INSTALLATION
2/4
INSIDE THE LUMINAIRE
Si-3
6
LED test switch
CAUTION: MAKE CERTAIN THE AC POWER IS OFF AND THE Si-36 UNIT CONNECTOR IS
DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE.
Output
Output Power
Voltage
0°C≤Ta≤55°C
Model
Input
230V/50Hz
Si-36
120V/60Hz
277V/60Hz
10°C≤Ta≤55°C
230V/50Hz
120V/60Hz
277V/60Hz
Max. 36W
With dimmable or
non-dimmable load
Max. 27W
Max. non-dimmable load
1. OPERATING SPECIFICATIONS
2. INSTALLING THE Si-36
The Si-36 can be mounted inside or outside (nearby or on top of) the luminaire.
3. INSTALLING THE LED TEST SWITCH (LTS)
Select a convenient location for the LED test switch so that it can be seen after installation.
Drill a 1/2"(12 mm) hole for mounting the LED test switch. Connect the wires from the LED
test switch to the Si-36 according to the wiring diagram on page 3.
OUTSIDE THE LUMINAIRE
Si-3
6
One 7/8" (22mm) hole for
conduit connector for Si-36
Typical length
1"
1/4"
10"
T<0.20"
All dimensions are typical
www
.
AssuranceLighting.com
(MOUNT ING HOLE) Ø1/2"
PUSH TO TEST