The
Configuration
page is used to configure the settings of the PE8208AV at
the individual power outlet level:
POP Settings
This section allows you to enable Proactive Overload Protection (POP).
Proactive Overload Protection is triggered when a PDU’s or Outlet’s
Current
Max Threshold setting is exceeded. Effective on all outlets, this
added safety feature automatically powers off outlets according to the
settings below:
Enable Outlet POP
checking this box triggers Proactive Overload
Protection to power off an outlet when it’s
Current
Max Threshold
setting is exceeded (see page 33).
Enable Bank POP LIFO Mode
checking this box triggers Proactive
Overload Protection to power off a newly inserted device (LIFO),
when it causes the PDU’s
Aggregate Current
Max Threshold setting to
be exceeded (see page 31). All other outlets stay powered on.
Enable Bank POP Priority Mode
checking this box triggers
Proactive Overload Protection when the PDU’s
Aggregate Current
Max Threshold setting is exceeded (see page 31). This will power off
outlets according to the
Bank POP Priority List
settings (see page 37).
For more information about how the POP Settings work together, see
Содержание PE6208AV
Страница 1: ...PE6108AV PE6208AV PE8208AV 8 Outlets eco PDU User Manual www aten com...
Страница 20: ...PE6108AV PE6208AV PE8208AV User Manual 10 This Page Intentionally Left Blank...
Страница 76: ...PE6108AV PE6208AV PE8208AV User Manual 66 This Page Intentionally Left Blank...
Страница 91: ...Appendix 81 Do not connect the RJ 11 connector marked Sensor to a public telecommunication network...
Страница 112: ...PE6108AV PE6208AV PE8208AV User Manual 102...