RF4510: EXTERNAL  ANTENNA

Installation Directions

1. Prepare door jamb for hybrid electric strike per the appropriate 

template detail on page 5.  Be sure to allow enough room 

behind the strike in the cutout to avoid pinching any wires.

2. Drill a 1” diameter hole for the reader/antenna per the  

appropriate template detail on page 5.   The reader/antenna may

be positioned as desired, within the limits of the 24” cable.  (If 

necessary, drill a channel from the reader/antenna to the hybrid

electric strike to accomodate the 24” cable.)

3. Drill a 3/8” hole for the door position switch per the appropriate 

template detail on page 5.  The door position switch may be 

positioned as desired, within limits of its 10” connector.  If 

necessary, drill a channel from the door position switch to the

hybrid electric strike to accomodate the 10“ cable. .  Align and drill

a matching 3/8” hole in the door and install the press-fit magnet 

so that it will trigger the door position switch. 

4. If applicable (e.g. aluminum frames), install mounting tabs (sold 

separately as P/N 152) using #10-32 screws.  

 

9. Connect the 24” cable to the reader/antenna (check labels to 

insure that you connect the correct end). Then, install the 

reader/antenna in the frame, using the #6-32 screws provided. 

Snap on the reader/antenna cover and pull the 24”cable through 

to the hybrid electric strike.

10. Plug the loose end of the 24” cable into the connector on the

side of the hybrid electric strike.

Prepare Hybrid Electric Strike & Frame

11. Install the trim enhancer on the hybrid electric strike   

(see page 4) if needed, to cover any extra space.

12. Install the hybrid electric strike unit in jamb cutout, using 

#12-24 screws provided.

13. If needed, see page 4 to make horizontal adjustments in 

frame .

14. If applicable, tighten the #10-32 screws holding the 

mounting tabs.

Finish Installing

15. When power is supplied to the hybrid electric strike, the LED 

will flash green three times, while the beeper simultaneously 

beeps. The LED will then turn red. This sequence indicates that the 

micro-controller is operating properly.

16.  Present a Proximity ID card to the reader/antenna. The LED will 

turn green, while the beeper beeps once. This indicates that the 

card was read successfully.

17. Simultaneously, the keeper will click open. This indicates that 

communication between the host and the hybrid electric strike is 

operational.

18. For further testing of communication with the host, consult the 

manual for the control panel or the site’s system administrator.

Testing and Operation

Connect Components and Wiring

Wire Gauge Diagram

Max. One-way Distance               Voltage Drop/100’               Recommended AWG
                  800’ 
                  500’ 
                  300’ 
                  200’ 
                  120’ 
            100’ or less

12VDC @ 240 mA

0.15
0.24
0.38
0.61
0.97
1.53

12 Gauge
14 Gauge
16 Gauge
18 Gauge
20 Gauge
22 Gauge

3

6. Verify that the wires running from the host control panel are of

adequate gauge (see Wire Gauge Diagram below).  Connect the

wire leads of the three pigtails provided to the host control panel 

wiring based on the wiring diagram on page 2 and the appropriate 

termination at the host control panel.

7. Mount the door position switch (DPS) into the frame.  Route the

10” cable back to the electric strike and connect it to the 2 pin 

connector coming out of the hybrid electric strike.  It does not 

matter which 2 pin connector is used.  The LBM & DPS are wired in 

series--a ‘closed’ electrical circuit depicts a closed door and extended 

latchbolt into the hybrid electric strike.

8. Attach the 8, 4 and 2 pin connectors at the hybrid electric strike

to the equivalent pigtail connectors routed from the host control

panel.  Dielectric grease should be applied to the pigtail electrical 

terminals if used in a humid environment

CAUTION! Before connecting any device at the installation site, verify that there is 12VDC input voltage using a multimeter.

Many power supplies and low voltage transformers operate at higher levels than listed.  Any input voltage outside the electrical

specifications outlined on page 1 may cause severe damage to the unit and will void the warranty.  This product contains

electrostatic sensitive components.  We recommend proper grounding techniques be observed during installation.

5. The appropriate Deadlatch Tab for the lockset being used with 

the hybrid electric (see page 4) should also be installed at this time 