HOW TO INSTALL THE PRODUCT

(Left side of the Reservoir)

Installation at the

lower left

(Right side of the Reservoir)

Installation at the

lower right

(Left side of the Reservoir)

Installation at the

lower left

(Right side of the Reservoir)

Installation at the

lower right

Select location at the

lower left or right of the

air conditioner.

Make holes in the wall

according to the location for

installation and then fix the pump

with bolts and anchor.

* The default product condition is for the lower right installation. 

When installing on the left, move the rubber part to the opposite side

as shown in the figure, assemble it, and then install it so that the

location of the resorvoir is on the left.

(The marked rubber parts should always have 4 on the front and 2 on the rear.)

Insert the air conditioner drain hose all the way into the reservoir and connect the

pump's discharge hose to the external drain hose. 

(At this time, be careful that the

air conditioner drain hose does not interfere with the water level sensor inside the 

product water container.)

- Hose standard: 6mm or 1/4" (inner diameter) x 9mm or 3/8" (outer diameter) 

- Be careful not to kink or pinch off the hose bended.  

Connect the power cable of the pump to the rated power. Power should be 

continuously supplied to this equipment except when maintenance or follow-up 

service is carried out after installation of this equipment. 

Safety switch installation method 

(Optional)

After cutting one line of the temperature sensor in the indoor unit of the 

air conditioner. connect COM and NC of the safety switch lead wire to the line 

respectively in order to prevent a possible water overflowing. This will shut off the 

compressor of the outdoor unit of the air conditioner when the drain pump runs 

abnormally, making no additional condensate water generated any more.

* It is possible to connect the lead wire of the safety switch to the control circuit of 

the air conditioner. However, the configuration of circuit is different depending on 

the manufac turers of the air conditioner, please be sure to connect the lead line of 

the safety switch to the control circuit with the help of an installation expert of the 

relevant air conditioner.  

AC (Light blue: COMMON)
AC (Brown: HOT)
Alarm (Brown: COM)
Alarm (Black: N.C.)

Air Conditioner

External drain hose

Pump’s discharge hose

Air conditioner

drain hose

[How to connect the lead wire of the safety switch]

Temperature

sensor of air

conditioner indoor unit

COM (Black)

NC (Black)

After installation is complete, install the cover according to the rubber parts.

Make a trial run of this equipment.

Pour a little water into the drain pan of the air conditioner’s indoor unit.
If the water level ascends to some extent while water enters the reservoir, the

pump runs for 2-3 seconds. discharging the water. Then. as the water level

descends, the pump stops. Make such operation repeat 8 to 10 times.
Check any leakage of water or generation of abnormal noise while the pump runs. 

Though there may be a little bit loud noise in the first 1-2 operations until the 

entering air escapes from the connection hose, this is not a failure.

PRODUCT SPECIFICATIONS

MAINTENANCE

1. Be sure to maintain the equipment in the following order when you stop

  operation of the air conditioner after summer season or resume operation of the

  air conditioner in earty summer. 

2. Be sure to cut off the power supply before maintaining this equipment 

3. Separate the reservoir by p-ng the hook part on the edge of the reservoir lid. 

  (Prepare for a dry towel in advance as the water can flow out from the inside

  when separating the reservoir.) 

4. Wash the inside of the reservoir with clean water. 

5. Fit the reservoir in place. 

6. Supply power to this equipment again and make a trial run according to the tip

  mentioned above. 

SAFETY PRECAUTIONS

While the pump runs, water should always pass from the inlet to the outlet of the 

pump. If the pump runs repeatedly with the air flowing in and out while water 

does not pass, it can cause failure of the pump.
This  equipment is produced exclusively for draining the condensate water of air 

conditioner.

DO NOT

 use it except for draining the condensate water of air conditioners.

DO NOT

 use this equipment for flammable liquid or hot water of 40

°

C/104

°

F or 

higher. 

DO NOT 

place inflammables near this equipment.

This appliance is not intended for use by persons (including children) with 

reduced physical, sensory or mental capabilities, or lack of experience and 

knowledge, unless they have been given supervision or instruction concerning

use of the appliance by a person responsible for their safety. Children should be

supervised to ensure that they do not play with the appliance.   
Before maintenance or follow-up service of this equipment. please cut off this 

equipment from the power. 
If the power cord is damaged in any way, 

DO NOT 

use this equipment to prevent

any danger.   
Do not touch this equipment at a wet place or with wet hand. 
To reduce the risk of electrical shock, be certain that the pump is connected to a

properly grounded earth.
This equipment is NOT a submersible pump. When this equipment is flooded, be 

sure to cut off the power supply and then contact our A/S Center or any 

installation expert of air conditioner.
Every installation or follow-up service should be done by a qualified service

technician.  
As this equipment is a pump with a short time rating, do not use it for applications 

requiring continuous operation for more than 3 minutes.
This pump is for indoor use only.

ASURITY

TM

CONDENSATE MANAGEMENT

www.diversitech.com   |   800.995.2222

Section

Specification

Capacity of A/C

Up to 16kw/54,000Btu/h

Power supply

100-240V / 60Hz

Power consumption

Max. flow rate

Max. discharge head

Size of outlet port

2.5W
8m / 26ft
7.66 GPH (29 LPH)
6mm or 1/4"

Available fluid

Condensate of

1~40°C/33~104°C

Dry running

Not allowed

Intermittent Rating

Capacity of reservoir

Safety switch 

Pump size(mm)

3 minutes
Max 3A at 110VAC or

Max 3A at 240VAC
140mL
62(W) x 59(H) x 282(L)

Weight

0.5kg

Section

Specification