CAUTION:
1. DISCONNECT ALL POWER BEFORE INSTALLATION.
2. ALL WIRING TO BE PERFORMED BY QUALIFIED
PERSONNEL TO COMPLY WITH ALL APPLICABLE
LOCAL CODES.
3. MAXIMUM WIRE SIZE IS 18 AWG.
Left Hand Shown
Right Hand Shown
1
Use template on page 4. Drill and tap door for 12-24 machine screws and frame for 1/4-20 machine screws.
Prepare hole for conduit.
Do not drill through channel, as damage will occur voiding warranty.
LH
2
3
4
Install closer body to door with spring
power nut away from hinge.
Following local codes, attach cable or conduit to track. Secure
track to frame with electronics away from hinge with screws
provided.
Wire unit as shown on Page 3; install cover as shown.
With wrench on bottom spindle, rotate spindle approximately 45°. Use screw and washer to secure main arm to
top spindle with index mark as shown.
L. H. Door
Hinge
Closer, spindle,
washer, and screw
Index mark
on spindle
45°
R. H. Door
Hinge
Closer, spindle,
washer, and screw
Index mark
on spindle
45°
NOTE: AN AUXILIARY DOOR STOP IS REQUIRED AT HOLD OPEN
®
2499
FIREGUARD
Closer-Holder Device
PUSH SIDE
INSTALLATION INSTRUCTIONS
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
1
Copyright © 2015, 2022, Sargent Manufacturing Company, an ASSA ABLOY
Group company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
A8198 Rev 4