 301 489-3 v1.4.1
4.
CONFIGURATION IN MODBUS MODE
The modem configuration can be made in the manufactory.
For erasing the modem configuration:
– Disconnect the battery
– Run down the remaining voltage in shorting circuit the + and the - of the battery connector
ARM-IO
are
provided
with
a
performing sleep mode (configuration
only with modbus commands. See the
use manual).
In mirror mode, the radio frame is
secured with addressing (last octet
of the serial number) and with an
error controller. By default the
ARM-IO is configured in slave mirror
mode. After configuration and
switch on, the modems will
automatically pair each other.