24 Installation and start-up
UM5C06D ( 169-2071-504 ) P0831010 Standard 7.00 May 2001
Table 5 - Rectifier and Controller interface connections (8-pin connectors)
Pin #
Design.
Description
Signal
1
EQL
Remote Equalize
BAT RTN
2
RG+
Sensing Positive
BAT RTN
3 RC-
Sensing
Negative
-48V
4
FAN ALM
Fan Failure
BAT RTN
5
HVSDR
Remote High Voltage Shutdown Reset
BAT RTN
6
HVSD
Remote High Voltage Shutdown
BAT RTN
7
RFA
Rectifier Failure Alarm
BAT RTN
8
TB
Temporary Release
BAT RTN
Note:
Both RFA and Fan alarm relays are energized during
normal operation and are de-energized during an alarm
condition.
Table 6 - Rectifier and Controller interface connections (26-pin connector)
Pin #
Designation
Description
Signal
1
RC1 -
Sensing Negative rect (1)
BAT-
2
RFA1 (NC)
Rectifier (1) fail alarm
NC
3
TR1
Temporary Release Rect (1)
Bat RTN
4
SH1+
Shunt Positive Rect (1)
50 mV
5
SH1-
Shunt Negative Rect (1)
50 mV
6
RC2-
Sensing Negative Rect (2)
BAT-
7
RFA2 (NC)
Rectifier (2) fail alarm
NC
8
TR2
Temporary Release Rect (2)
Bat RTN
9
SH2+
Shunt Positive Rect (2)
50 mV
10
SH3-
Shunt Negative Rect (3)
50 mV
11
RC3-
Sensing Negative Rect (3)
BAT-
12
RFA3 (NC)
Rectifier (3) fail alarm
NC
13
TR3
Temporary Release Rect (3)
Bat RTN
14
SH3+
Shunt Positive Rect (3)
50 mV
15
SH3-
Shunt Negative Rect (3)
50 mV
16
CUR SHARE
Current Share
0 - 12VDC
17
RFA (C)
Rectifier Fail Alarm
Common
18
ALM COMMON
Alarms Common
Common
19
EQL
Remote Equalize
BAT RTN
20
RG+
Sensing Positive
BAT RTN
21
HVSDR
Remote High Voltage Shutdown Reset
BAT RTN
22
HVSD
Remote High Voltage Shutdown
BAT RTN
continued
Содержание NT5C06D
Страница 2: ......
Страница 4: ......
Страница 10: ...10 Contents UM5C06D 169 2071 504 P0831010 Standard 7 00 May 2001 This page is left blank intentionally ...
Страница 46: ...46 Maintenance UM5C06D 169 2071 504 P0831010 Standard 7 00 May 2001 This page is left blank intentionally ...
Страница 55: ......