background image

Step 3

. Open the doors about 1” and wait 5 

seconds until the air flow has stabilized.  Then 

open the doors completely, put the logs in and 

close the doors. 

Step 4

. Set the primary air control to the 

desired burn level. Open the bypass damper 

for 10 minutes before closing it. It will ensure 

sufficient temperatures for combustor light-off.

To refuel the Montecito Estate™ CAT fireplace 

when the unit is still hot (Some burning fuel 

remaining or a glowing combustor)

A. Fully open the primary air control and the 

bypass completely.

B.  Open the doors about 1” and wait 5 seconds 

until the air flow has stabilized.  Load the fuel, 

close the doors and bypass (temperatures 

within the firebox should be enough to 

maintain catalytic operation).

C. Set the primary air control to the desired 

burn level.

NOTES: 

•  For spectacular fire and optimization of  the 

fireplace efficiency, we recommend that the 

wood load be placed as far back as possible.

•  It may be necessary to turn off any blower(s) 

in operation during the refueling process in 

order to minimise smoking in the room.  It 

is recommended to wait 15 to 30 minutes 

before turning the blower(s) back on to 

ensure successful rekindling.

SMOKING – 

CAUSES AND TROUBLESHOOTING

To reduce the likelihood of smoke coming 

into the room when opening the doors, set 

the combustion air controls to the left (“Ac-

celerated Combustion”) and open the bypass 

before opening the doors.  Your fireplace has 

been designed and tested to provide smoke 

free operation.
As the fire burns, air goes up the chimney.  

This air must be replaced through the outside 

air duct.  When operating the fireplace, open a 

nearby window temporarily to check if there is 

adequate replacement air supply.  Occasionally, 

there may be a small amount of smoking upon 

lighting the fire, until the chimney heats up but 

this should not last.  If the fireplace continues 

to smoke it is probably for one of the follow-

ing reasons:

A. The doors are partially opened - 

 When you 

close the doors, close them completely.

B. Negative pressure in the house - 

As the 

fire burns, air goes up the chimney.  This 

air must be replaced through leakage into 

the house or through the outside air duct 

(optional).  When operating the fireplace, 

open a nearby window temporarily to check 

if there is adequate replacement air supply.

C. Fans operating (e.g.: range hood) - 

These 

fans draw air out of the house and may 

actually cause a negative pressure in the 

house.  Turn off all fans and open a nearby 

window to determine if this is the cause of 

the problem.

D. Wet wood - 

Wet or tarred wood will smoulder 

and smoke instead of burning properly. Your 

dealer can help you determine if you have 

properly seasoned wood for burning.

E. Dirty or blocked chimney - 

Check to make 

sure the chimney is clear and clean.  If 

dirty call a certified chimney sweep or use 

a properly sized chimney brush to clean.

F.  Chimney not long enough - 

The minimum 

chimney height is 12 feet not including the 

fireplace height.  The chimney must extend at 

least three (3) feet (915 mm) above its point 

of contact with the roof and at least two (2) 

feet (610 mm) higher than any roof or wall 

within ten (10) feet (3 m) of it.  When installed 

with offsets, the minimum chimney height is 

15 feet.  Additional height will increase draft 

and will decrease the tendency to smoke.

G. Poor chimney draft

  With no fire, there should be sufficient draft 

to exhaust cigarette smoke introduced under 

the baffle.  Chimneys installed against an 

outside wall without protection may gener-

ate back draft problems which will cause 

start-up problems.  To prevent this, open 

a nearby window; roll up a piece of paper, 

light it and hold it in the upper part of the 

firebox to warm up the chimney.  Wait until 

the draft is sufficient, then start the fire.

H. Blower for forced air kit operating - 

Make 

sure that the blower is at the “off” position 

when you open the fireplace door for reloading.

IMPORTANT CAUTIONS

A. Do not block the openings at the top of the 

fireplace as this will cause the fireplace to 

overheat.

B. Never use gasoline, gasoline-type lantern 

fuel, kerosene, charcoal lighter fluid, or 

similar liquids to start or ‘freshen up’ a fire 

in this fireplace.  Keep all such liquids well 

away from the fireplace while it is in use.

C. Do not burn coal.  The sulphur in coal will 

corrode the firebox and chimney.

D. Do not burn driftwood which has been in the 

ocean or salt water.  The salt will corrode 

the firebox and chimney.

E. Do not operate the unit with the door(s) 

partly open since this may cause smoke to 

be drawn into the room.

F.  Do not burn wood in the area in front of the 

grate.

G. Do not abuse the unit by burning paper, or 

cardboard or construction material such as 

pressed wood, plywood or lumber.  Wood 

protectors, metallic paper, coal, plastic, 

waste, sulphur and/or oil will damage the 

fireplace.

H. Do not allow the wood to smoulder or burn 

without flame, since this will produce exces-

sive creosote in the unit as well as increased 

particulate emissions. 

STARTING AND MAINTAINING A FIRE

Step 1.

  Place several crumpled up balls of 

newspaper in the firebox.  Place small dry pieces 

of kindling on top of the paper, criss-crossing 

the kindling so that there are air spaces in 

between. The kindling should be placed at the 

center of the firebox so as to allow for sufficient 

air circulation. 

Step 2.

 Adjust the primary air control and pull 

the bypass damper control towards you to put 

it in the OPEN position. Light the newspaper. 

Leave the doors partially opened to facilitate 

the start-up.

Step 3.

 Once the kindling fire is well established, 

cord wood can be added.  Close the door and 

maintain an accelerated combustion air set up in 

order to achieve combustor light-off conditions 

(See Primary Air Control Section). 

Step 4.

  When the fire is burning well, close the 

bypass damper control by pushing the control 

rod in.  It takes about 15 – 30 minutes with 

the bypass opened to reach proper light-off 

temperatures for the catalytic combustor.

Step 5.

 Set the primary control to the desired 

burn level. The fireplace will automatically go 

to that level after the fire is fully established.
The unit will burn best with 2-3 pieces of cord 

wood spaced 1 to 2 inches apart and allowing 

air to get under the fuel.  Criss-crossing or ar-

ranging the fuel so that air can get underneath 

will help the fire to get started easily. The unit 

should be operated with the air control fully open 

long enough to get the cord wood well ignited. 

REFUELING FOR BEST PERFORMANCE

To refuel the fireplace at the end of a burn cycle 

when only hot embers remain and flames are 

gone (not enough heat to maintain catalyst 

operating temperatures):

Step 1

. Open the bypass and air controls fully 

(see 

Figure 1

)

.

Step 2

. Completely open the primary air control.  

See 

Figure 2

.

REFUELING: During the refueling and 

rekindling of a cool fire, or a fire that has 

burned down to the charcoal phase, operate 

the stove at a medium to high firing rate for 

about 10 minutes to ensure that the catalyst 

reaches approximately 400°F.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

6

Содержание MONTECITO ESTATE CAT

Страница 1: ...eration and will retain heat for a while after shutting off the appli ance Severe burns may result Carefully supervise children in the same room as appliance If small children are present in the home it is recommended that this appliance be fitted with an adjustable safety gate or barrier screen WARNING Thefireplacecannotbeoperatedwithoutdoors Consultyourdealertoselectthecorrectreplace ment door T...

Страница 2: ...tructions and retain this manual for future reference Before beginning the fireplace installation consult the appropriate local authorities to obtain your building permit and check your local building codes Install the fireplace only as described in these instructions and using only IHP components This fireplace has been tested for CAN ULC S610 M87 and ANSI UL 127 It has also beentestedforEPA40C F...

Страница 3: ...ich is included with fireplace WARNING Neverleavechildrenunattended when there is a fire burning in the fireplace IMPORTANT GENERAL SAFETY PRECAUTIONS READ AND UNDERSTAND THESE SAFETY RULES BEFORE YOUR FIRST FIRE WARNING Never leave your fireplace unat tended while it is burning WARNING THE FIREPLACE MUST BE OPER ATED WITH THE DOORS FULLY CLOSED IF THE DOORS ARE LEFT PARTLYOPENED GASANDFLAME MAYBE...

Страница 4: ... Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater First Fires Make sure the doors are properly adjusted thus avoiding color change to finish due to overheating The first five or six fires should be small fires of short duration about 30 to 60 minutes This will help cure the refractory bricks During the first few fires of th...

Страница 5: ... 000 BTU per hour and the loading time will be about every 3 4 hours Use caution when firing with the combustion air control wide open Only burn cord wood in this manner Small dry pieces of softwood andconstructionscrapswillburnveryintensely using this method and may damage the firebox as well as the catalytic combustor Medium Combustion Thisistherecommendedmodeofoperatingthe Montecito Estate CAT ...

Страница 6: ...affle Chimneys installed against an outside wall without protection may gener ate back draft problems which will cause start up problems To prevent this open a nearby window roll up a piece of paper light it and hold it in the upper part of the firebox to warm up the chimney Wait until the draft is sufficient then start the fire H Blower for forced air kit operating Make sure that the blower is at...

Страница 7: ...mal Cracking This combustor does NOT experience thermal cracking Not applicable Applies to honeycomb combustors only Combustor Problem Combustor Peeling This combustor does NOT experience combustor peeling Not applicable Applies to honeycomb combustors only Reduced Combustor Performance Combustor Clogging or Fatigue Signs of combustor fatigue include reduced heat output and sluggish performance In...

Страница 8: ...ating instructions in the manual DEALING WITH A CHIMNEY FIRE Regular chimney maintenance and inspection canpreventchimneyfires Ifyouhaveachimney fire follow these steps 1 IMPORTANT Close the fireplace door and the combustion air controls this will stifle the fire 2 Alert your family of the possible danger 3 If you require assistance alert your fire department 4 If possible use a dry chemical fire ...

Страница 9: ...g wood framing Creosote formation in a chimney can be minimized by making sure there is always visible flame burning avoid smoldering fires and by proper refueling techniques Chimney Maintenance Regular chimney inspection and maintenance combined with proper operation will prevent chimney fires Keep your chimney clean Do not allow more than 1 16 1 6 mm creosote build up in your chimney Prohibited ...

Страница 10: ...ed up and into position it seals to the bracket behind it Secondary Burn Tubes 3 SECONDARY AIR TUBE REMOVAL IN STRUCTIONS 1 Remove the two ceramic baffles gently pulling them forward and down 2 To remove the burn tubes first remove the bracket which position and secures the tubes in place This is done be removing the 2 screws see Figure 8 which hold this bracket in place upper left side inside the...

Страница 11: ...ry bricks follow these steps 1 Remove the side refractory brackets 6 2 Remove the front refractory bricks 3 3 Remove the bottom refractory brick 4 4 Remove the left side refractory bricks 5 5 Remove the right side refractory bricks 2 6 Remove the back refractory brick 1 To install the new refractory bricks follow the above steps in reverse DISPOSING OF ASHES Whenever ashes get 3 to 4 inches deep i...

Страница 12: ...glass cleaners will not clean creosote Do not use abrasives such as steel pads steel wool or oven cleaner as they will scratch the glass DO NOT USE CHEMICAL GLASS CLEANERS ON PAINTED SURFACES AS IT MAY CAUSE THE PAINT TO PEEL CAUTION DO NOT ALLOW WINDOW CLEANER TO GET IN CONTACT WITH DOOR GASKET OR PAINT ON FACADE OR DOOR ONCE CLOSED CONTACT OF GLASS CLEANER WITH THE FIREPLACE FACADE CAN LEAD TO P...

Страница 13: ...equacy of the floor can be checked by first estimating the weight of the fireplace system Weights are given in the appendix Next measure the area occupied by the fireplace Note the floor construction and consult your local building code to determine if additional support is needed This fireplace must be installed on a 1 2 minimum non combustible surface and at a minimum of 80 measured from the bas...

Страница 14: ...And Mantel The construction of the framing facing and mantel must be in accordance with the stan dards and the following illustrations Figure 15 and 16 A Frame the fireplace using 2 x 3 or heavier lumber B WARNING Combustible materials can not be used in the space directly above the fireplace except for the studs above the facade that support the facing and mantel This area must remain empty for a...

Страница 15: ...materials such as brick stone or ceramic tile may project in front of and onto the fireplace facing Figure 18 IMPORTANT The facade must be removable once installed The facade is designed to overlapanyfacingmaterialinstalled onthefrontofthefireplace Ifthicker material is installed use the facade as a template and make sure it can be easily removed for servicing FACING Rough Framing Face dimension i...

Страница 16: ...nt ceiling Followlocalrulesregardingfram ing construction 1 3 4 5 6 2 1 2 7 3 4 1 Fireplace 2 Front of fireplace 3 Wood frame 2 x 3 min 4 Drywall 5 Tiles 6 Rock board or other 7 Brick Fireplace Frame Section Top View Figure 18 SEE NOTE MANTEL and FACING The mantel must be installed at least 56 1143 mm abovethebaseofthefireplace Figure19 Nailing Flanges Four nailing flanges are provided to secure t...

Страница 17: ...ireplace Figure 20 50 Min Figure 19 Mantel Noncombus tible Facing 62 Drywall 2 x 3 Min Standoff Mantel and Facing Side View Rock Board or Other Noncombustible Material Noncombustible Facing Drywall Rock Board or Other Noncom bustible Material NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 17 ...

Страница 18: ...ible pipe Using the aluminium tape provided Figure 24 OUTSIDE CONNECTION Outside Intake Screw Opening Facing Down Wall Aluminum Tape Plastic Cover Insulation Flexible Pipe Aluminum Tape Figure 25 Aluminum Tape Aluminum Tape Fireplace Connection Plastic Cover Insulation Flexible Pipe Fireplace OUTSIDE AIR CONNECTION TO THE FIREPLACE Fireplace Blower The fireplace comes equipped with a heat activate...

Страница 19: ...ed by the supports The maximum chimney length that can be supported by the fireplace is nine 9 feet 2 75 m 6 The chimney must extend at least three 3 feet 915 mm above its point of contact with the roof and at least two 2 feet 610 mm higher than any wall roof or building within ten 10 feet 3 m of it Figure 31 7 If the chimney extends higher than five 5 feet 1 500 mm above its point of contact with...

Страница 20: ...ber of equal size to the joist should be used Figure 32 FEMALE END MALE END BUTTON LOCK ATTACH FOR LOCK Figure 33 INSULATION SHIELD CAT NO SPIS NAIL FIRESTOP CAT NO SPFS Chimney Flue Diameter 7 A 13 7 16 B 13 7 16 Table 3 If the area above the ceiling is an attic go to step 5 2 Install SNAP PAK chimney sections start ing at the top of the appliance Leave the first section loose until the installat...

Страница 21: ...rance to combustibles AT THIS POINT TIGHTEN CLAMPS 11 Slide IHP chimney pipe into top of tee Align male and female ends Push down on pipe sec tions until locked As sections are added it will be necessary to secure them to the outside wall with bands SPWB at eight foot intervals and 2 from combustibles Wall Bands SPWB are secured to the chimney by placing band around the chimney and tightening clam...

Страница 22: ...roof will vary depending on the roof pitch 2 Install the next SP chimney section through the roof See Figure 38 NOTE If your roof is already shingled be sure to slide the upper edge under the shingles to prevent leakage 3 Install a bead of caulk around the pipe at the top edge of the flash ing Wrap the storm collar around the pipe and imbed the edge in the caulk to prevent leakage around the pipe ...

Страница 23: ...operation Trees buildings adjoining roof lines adverse wind conditions etc may create a need for a taller chimney should smoking occur Additional support is required above the roof if the chimney height exceeds four 4 feet Select the proper support for your application using either a roof brace Figure 42 or a support band with guy wires Figure 43 Figure 40 IF 10 FEET OR LESS L944 FIG21 THEN BUT MU...

Страница 24: ...m Figure 44 Chimney Adaptor Canada only CHIMNEY ADAPTOR CANADA ONLY The fireplace is normally supplied with a chimney adaptor suitable for use with IHP SnapPak venting In Canada the use of Security Chimneys ASHT adaptor is required Security part number 7IHP2 Two inch wall CANADA ONLY CHIMNEY INSTALLATION INSTRUCTIONS USING SECURITY CHIMNEYS ASHT CANADA APPROVED VENTING SYSTEMS 7 diameter chimney C...

Страница 25: ...f the hole until a 30º liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip through the hole a 30º liner elbow and connect it to the liner 6 Add a small liner section to the liner elbow which will allow the liner to extend at least 12 measured at the top of the liner from the masonry chimney 7 Seal the opening ar...

Страница 26: ...e Air UZI To Fireplace UZIAD UZIAD Outside Air Ducting includes 4 insulated flex x 10 long UZI UZI OPTIONAL INSTALLATION ACCESSORIES Fireplace Kits Description Cat Part No Central Forced Air Kit Accessories Central Forced Air Kit Central forced air kit including blower BISZY flex adaptor BISAF 2 clamps variable speed control VRUW thermo disk VTU fan to flexible pipe adapter BISAVF back draft dampe...

Страница 27: ...Refractory Bricks PR SR2421 Back Refractory Brick PR SR2415 Right Side Refractory Bricks Back PR SR2417 Right Side Refractory Bricks Front PR SR2419 Left Side Refractory Bricks Back PR SR2416 Left Side Refractory Bricks Front PR SR2418 Bottom Refractory ME CAT F3020 Thermopile gauge and label replacement J8004 Catalytic Combustor with Gasket F3015 Complete Catalytic Combustor Assembly F3016 Burn T...

Страница 28: ...Collar spacer included 7XFC 7XFC Firestops and Braces Firestop 7XBF 7XBF Radiation shield 7XRS 7XRS Insulated attic radiation shield 7XRSA 7XRSA2 30º Insulated wall radiation shield 7XRSMI30 7XRSMI30 Wall Band XBM XBM FireplaceModelMontecitoEstate CAT ApprovedVentingComponents manufactured by Security Chimneys or DuraVent 7 diameter chimney Secure Temp GX U S only Secure Temp S 2100 orNovaTemp HT6...

Страница 29: ...FOYER DOIVENT ÊTRE HO MOLOGUÉES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE CÉRAMIQUE DE 5mm D ÉPAISSEUR POUR UNE UTILISATION SÉCURITAIRE INSTALLER CONFORMÉ MENT AUX DIRECTIVES DU FABRICANT ATTENTION NE PAS OBSTRUER LES ARRIVÉES D AIR COMBURANT NE PAS FAIRE SURCHAUFFER LE FOYER LA PORTE DU FOYER DOIT DEMEURER TOTALEMENT FERMÉE LORSQUE LE FOYER FONCTIONNE NE PAS UTI...

Страница 30: ...uct d damages repairs or inefficiency resulting from faulty installation or application of the Product IHP is not responsible for inadequate system draft caused by air conditioning and heating systems mechanical ventilation systems or general construction conditions which may generate negative air pressure in the room in which the appliance is installed Additionally IHP assumes no responsibility f...

Страница 31: ...er may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning dry seasoned wood only c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faul...

Страница 32: ... 27 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 The description o...

Отзывы: