ATI
Q46H/65 Residual Chlorine Dioxide System
Part 4
– Electrical Installation
26
O&M Manual
Rev-J (11/18)
4.5
Junction Box Connection
Installations where the sensor is to be located more than 25 feet from the monitor (max. 100 feet)
require the use of a junction box. The junction box is shown in, and is supplied with two cable
glands on the bottom of the enclosure.
Note:
If sensor is experiencing Low-Slope or Low-Output conditions, due to poor Earth
Ground Connections, move the Shield connection from P/S board to alternate
location on lid, where indicated with an
“S”.
Figure 19 - Junction Box Interconnect Wiring
Note
: The
BLUE
wire is
NOT
used when connecting a Flow or
Submersible style Probe to the
analyzer