Parameter Setup (
V.2W2KPV105
)
After power off and remove the backboard and clapboard from the main part as shown in
fig. 2
. There are 4 Dipswitches in the circuit board as following:
DIP1: ON-Parameter setup OFF- User operation Leaving Factory
:
OFF
DIP2: ON- Fahrenheit OFF- Celsius Leaving Factory
:
OFF
DIP3
:
ON- The analog output is direct proportion linearization
OFF- The analog output is PID adjustment (Please refer to Item -23 at table below) Leaving Factory
:
OFF
DIP4
:
ON- with an analog output OFF- without an analog output Leaving Factory
:
ON
Dipswitch
up
is
on
and Dipswitch
down
is
off.
Press
switch
key to switching parameters and press
▼▲
keys to setting. After setup, DIP1 must be put to OFF.
Display
on LCD
Parameter
Range of setup
Default
-00
Device Version
1105
-01
Device ID
1~255
1
-02
Device Baud Rate
4800,9600,14400,19200,38400
19200
-03
Device Stop and Parity Bits
1-None 1Stop;
2-None 2Stop;
3-Odd 1Stop; 4-Even 1Stop
1
-04
The slight temp. difference of starting / closing analog output
(
just for DIP3=OFF,DIP4=ON, -23=1
)
0.5~3.0C/0.9~4.5F
1.0C/2.0F
-05
Adjusting the brightness of 3-lights
0~1023
50
-06
CO2 modification Aim
0~ The maximum of
CO
2
measurement and setting
(Please refer to Item -22)
0
-07
Temp. modification Aim
0~60C/32~140F
25.0C/77F
-08
Humidity modification Aim
5~95%RH
50%RH
-09
The lowest voltage of the analog output (just for DIP3=OFF)
0~the highest analog output
2.0
-10
The highest voltage of the analog output (just for DIP3=OFF)
the lowest analog output~10.0
10.0
-11
Response rate of analog output (just for DIP3=OFF)
1~200
(the smaller the value, the quicker the response)
20
-12
0: analog output is 0 when CO2 detecting value < setting value
1:analog output is the setting lowest voltage when CO2 detecting value < setting value (just for DIP3=OFF)
0
-13
When it used as a transmitter, analog output linearize with CO
2,
the output voltage which corresponds with 0ppm
0~9.0
(corresponding 0~9V
)
0.0
e.g. the setting value is 2.0 and CO
2
measuring range is 0~2000ppm, DC 2V output corresponds with 0ppm and DC10V with
2000ppm
-14
Preheating time for
CO
2
sensor
(before
CO
2
sensor steady, no analog output)
1~600 seconds
60s
-15
State of the monitor when power on again after power broken.
0
:
Turn off after power on again 1
:
Turn on after power on again 2
:
Keep on previous state before power broken
2
-16
CO2 Elevation Calibration
Warning: if you change this item, please wait a few seconds after
the icon "
——
" disappear on the LCD, then the new setting will
prevail.
press
▼
or
▲
more than 20 seconds to perform CO2 Elevation
Calibration.
0~
5000
Feet
0
-17
CO2 ABC Logic
Warning: if you change this item, please wait a few seconds after
the icon "
——
" disappear on the LCD, then the new setting will
prevail.
press
▼
or
▲
more than 20 seconds to perform CO2 ABC Logic
1-Enable
2-Disable
1
-18
CO2 Single Calibration
Warning: if you change this item, please wait a few seconds after
the icon "
——
" disappear on the LCD, then the new setting will
prevail. Press
▼
or
▲
more than 20 seconds to perform CO2
Single Calibration
Please note:
1. Make sure to place the CO2 controller in an environment
where CO2 concentration is stable.
2. After CO2 single point calibration process is completed, please
keep the CO2 controller in the same environment until the
CO2 measurement value displayed turns into the target CO2
value of CO2 single point calibration.
3. If CO2 concentration of the calibration environment is not
stable, or if the CO2 controller is moved away before its CO2
measurement display reaches the target value, then there might
be serious distortion to future CO2 measurements.
0~50000
450
-19
CO2
modification;
CO
2
reading calibration at a certain point
between the monitor and a standard
CO
2
gas sample. The
calibration can only be used in a small range.
-500~500PPM
0 PPM
-20
Temp modification
-118.0~100.0C/-212~212F
0
-21
Humi. modification
-100~100
0
-22
The maximum of
CO
2
measurement and setting
1000~20000ppm
2000
-23
Temp. controlling
’s feasibility
(
just for DIP3=OFF,DIP4=ON
)
0: PID anolog output;
1: PID anolog output when detect temp.< (setting temp.
- temp. differential); Anolog output maximum when
detect temp.>(setting temp.-temp. differential)
1
Note: The numbers blinking indicates it being setup, the numbers stop to blink to indicate the parameter confirmed.
RESET:
Put the DIP1 to ON and press
switch
key for about 25 seconds until the monitor is off, then all the setting values return to the factory default..