The architecture with a closed control loop makes it possible to connect more detectors to the control
module and to carry out the system test directly from the control unit, which is infeasible in case of an open

control loop. Details of these procedures are described in Section 8.3.

8

Life cycle

8.1

Transport

The device can be shipped in the same way as new equipment of that type. If the original package or

another protecting means (e.g. corks) is unavailable the conveyed equipment must be secured against
shocks, vibrations or moisture by means of adequate methods and material at the own responsibility of the

sender.

8.2

Installation

The control unit should be installed inside a control cabinet on the DIN35 rail or inside a terminal box. The
mounting position should be as shown in Figure 1The device must be easily accessible to authorized staff

but, if possible, access of third and unauthorized persons should be prevented. It is recommended to install
the device at an appropriate height to enable unobstructed access to the device. 
If electric connections are made by means of multi-wire conductors (commonly referred to as a strand),

conductor ends must be secured by means of terminal sleeves. 
When   two   conductors   are   to   be   connected   to   a   single   terminal   clamp   of   the   device   they   must   be
encapsulated first within a common clamping bushing (lug) – see details in Table 3.

It is unacceptable to combine in one connector two wires which are not pinched in one cable

lug.

8.3

Commissioning

8.3.1

Test for the system with a closed control loop

The systems that include the Control Unit Module Alpa MOD LED1 collaborating with the Alpa EcoWent XT,
Alpa EcoDet XT or  Alpa EcoTerm XT mutually connected within a closed current loop are capable of

executing a test of that loop upon any request of the system operator. To initiate the test please held and
depress for 15 seconds the both buttons PAMIĘĆ (MEMORY) and POTWIERDZENIE (ACK). Start of the test

shall be signalled by a short sound beep with activation of the yellow TEST indicator lamp and deactivation
of the PRACA (OPERATION) LED. Successful passing of the test by the device is indicated by activation of the

red indicator light   ALARM. Testing of the system takes about 1 minute and afterwards the unit indicates
its return to the regular operation mode. Should the ALARM indicator light fails to go on it means that the

unit failed the test. If so, check connections of the gas detectors with the control unit, make sure that
jumpers are in correct positions and start the test once again. Should subsequent tests fail as well, please

contact the equipment manufacturer. 

Test of the gas monitoring system is only possible when the control unit is in the PRACA
(OPERATION) mode. For systems with an open control loop such a test is infeasible.

s. 10|13

User Manual: POD-015-ENG R02

 

Содержание Alpa MOD LED1

Страница 1: ...POD 015 ENG R02 Control Unit Module Alpa MOD LED1 Product code PW 023 A User Manual...

Страница 2: ...ring Detection and Reduction of gas hazards We invite you to familiarize yourself with our offer on www atestgaz pl Atest Gaz A M Pachole sp j ul Spokojna 3 44 109 Gliwice Poland tel 48 32 238 87 94 f...

Страница 3: ...nts during the entire lifetime of the product Use of unauthorized spare parts different from the ones listed in Table 4 is strictly forbidden How to use this manual The following symbols of optical in...

Страница 4: ...Product marking 13 12 Appendices 13 List of Tables Table 1 Optical indicators status notation 3 Table 2 Electric connections description 8 Table 3 Technical specification 12 Table 4 List of consumable...

Страница 5: ...s analysis of signals received from detectors dissemination of warning and alarm signals monitoring and troubleshooting of the system 2 Safety All activities related to connecting detectors signallers...

Страница 6: ...n intermittent beep will be emitted which can be blocked by pressing and holding for a few seconds the CONFIRM button the OC WARNING signal is enabled to control the external optical signaller R1 WARN...

Страница 7: ...f the device is confirmed by continuous light of the OPERATION and SUPPLY controls When any irregularity of the system operation lead to short term presence of any following status FAILURE ALARM WARNI...

Страница 8: ...riate terminals S Signaller to the terminal OC Output 12V OC1 OC2 Control Unit Module Alpa MOD LED1 has 4 relays with potential free contacts that can be used to control automation systems signalling...

Страница 9: ...nection of peripheral equipment to the Control Unit within a closed control loop Please refer to Appendix 2 for details about the number of detector that can be connected within the open loop control...

Страница 10: ...ulated first within a common clamping bushing lug see details in Table 3 It is unacceptable to combine in one connector two wires which are not pinched in one cable lug 8 3 Commissioning 8 3 1 Test fo...

Страница 11: ...e reliably secured during any repair installation or maintenance works 8 5 Utilization This symbol on a product or on its packaging indicates that the product must not be disposed of with other househ...

Страница 12: ...cted Integrated signalling equipment visual LED controls Integrated signalling equipment optical 75 dB 1 m distance Dimension See Figure 1 Acceptable cables 1 2 mm2 cable lugs 2 x 1 mm2 or 2 x 0 75 mm...

Страница 13: ...pa MOD LED1 Table 5 Method of product s marking 12 Appendices 1 DEZG025 ENG EU Declaration of Conformity Alpa MOD LED1 2 PU Z 098 ENG Maximum quantity of Alpa EcoWent XT and Alpa EcoDet XT detectors b...

Страница 14: ...igned for use within certain voltage limits EN 60335 1 2012 In relation to directive 2011 65 EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment EN...

Страница 15: ...6 17 168 738 20 186 636 16 207 747 19 229 649 15 1 5 62 872 28 81 741 23 94 874 27 115 745 22 128 878 26 150 750 21 163 883 25 188 758 20 200 890 24 229 769 19 2 5 69 1389 45 53 1193 39 100 1390 44 84...

Страница 16: ...5 45 555 18 42 462 15 77 557 17 74 464 14 111 561 16 109 469 13 146 566 15 146 476 12 184 574 14 187 487 11 224 584 13 234 504 10 2 5 35 725 24 28 598 20 66 726 23 59 599 19 98 758 22 91 601 18 132 7...

Страница 17: ...56 12 98 378 10 153 464 11 138 387 9 197 477 10 183 432 8 245 494 9 237 424 7 2 5 66 636 20 52 532 17 99 639 19 84 534 16 133 643 18 118 538 15 169 649 17 154 544 14 Table 3 Maximum quantity of sets o...

Страница 18: ...26 212 812 21 1 5 50 1130 36 55 955 31 82 1132 35 87 957 30 115 1135 34 120 960 29 149 1139 33 155 965 28 184 1144 32 192 972 27 220 1150 31 230 980 26 2 5 47 1877 62 56 1616 53 78 1878 61 87 1617 52...

Страница 19: ...14 207 507 11 1 5 67 697 22 68 578 18 99 699 21 101 581 17 133 703 20 137 587 16 169 709 19 174 594 15 207 717 18 215 605 14 2 5 51 951 31 65 785 25 82 952 30 98 788 24 115 955 29 131 791 23 148 958 2...

Страница 20: ...05 14 108 605 17 139 512 13 144 610 16 181 523 12 184 619 15 228 539 11 227 631 14 2 5 24 834 28 38 698 23 55 835 27 70 700 22 87 837 26 103 703 21 120 840 25 137 707 20 154 844 24 173 713 19 Table 6...

Страница 21: ...Gas Detector at the end of the line L2 m L2 m 0 75 1400 1400 1 1400 1400 1 5 1400 1400 2 5 1400 1400 Table 7 Maximum length of cables star configuration Atest Gaz A M Pachole sp j ul Spokojna 3 44 10...

Страница 22: ...13 155 425 10 187 517 12 198 438 9 229 529 11 248 458 8 2 5 39 669 22 42 552 18 72 672 21 74 554 17 104 674 20 108 557 16 137 677 19 142 562 15 172 682 18 179 569 14 Table 1 Maximum quantity of Alpa...

Страница 23: ...882 28 72 732 23 104 884 27 104 734 22 139 889 26 138 738 21 171 891 25 174 744 20 207 897 24 211 751 19 Table 4 Maximum quantity Alpa EcoTerm XT detectors closed loop configuration Atest Gaz A M Pac...

Страница 24: ...line L2 m 1 1400 1 5 1400 2 5 1400 Table 7 Maximum length of cables star configuration Atest Gaz A M Pachole sp j ul Spokojna 3 44 109 Gliwice Poland VAT No PL 9691433231 tel 48 32 238 87 94 fax 48 32...

Страница 25: ...p j ul Spokojna 3 44 109 Gliwice Poland VAT No PL 9691433231 tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl Appendix PU Z 021 ENG R01 s 1 1 T connector XT T connector XT Bipolar ov...

Страница 26: ...j ul Spokojna 3 44 109 Gliwice Poland VAT No PL 9691433231 tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl Za cznik PU Z 025 ENG R01 s 1 1 T connector XT T connector XT Power Suppl...

Страница 27: ......

Страница 28: ...M Pachole sp j Spokojna 3 44 109 Gliwice tel 48 32 238 87 94 fax 48 32 234 92 71 e mail contact atestgaz pl For more details on our devices and other products and services offered by us visit www ate...

Отзывы: