![Atag IS 12 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/atag/is-12/is-12_installation-and-servicing-instructions-manual_2995195014.webp)
Installation & Servicing instructions ATAG iS-Range
14
The boiler is NOT equipped with a built-in internal filter.
Advice: ATAG Heating Technology Ltd recommend the installation of an in-line filter installed into the
heating return as close to the boiler as possible. ATAG Heating Technology Ltd recommend the use
of the:
ATAG iGuard Magnetic filter 22mm (Plastic) FC000100, (Brass) FC000200, 28mm (Brass) FC000250.
The boiler is not suitable for installations that are equiped with “open” expansion tanks.
Additives in the installation water are only permitted in consultation with the country distributor. See
chapter 9.3 for detailed information.
9.2 Expansion vessel
The iS boilers are featured with a built-in expansion vessel with a capacity of 8 litres and a pre-pressure
charge 1 bar. If the expansion vessel size is insufficient for the CH system, an additional expansion must be
installed. The additional expansion vessel should, together with the built-in expansion vessel, be sized to the
water content of the installation. The pre-pressure charge depends on the height of the installation above the
installed expansion vessel. See Table 9.2.a.
The (additional) expansion vessel should be connected as closely as possible in the return pipe near
the boiler.
Installation height above the expansion vessel
pre-charge pressure of the expansion vessel
5m
0,5 bar
10m
1,0 bar
15m
1,5 bar
table 9.2.a
The pressure relief valve outlet is combined with the condensate outlet (see figure 9.8.e on page 29).
9.3 Water quality
Fill the installation with mains cold water.
In most cases, a heating system can be filled with water according to national standards for water and
treatment of this water is not necessary.
In order to avoid problems with the CH-installations, the quality of the filling water has to meet the
specifications mentioned in table 9.3.a:
If the filling water does not meet the required specifications, you are advised to treat the water to such an
extent that it does meet the required specifications.
The warranty becomes invalid, if the installation is not being flushed and/or the quality of the filling
water does not meet the specifications recommended by ATAG Heating Technology Ltd. Always
contact ATAG Heating Technology Ltd in advance, if things are not clear or you wish to discuss any
deviations. Without approval, the warranty becomes invalid.
Installation:
- The use of groundwater, demi-water and distilled water is prohibited. (on the next page you will find an
explanation of these definitions)
- If the mains water quality meets the specifications mentioned in table 9.3.a, you can start flushing the
installation before installing the device.
- Whilst flushing, corrosion products (magnetite), fitting products, cutting oil and other undesirable products
have to be removed.
- Another possibility is to remove the pollution by installing a filter. The filter type has to fit the type and
grain size of the pollution. ATAG Heating Technology Ltd recommends filter usage.
- In this case, the whole piping system should be taken into consideration.
- The CH-installation has to be properly vented before using the system. For that purpose, we refer to the
commissioning chapter.