2.2.11 To connect a doorbell
Note 1:
The doorbell may be connected either to
PCBA 3019
or
PCBA 3024
.
Note 2:
The doorbell output is a normally open contact of a solid state relay.
Note 3:
The doorbell output is not polarized (may be used for both AC and DC).
Note 4:
The relay contacts are closed as long as the doorbell button is pushed.
Figure 20
2.2.12 To connect an electric strike
Note:
The electric strike is always connected via SmartCable.
Specification for electric strike:
If the strike is connected to the
main control unit
(MCU), any strike designed for 12-24VDC
can be used.
The power supply must be powerful enough for both the MCU and the strike under load.
The maximum current from the MCU strike output is 350 mA.
You can use any strike with its own power supply by using a relay on the MCU strike output.
The SmartCable
only works with the
VingCard Allure
main control unit
must be ordered from ASSA ABLOY Hospitality
can be extended locally if required
can be configured in
Lock Service 3G
('Set fail safe strike' and 'Set fail secure strike'
under
Configure lock
)
is not interchangeable with the SmartCable for the egress switch