Astria Fireplaces Odyssey36ZNM Скачать руководство пользователя страница 6

Astria.US.com

126797-01F 

6

INSTALLATION

OUTDOOR ENCLOSURE REQUIREMENTS

Must conform to one of the following conditions:

• With walls on all sides, but with no overhead cover;
• Within a partial enclosure which includes an overhead cover and 

no more than two side walls. These side walls may be parallel, 
as in breezeway or at right angles to each side; or

• Within a partial enclosure which includes an overhead cover 

and three sidewalls, as long as 30% or more of the horizontal 
periphery of the enclosure is permanently open.

 CAUTION: Do not install the fi replace directly on 

carpet or vinyl.

 WARNING: Fireplace hood must be used if a com-

bustible mantel material is installed.

Mantel Clearances for Built-In Installation

If placing custom mantel above built-in fi replace, you must meet 
the minimum allowable clearance between mantel shelf and top of 
fi replace opening shown in 

Figure 3, Page 6

. These are the mini-

mum allowable mantel clearances for a safe installation. Use larger 
clearances wherever possible to minimize the heating of objects and 
materials placed on the mantel.

NOTICE: Surface temperatures of adjacent walls and 
mantels become hot during operation. Walls and 
mantels above the fi replace may become hot to the 
touch. If installed properly, these temperatures meet 
the requirement of the national product standard. Fol-
low all minimum clearances shown in this manual.

Figure 2 - Minimum Clearance for Combustible to Wall

*Minimum 16" from Side Wall

*

Example

IMPORTANT:

 Make sure fi replace is level. If fi replace is not level, log 

set will not work properly. 
Use dimensions shown for rough openings to create the easiest 
installation 

(see Built-In Fireplace Installation, 

Page 7

).

INSTALLATION CLEARANCES

 WARNING: Maintain the minimum clearances. If 

you can, provide greater clearances from fl oor, ceiling 
and adjoining wall.

Carefully follow these instructions. This will ensure safe installa-
tion. Fireplace hood must be used if combustible mantel material 
is installed.

Minimum Wall and Ceiling Clearances 

(see 

Figure 2

)

A.  Clearances from the side of the fi replace cabinet to any combus-

tible material and wall should follow diagram in 

Figure 2

.

 

Example: The face of a mantel, bookshelf, etc. is made of combus-
tible material and protrudes 3-1/2" from the wall. This combustible 
material must be 4" from the side of the fi replace cabinet 

(see 

Figure 2

)

.

B.  Clearances from the top of the fi replace opening to the ceiling 

should not be less than 42".

C.  When fi replace is installed on carpeting, tile (vinyl) or other com-

bustible material, other than wood fl ooring, fi replace should be 
installed on a metal or wood panel extending the full width and 
depth of enclosure.

D.  Clearances from bottom of fi replace to the fl oor is 0".

Figure 3 - Minimum Mantel Clearances for Built-In Installation

Hood MUST 
be used if a
combustible 
mantel is installed.

Wire-mesh
Screen

Firebox

Noncombustible
Material May
Project Off this
Surface above
the Firebox Hood

Mantel Shelf 

Note: Any portion

of the mantel shelf must NOT
extend beyond this profile.

A

B

C

Note: All vertical 
measurements are
from top of fireplace 
hood opening to
bottom of mantel shelf.

Facing material above firebox
must be of noncombustible
material. A 12" (305 mm) 
concrete board
projecting the width of the 
fireplace is supplied.

Framing
Material

D

12" (305 mm)

Min.

E F

Minimum Mantel 

Clearances

A

1-1/2" (39 mm) 

B

6-3/4" (172 mm)

C

12" (305 mm)

D

12" (305 mm)

E

16" (407 mm)

F

20" (508 mm)

Содержание Odyssey36ZNM

Страница 1: ...e service des incindies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WHEN USED AS AN OUTDOOR APPLIANCE DANGER CARBON MONOXIDE WARNING This appliance can produce carbon monoxide which has no odor Using it in an enclosed space can kill you Never use this appliance in an enclosed space such as a camper tent car ...

Страница 2: ...tect a gas leak However the odor added to the gas can fade Gas may be present even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING If the information in this manual is not followed exactly a fire or explosion may result caus ing property damage personal injury or loss of l...

Страница 3: ...y part of the control system and any gas control which has been under water 12 Do not operate fireplace if any log is broken Do not operate fireplace if a log is chipped dime sized or larger 13 Turn fireplace off and let cool before servicing Only a qualified service person should service and repair fireplace 14 Operating fireplace above elevations of 4 500 feet could cause pilot outage 15 Provide...

Страница 4: ...connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Unvented appliances may NOT be installed in bedrooms or bathrooms A working smoke detector must be installed in the area where vent free appliances are installed Seller of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a co...

Страница 5: ...67 mm 42 Models Electrical Access Hole 37 940 mm 36 Models 41 1042 mm 42 Models 41 1042 mm 36 Models 45 1143 mm 42 Models 21 534 mm 36 Models 23 584 mm 42 Models 29 737 mm 36 Models 36 915 mm 42 Models 43 1093 mm 36 Models 50 1270 mm 42 Models 9 1 4 235 mm 9 1 4 235 mm 5 8 16 mm 4 102 mm 3 1 2 89 mm 3 1 2 89 mm 4 1 2 115 mm 10 1 2 267 mm 36 Models 10 1 4 261 mm 42 Models 14 1 2 369 mm 36 Models 16...

Страница 6: ...gs to create the easiest installation see Built In Fireplace Installation Page 7 INSTALLATION CLEARANCES WARNING Maintain the minimum clearances If youcan providegreaterclearancesfromfloor ceiling and adjoining wall Carefully follow these instructions This will ensure safe installa tion Fireplace hood must be used if combustible mantel material is installed Minimum Wall and Ceiling Clearances see ...

Страница 7: ...0 mm 44 1118 mm FOR 36 MODELS 74 1880 mm 52 1321 mm Figure 4b 45 TOP VIEW 51 1296 mm 43 1093 mm 86 2185 mm 61 1550 mm FOR 42 MODELS Figure 4c Figure 5 Installing Firebox INSTALLING DRAIN PAN DP36 DP42 The fireplace enclosure must allow for adequate drainage and fresh air ventilation It is recommended that a sealed corrosion resistant catch pan with provision for drainage be installed under firepla...

Страница 8: ...nto pivot plate or pivot hole located near bottom corner of front face opening and swing door to the vertical position making sure top pins slide into door track Door is installed when top door pin snaps into spring clip see Figure 8 2 Repeat step 1 for remaining door WARNING Fireplace must be operated only with doors fully opened Door Adjustment Remove doors and slightly loosen lower pivot plate ...

Страница 9: ...d below approved flexible gas hose and fittings supplied with appliance if allowed by local codes external regulator propane LP models only piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connection sediment trap tee joint pipe wrench An equipment shutoff valve with 1 8 NPT tap is an acceptable al ternative to test gauge connection Purchase the optio...

Страница 10: ... LP tank must have at least four 10 square inches 65 cm2 openings a 2 x 5 5 x 13 cm square The top openings must be 180 opposing and be placed at valve level The bottom openings must be 180 opposing and be placed 5 12 7 cm above bottom floor There must be 2 5 cm minimum clearance from the floor to ground level of enclosure CAUTION Use only new black iron or steel pipe Internally tinnedcoppertubing...

Страница 11: ...6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa 1 Close equipment shutoff v...

Страница 12: ...CE 5 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information in column 1 If you don t smell gas go on the next step 6 Press in and turn control knob counterclockwise to the PILOT position Press in control knob for five 5 seconds see Figure 18 Page 13 7 With control knob pressed in press and release igniter button This will light pilot If needed keep p...

Страница 13: ... causing brief patches of orange flame If burner flame pattern is incorrect as shown in Figure 22 turn appliance off see To Turn Off Gas to Appliance see Troubleshooting Page 16 OPERATION Continued TO TURN OFF GAS TO APPLIANCE 1 Push switch into OFF position The pilot will remain lit for normal service 2 Access control knobs 3 Press gas control knob slightly and turn clockwise to OFF Do not force ...

Страница 14: ...ound log set clean and clear of debris Periodically inspect the air mixer and burner tube for foreign matter blocking the air inlet and flame holes HIGH ALTITUDE INSTALLATION When the fireplace is installed at an elevation above 2000 feet you may need to decrease the input rating by changing the existing burner orifice to a smaller size Reduce input 4 for every 1000 feet above 2000 feet which they...

Страница 15: ...0 47 000 Btu Hr Gas Type Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure inches of water Max 10 5 W C Min 5 0 W C Air Shutter 3 16 OPEN Odyssey42ZPM Rating Variable 35 000 45 000 Btu Hr Gas Type Propane LP Ignition Piezo Manifold Pressure 10 W C Inlet Gas Pressure inches of water Max 14 W C Min 11 W C Air Shutter FULLY OPEN For purpose of input adjustment HEAT LIMIT SWITCH TO P...

Страница 16: ...onnected or im properly connected 4 Thermopile is defective REMEDY 1 Reconnect igniter cable 2 Free igniter cable if pinched by any metal or tubing Keep igniter cable dry 3 Tighten nut holding piezo igniter Nut is located behind the mounting bracket 4 Replace igniter cable 5 Replace piezo igniter 6 Replace pilot assembly 7 Tighten electrode Replace if necessary 1 Turn on gas supply or open equipme...

Страница 17: ... and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance Page 14 or replace burner orifice 1 This is normal If noise is excessive contact qualified service person 1 Replace batteries in receiver and hand held remote control see Page 14 POSSIBLE CAUSE 1 Gas control kno...

Страница 18: ... and pan material OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue on logs or inside of fireplace REMEDY 1 Locate and correct all leaks see Checking Gas Connections Page 11 1 Fireplace has been tested for up to 40 mph winds However extreme conditions may occur See Lighting Instru...

Страница 19: ...also visit our web site at Astria US com REPLACEMENT PARTS See Pages 20 to 22 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace 2...

Страница 20: ... 13 10 11 12 31 33 33 32 34 22 22 CAT NO MODEL INTERIOR F0584 Odyssey36ZNM White Stacked F0585 Odyssey36ZPM White Stacked F0586 Odyssey36ZNM White Herr F0587 Odyssey36ZPM White Herr F0592 Odyssey42ZNM White Stacked F0593 Odyssey42ZPM White Stacked F0594 Odyssey42ZNM White Herr F0595 Odyssey42ZPM White Herr ...

Страница 21: ...opane LP 1 15 J5435 Log Set and NG Chassis 1 J5436 Log Set and LP Chassis 1 J5432 Log Set and NG Chassis 1 J8000 Log Set and LP Chassis 1 16 J3546 Piezo Igniter 1 17 J4046 Valve Bracket 1 18 J6833 3 8 x 3 8 Brass Adapter 1 19 Fireplace Top 1 Fireplace Top 1 20 J4717 Dormont T6 36 3 8 x 18 Flextube 1 21 J5450 Log Set Retainer 2 J5451 Log Set Retainer 2 22 J6918 Top Spacer 2 23 J6895 Firebrick Retai...

Страница 22: ...als not approved by IHP Use of non approved parts can result in poor performance and safety hazards PARTS IMPORTANT Installation of brick panels should be done after the fireplace is placed in a permanent location WARNING LIFTING HAZARD SINGLE PERSON LIFT COULD CAUSE INJURY USE ASSISTANCE WHEN MOVING OR LIFTING 1 2 3 4 5 6 7 8 ...

Страница 23: ...255 WHITEHERRINGBONEREFRACTORYSET 42 2 REFRACTORY BTM REAR 36 WHITE 1 REFRACTORY BTM REAR 42 WHITE 1 3 J5988 REFRACTORY BTM FRONT RT 36 WHITE 1 J5982 REFRACTORY BTM FRONT RT 42 WHITE 1 4 J5990 REFRACTORY BTM FRONT LT 36 WHITE 1 J5984 REFRACTORY BTM FRONT LT 42 WHITE 1 5 J5427 REFRACTORY BTM CTR ASM WHITE 36 42 1 6 REFRACTORY LT STD WHITE C36 1 REFRACTORY LT WHITE HERR C36 1 REFRACTORY LEFT WHITE 4...

Страница 24: ... w 4 Brow DRAIN PAN Not shown F1089 DP36 36 Drain Pan w 1 Stainless Decorative Face Extension F1090 DP42 42 Drain Pan w 1 Stainless Decorative Face Extension BI FOLD GLASS DOORS F0987 BDO36 36 Outdoor Bi Fold Glass Door Black finish F0988 BDO36B 36 Outdoor Bi Fold Glass Door Brushed Brass finish F0989 BDO36P 36 Outdoor Bi Fold Glass Door Platinum finish F0990 BDO42 42 Outdoor Bi Fold Glass Door Bl...

Страница 25: ...ry panels a new look Kit includes foam roller roller handle paint tray and one can of stain Available stain colors are Creamer ivory Rust terra cotta and Cappuccino rosy taupe H8176 BSK CR Refractory Stain Kit Creamer H8177 BSK RT Refractory Stain Kit Rust H8178 BSK CP Refractory Stain Kit Cappuccino Creamer Rust Cappuccino ...

Страница 26: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________________...

Страница 27: ...ot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive te...

Страница 28: ...al distributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 126797 01 Rev F 01 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 P126797 01 Astria US com Record the following important information about your appliance Appliance model number Appliance serial number Date appliance was Installed Type of gas appliance uses Dealer name 28 ...

Отзывы: