Model F12/D Gas Transmitter
Part 4
– Operation
52
O&M Manual (Rev-H)
Alarm Setting Menus
The Alarm Setting Menus are accessed from the Alarms Menu and are used to configure the three gas
level alarms.
Figure 69. Alarm Setting Menus
Item
Select to…
Type
Set the type of alarm as
High
,
Low
, or
None
. When set to
High
, the alarm becomes
active
at and above
the
Set Level
. When set to
Low
, the alarm becomes active
at
and below
the
Set Level
. Setting the value to
None
permanently deactivates the
alarm. The setting is stored in the sensor memory.
Set Level
Set the gas concentration level at which the alarm becomes active. The alarm then
becomes active at the expiration of the
Set Delay
period. Changing
Set Level
changes
Res Level
to the same value. Limits for the
Set Level
are maintained in
the gas sensor memory.
Res Level
Set the gas concentration level at which the alarm becomes inactive. The alarm then
becomes inactive after expiration of the
Res Delay
period, and only if the
Reset
setting is programmed as
Auto
– see below. The limits for the
Res Level
depend
on the alarm
Type
setting.
Type
=
High
Upper limit =
Set Level
Lower limit = lowest
Set Level
Type
=
Low
Upper limit = highest
Set Level
Lower limit =
Set Level
Changing
Set Level
changes
Res Level
to the same value.
Type= High
Set Level= 20.0
Res Level= 20.0
►More
Type= High
Set Level= 10.0
Res Level= 10.0
►More
Type= Low
Set Level= -10
Res Level= -10
►More
►Reset=Manu
On Trouble=HOLD
Set Delay=0
…Alarms>Alarm
►Reset=Auto
On Trouble=HOLD
Set Delay=0
Res Delay=0
►Reset=Auto
On Trouble=HOLD
Set Delay=0
Res Delay=0
…Alarms >Warning
…Alarms >Caution
…Alarms>Alarm >More
…Alarms>Warning >More
…Alarms>Caution >More
>Menu>Setup>Alarms
Alarms
►Alarm Inhibit
Warning Test
Caution