background image

Astria.US.com

126659-01D

5

FIREPLACE INSTALLATION

SELECTING LOCATION

To determine safest and most efficient location for fireplace, you 

must take into consideration the following guidelines:

1.  Location must allow for proper clearances (see Figures 1 and 2).
2.  Consider a location where fireplace will not be affected by drafts, 

air conditioning ducts, windows or doors.

3.  A location that avoids cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see 

Optional 

Outside Air Kit

 on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Back and sides of fireplace                                      3/4" minimum*
Floor**                                                                       0" minimum
Perpendicular wall to opening                                   12" minimum
Top spacers                                                                0" minimum
Mantel clearances                                            see Mantels, page 6 

Chimney outer pipe surface                                        1" minimum

* Not required at nailing flanges

** See step 2 of Framing

 WARNING: DO NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

Minimum/Maximum Chimney Height

Minimum height of chimney, measured from base of fireplace to 

flue gas outlet of termination, is 14.5 feet for straight flue or a flue 

with one elbow set. Maximum distance between elbows is 6 feet. For 

systems with two elbow sets, minimum height is 22 feet. Maximum 

height of any system is 50 feet. This measurement includes fireplace, 

chimney sections and height of termination assembly at level of flue 

gas outlet (see Figure 20, page 12).

FRAMING

1.  Frame opening for fireplace using dimensions shown in Figures 

1 and 2.

2.  If fireplace is to be installed directly on carpeting, tile (other than 

ceramic) or any combustible material other than wood flooring, 

fireplace must be installed upon a metal or wood panel extending 

full width and depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

4.  Check level of fireplace and shim with sheet metal if necessary.

5.  Before securing fireplace to prepared framing, ember protector 

must  be  placed  between  hearth  extension  (not  included)  and 

under bottom front edge of fireplace to protect against glowing 

embers falling through. If fireplace is to be installed on a raised 

platform, a Z-type ember protector (not included) must be fabri

-

cated to fit your required platform height. Ember protector should 

extend under fireplace a minimum of 1 

1

/

2

".  Ember  protector 

should be made of galvanized sheet metal (28 gauge minimum) 

to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

HEARTH EXTENSION

A hearth extension projecting a minimum of 16" in front of and a 

minimum of 8" beyond each side of fireplace opening is required to 

protect combustible floor construction in front of fireplace. Fabri-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of k = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
  0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such 

as sand-cement grout (see Figure 3, page 6).

Figure 1 - Framing Dimensions

Figure 2 - Corner Installation

41 

3

/

4

"

41 

3

/

4

"

21 

7

/

8

"

Maintain 3/4"

Clearance at

Sides and

Back of

Fireplace

3/4" Clearance Not 

Required at Nailing Flanges  

52 

1

/

4

"

17 

5

/

16

"

73 

13

/

16

"

24 

7

/

16

"

Содержание Craftsman 36P2

Страница 1: ...obtenir un permis This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes WARNING If the information in thes...

Страница 2: ...will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace components doors air inlet system and damper control b Use of any component part not m...

Страница 3: ...insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide Poiso...

Страница 4: ...ALL 1 AIRSPACE TO COMBUSTIBLE MATERIAL COMBUSTIBLE WALL BOARD 0 TO TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUTS AIR KIT KNOCK OUT GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIG...

Страница 5: ...it back until nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed betwee...

Страница 6: ...than 1 1 2 from fireplace must not be placed less than 12 from top opening of fireplace NFPA 211 Section Clearance from Combustible Material Mantels or any other combustible material also may come up...

Страница 7: ...through a sidewall AK4 See Figure 7 for instruction of operating air kit CAUTION Combustion air inlet ducts shall not terminate in attic space The maximum height for the air vent can not exceed 3 feet...

Страница 8: ...r flue pipe section must be installed first with lanced side up Outer pipe section can then be installed over flue pipe section with hemmed end up Press down on each pipe section until lances securely...

Страница 9: ...6 Max 6 Max 6 Max 6 Max 6 Max Return Elbow Offset Elbow Offset Elbow Return Elbow A B C Ceiling Support Pipe 12S 8DM Return Elbow Figure 10 Ceiling Support Pipe 12S 8DM 2 Min Straps Straps Straps Stra...

Страница 10: ...be cut 1 Determine center point where pipe will penetrate the roof 2 Determine center point of the roof Pitch is the distance the roof drops over a given span usually 12 A 6 12 pitch means that the ro...

Страница 11: ...roof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be terminate...

Страница 12: ...gure 19 FINISHING FIREPLACE Combustible materials such as wallboard gypsum board sheet rock drywall plywood etc may make direct contact with sides and top around fireplace face It is important that co...

Страница 13: ...stall gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap and wa...

Страница 14: ...ng guidelines instructions and warranty informa tion please refer to your homeowner s guide or contact your dealer GLASS DOORS Glass doors are optional with this fireplace When fireplace is in operati...

Страница 15: ...from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give th...

Страница 16: ...5 21 2 34 18 11 14 3 13 22 10 6 31 7 36 37 35 38 28 29 15 26 16 27 16 27 23 24 PARTS WOOD BURNING FIREPLACE MODELS MODEL CATALOG NO Craftsman 36P2 F0705 Craftsman 36P2 F0706 Craftsman 36P3 F0707 Craf...

Страница 17: ...Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 107854 01 Right Refractory Bracket 1 24 107854 02 Left Refractory Bracket 1 25 109910 01 Grate 1 26 11418 Push On Nut 2 27 12105 Screen...

Страница 18: ...Rear White 1 108168 01 Refractory Bottom Front White 1 106658 01 Refractory Left Stacked White 1 106659 01 Refractory Right Stacked White 1 106660 01 Refractory Rear Stacked White 1 106661 01 Refracto...

Страница 19: ...F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Sectio...

Страница 20: ...Louvered Screen ROUND TOP TERMINATIONS WITH LOUVERS W SLIP SECTION F0919 RLTT 8DM Round Top with Slip Section Louvers F0891 RLTT 8HT Hi Temp Round Top w Lvrd Screen and Slip Section SQUARE TOP TERMIN...

Страница 21: ...F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree...

Страница 22: ...______________________________________________________ ______________________________________________________ ______________________________________________________ __________________________________...

Страница 23: ...al or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive tempera...

Страница 24: ...ecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 126659 01 Rev D 05 2015 P126659 01 WARRANTY KEEP THIS WARRANTY 1508 Elm Hill P...

Отзывы: