
Astria.US.com
126733-01B
14
Note:
If vent pipe passes through any occupied areas above first floor,
including storage spaces and closets, you must enclose pipe. You may
frame and sheetrock enclosure with standard construction material. Make
sure and meet the minimum allowable clearances to combustibles. Do not
fill any required air spaces with insulation.
Vertical Termination Configurations
Figures 19 and 20, show the configurations for vertical termination.
Figure 18 - Installing Firestop
Figure 19 - Vertical Venting Configuration
Figure 20 - Vertical Venting Configuration Using Two 90° Elbows
If area above is a living space, install
firestop below framed hole.
If area above is an attic or insulated area,
install firestop above framed hole.
VENTING INSTALLATION
Continued
Venting with Two 90°
Elbows
Vertical
(V
1
)
Horizontal
(H)
6' min.
12' max.
7' min.
18' max.
8' min.
20' max.
20' max. 20' max.
V1 + V2 = 40' max.
Vertical
Venting
V = 40' max.
Note:
Install
Restrictor into
Inner Collar of
Fireplace as
Shown
HIGH ALTITUDE INSTALLATION
Your IHP direct vent fireplace has been tested and approved for elevations
from 0-2000 feet.
When installing a fireplace at an elevation above 2000 feet, you may need
to decrease the input rating by changing the existing burner orifice to a
smaller size. Reduce input 4% for each 1000 feet above sea level. Check
with your local gas company for proper orifice size identification.
When installing this fireplace at an elevation above 4500 feet, check with
local authorities.
PARTS LIST FOR VENTING KITS AND COMPONENTS
IHP (5/8") Pipe & Vent Kits
Catalog No. Part No.
Description
J2209
P58-6
6" Section Double Wall Pipe, Galvanized
J2201
P58-12
12" Section Double Wall Pipe, Galvanized
J2203
P58-24
24" Section Double Wall Pipe, Galvanized
J2205
P58-36
36" Section Double Wall Pipe, Galvanized
J2207
P58-48
48" Section Double Wall Pipe, Galvanized
J2082
PA58-712 Adjustable 7"-12" Section Double Wall Pipe, Galvanized
J0661
E58-45
45° Elbow, Galvanized
J0663
E58-90
90° Elbow, Galvanized
J1504
HTS-58
Horizontal Square Termination, Galvanized
J3190
VT-58
Vertical Round Termination, Galvanized
J2300
SC-58
Storm Collar, Galvanized
J3479
WF-58
Wall Firestop, Galvanized
J2251
RF-58-6
Roof Flashing - 0 to 6/12 Pitch, Galvanized
J2249
RF-58-12
Roof Flashing - 6/12 to 12/12 Pitch, Galvanized
J3134
VR-58
Vertical Restrictor, Galvanized
J2292
S-58
Vinyl Siding Standoff, Galvanized
J3483
WS-58
Wall Strap
J0373
CS-58
Cathedral Ceiling Support
J0953
FP-58
Firestop Plate
J2316
SF-58
Stucco Flashing - For use with HTS-58