Figure 25

The duct system must be installed respecting 

the following:

1. Remove the plates closing up the 8” dia. 

holes on top of the fireplace.  Then, cut 

the insulation in order to obtain two 8” dia. 

openings.  Fix the adaptors on the fireplace 

openings by turning clockwise (

Figures 23 

and 24

).

2. Maintain at least a 2” (50 mm) clearance 

between the ducts and any combustible 

material; the required hole size is 13”  x  13” 

(330 mm x 330 mm).

  Exception #1:  For the grills, the fram-

ing can be 10-3/4” x 10-3/4” (275 mm 

x 275 mm) to provide the clearance as 

required by the integral spacers on the 

double outlet duct system.

3.  The maximum number of elbows in a run of 

duct is two.

4.  Maintain at least 6-1/2” (160 mm) clearance 

from the outlet grill framing to a combustible 

ceiling, side wall, mantel or floor.

5.  When traversing a combustible wall or floor, 

a firestop must be installed at the wall or floor 

penetration.  The hole size must be 13” x 13” 

(330 mm x 330 mm)

6.  Do not connect the hot air ducts to a central 

heating system.  Malfunction of the heating 

system’s blower will cause the fireplace to 

overheat.  A furnace duct is only single wall 

and not double wall as is required for the 

Ladera™ CAT fireplace hot air exhaust.  

7. Use only IHP grills and components as 

described in this manual. Other grills or 

registers, for example, may be too restrictive 

and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they 

will overheat.

9. Do not use tees or any other components 

than the ones specifically listed here.

10. Never allow the ducting to pitch down as 

hot air will be trapped creating a fire hazard. 

 

Never route the ducting downwards.

11. The hot air outlet grills must be installed with 

the louvers pointing downwards in order to 

prevent overheating adjacent ceilings.

Rain Cap

Flashing Collar

Flashing

Firestop

68” Min.

(1727mm)

39” Min.

(990mm)

Non-Combustible

Facing

Roof Support

Attic Radiation Shield

6-1/2” Min.

(165mm) to ceiling

u

Combustibles are not allowed below top spacers 

above the fireplace. Facing in front of fireplace must 

be non-combustible below this area.

u

NOTES:

-  Seal the top and 

both sides of the 

roof flashing with 

waterproof caulk-

ing.

-  The gap between 

the vent pipe and 

a vertical firestop 

shall be sealed with 

non-combustible 

caulking.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

18

Central Forced Air Kit 

NOTE: Not tested under EPA certification. If 

installed, this appliance no longer qualifies 

for EPA certification.

The knock-outs provided on the back and on 

the sides of the Ladera™ CAT fireplace allow 

the connection of insulated flexible pipe which 

enables you to heat adjacent rooms up to 50 

feet from the fireplace hot air outlet.

The ducting system must be installed as de-

scribed below:

A) Remove knock-out plate and cut insulation 

the adaptor at the back and/or the side of the 

fireplace.  Fix the adaptor by twist-locking 

it to the fireplace.  You can use more than 

one outlet on the fireplace (see 

Figure 26

).

B) Attach the 5” flexible pipe, using the collars 

provided. 

 Important: Make sure that the 

plastic wrapping around the flexible pipe 

will not be in contact with the fireplace.

C) Route the flexible pipe to the chosen location.  

The ducting system can be installed either 

in an upper room or in a lower room. 

D) Attach the flexible pipe to the blower, using 

the collars (

Figure 27

).

E) Fix the back draft damper to the blower 

outlet.

F)  Attach a flexible pipe to the fan / flexible pipe 

adapter (square to round) and stretch it up 

to the location where the heat is required.

G) At that point, the flexible pipe can be attached 

to any air distribution grill.

H) Install the blower heating and cooling ther-

mostat (HCTW) in that part of the house to 

be heated by the hot air duct. The thermostat 

can be switched to a cooling thermostat and 

installed in the same room as the unit.  This 

thermostat will turn on the blower when the 

room where the fireplace is located becomes 

too hot.

This option requires electricity. Make sure that 

the connections to the blower have been made 

according to the local codes and comply with 

their requirements (see instruction provided 

with the thermostat). For more information 

regarding central forced and ducting, refer 

to the BISFWK-1 installation sheet provided 

with the kit.

Содержание 900880-00

Страница 1: ...rds ULC S610 and UL 127 Report 14 181 EPA Cert No 111 17 WARNING The fireplace cannot be operated without a door Consult your dealer to select the correct replacement door The fireplace is equipped wi...

Страница 2: ...that are of suf ficient length to be blown in front ofanopenflamewhenthewindow is opened Keep any combustible furniture materials or decorative pillows at least 48 1219 mm from the front fireplace op...

Страница 3: ...era CAT fireplace is NOT intended for use with a gas log set Do not use a fireplace insert or any other product with this fireplace unless it is specified by IHP for use with this appliance Failure to...

Страница 4: ...thecatalyticcombustor Openingthe CAT bypass damper control increases the draft allowing the unit to achieve proper operating temperatures during a cold start up It also provides more draft to prevent...

Страница 5: ...tent of the wood For instance a long chimney will necessitate closing the damper more To obtain the proper combustion closethedampercompletely then open it about 1 4 to 1 2 6 4mm to 13mm Two medium si...

Страница 6: ...esabout15 30minuteswiththeCATbypass opened to reach proper light off temperatures for the catalytic combustor Step 5 Set the primary control to the desired burn level The fireplace will automatically...

Страница 7: ...sture content can exceed 80 which must be reduced to less than 20 Wood properly seasoned is then capable of generating the heat the stove was designed to provide Greenwooddoesnotburneasily Attemptingt...

Страница 8: ...remove the combustor Remove dust accumulation after chimney sweep and put the combustor back in place CATALYTIC COMBUSTOR This fireplace is designed with a catalytic com bustor which will reduce pollu...

Страница 9: ...rewsandslidingthehingebracketupordown to create better seal and then retightening Catalyst Bypass linkage replacement see Figure 9B Toolsrequired 2 9 16 wrenches 2square drive bit driver Withcatalystb...

Страница 10: ...ombustorProblem Thermal Cracking ThiscombustordoesNOTexperiencethermalcracking Notap plicable Appliestohoneycombcombustorsonly CombustorProblem CombustorPeeling ThiscombustordoesNOTexperiencecombustor...

Страница 11: ...the ashes are cold 24 to 48 hours after the fire is out Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases Figure 10 WARNING DisposalofAshes Ashesshould be plac...

Страница 12: ...dealer see Replacement Parts Page 28 DO NOT OPERATE THE UNIT WITH CRACKED OR BROKEN GLASS Glass Cleaning TheLaderaCATfireplaceisdesignedtokeeptheglasscleanundernormal operating conditions If the Lade...

Страница 13: ...replace is determined by considering the location of windows doors and the traffic flow in the room where the fireplace is located allowing space in front of the unit for the hearth exten sion and the...

Страница 14: ...must cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with at least a 1 2 inch of non combustible material tile marble stone etc See Figure 15 CO...

Страница 15: ...phs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesaresubjecttochangeordiscontinu ance without notice Allframingdimensionscalcula...

Страница 16: ...Fireplace Side Mantel Rock Board or Other Noncombustible Facing 39 990 mm Drywall 2 x 3 Min 51mm x 76mm Spacer Mantel and Facing Side View Rock Board or Other Noncombustible Facing Drywall Figure 17...

Страница 17: ...mbustible Facing Drywall 2 x 3 Min Rock Board or Other Spacer Figure 22 A wall on off switch must be installed to control theblower Anoptionalheatswitchandvariable speed control are available see Page...

Страница 18: ...front of fireplace must be non combustible below this area u NOTES Seal the top and both sides of the roof flashing with waterproof caulk ing The gap between the vent pipe and a vertical firestop shal...

Страница 19: ...the base of the fireplace C The fresh air must come from outside the house The air intake must not draw air from the attic basement or garage D The air intake should be installed where it is not like...

Страница 20: ...feet 3 7 m In altitude add 18 450 mm to the chimney for every 2 000 feet 600 m above sea level 6 All chimney installations must include at least one support Re ducing the amount of chimney weight on t...

Страница 21: ...he joint between the roof and the flashing with roofing pitch see Figures 34 and 35 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to...

Страница 22: ...4 Use a plumb bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From b...

Страница 23: ...6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 2432 mm...

Страница 24: ...ed wall radiation shield since it will maintain the home s thermal barrier Figure 39 Drywall Insulated Wall Angel Wall Radiation Shield Insulated Available from Security Chimneys Available from DuraVe...

Страница 25: ...AND MULTIPLE TERMINATIONS For the purpose of this manual a chimney chase is considered a part of the chimney system rather than part of a building The termination must be placed a minimum of 18 460 mm...

Страница 26: ...rily install the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval drill a hole in...

Страница 27: ...er EPA certification If installed this appliance no longer qualifies for EPA certification Check with local authorities having jurisdiction for requirements in your area Central Forced Air Kit Accesso...

Страница 28: ...tory 2 pieces PR SR2829 Secondary air tubes set of three F3540 Fireplace Ashlip F3551 Fireplace Front Bottom F3550 Top Front Insulation Protector F3554 Gasket Catalyst F3552 Catalyst Replacement Cartr...

Страница 29: ...fset Support SO Roof Support ST Roof Brace BS2 Firestops Firestop 6BF Radiation Shield 6RS Insulated Attic Radiation Shield 6RSA2 Insulated Wall Radiation Shield 6RSM Insulated Wall Radiation Shield 3...

Страница 30: ...Relining A Masonry Chimney 6 Diameter Listed to ULC S635M UL 1777 and ULC S640M at 2100 F Description Cat Part No 6 Length 6 Dia 6LL6 6LL6 12 Length 6 Dia 6LL12 6LL12 24 Length 6 Dia 6LL24 6LL24 36 Le...

Страница 31: ...ES AVEC LE FOYER DOIVENT TRE HO MOLOGU ES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE C RAMIQUE DE 5mm D PAISSEUR POUR UNE UTILISATION S CURITAIRE INSTALLER CONFORM ME...

Страница 32: ..._______________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___________________...

Страница 33: ...r may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry seaso...

Страница 34: ...NT PARTS See Page 28 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be ship...

Отзывы: