ASSA Pando display reader
About ASSA Pando
ASSA Pando reader is a combination reader, supports both Hi-O protocol
and RS485-based protocols.
By default reads the Pando reader serial number on the cards but ASSA
recommends that readers configured for the sector reading to achieve a
higher level of security. The programming are made with a customer specific
Setup card. Mifare classic, Desfire card and iClass is supported.
Hi-O Installation
Hi-O devices are easy to install, all devices are connected in parallel and
just using four threads. Units of Hi-O bus usually gets its supply voltage from
the DAC 530II, DAC564II or LCU9101.
Connect the CAN bus the CAN-H and CAN-L and power out to the CAN bus
at the next two terminals in the DAC/LCU, +12 V and 0V.
Connect one or more ASSA Pando readers and motor lock and RTE buttons
to the CAN bus. Set the SIO bus address to 00 in the reader and set the
function selection 1 for in or out reader.
Installing Pando display on the SIO bus.
Connect the SIO bus to the A and B terminals and power supply to the
reader to + V and 0V connections (+24 V and 0V).
Set SIO bus address from 1-99, depending on which address is available on
the SIO bus.
Indications for Hi-O mode = SIO address 0
Green: Lights when the reader is uninitialized at
the Hi-O bus, Pando reader is not locked to a specific Hi-O bus.
Red: lights when Pando reader is locked to a specific
Hi-O bus, red indicates that the reader is locked and encrypted.
Indications for SIO mode address 1-99
Green: TX, Sending data
Red: RX, Receiving data
Table for the function selection via the keypad
Key
function
1
Inside/outside reader
On = Inside
Off = Outside
2
Key beep, beep when keystrokes and major &
minor signal at invalid/valid card.
3
Card beep, Beep at card read
4
Light ON, Keypad always lit.
5
Light Code, Keypad lit when the indication for
door code/PIN code is activated
Settings and addressing
Set Conf. Dip in the ON position
Then press the “A”
The menu lights up on the display
Switching function choices (Fx) On/Off by pressing the
respective number key.
F1 = Numeric Key 1, etc .
(See table for functions).
Then press the "B", to address.
Enter the address using the numeric keys.
Hi-O Address = 00
SIO bus Address 1-99
Press "B" to save
Set Conf. DIP to OFF
Restart the reader.
Change Address / Factory Reset of SIO connected
readers.
Set Conf. Dip in the ON position
Turn on the reader
Then press "B", to address.
To factory reset the communication key.
Needs to be done if the address changes or when you changed
the database on the server or starting over with an empty
database.
See ARX manual for more information.
o
Enter address 00 (Restores crypto key)
o
Press "B" to save (crypto key restored)
o
Then press "B" again, to address.
Enter the address 1-99
Set Conf. DIP to OFF
Press the "B" to save, (Readers restart)
Unlock a locked Hi-O reader.
Normally unlocks the reader through the DAC or the LCU that is connected to, but if you
need to unlock the reader without the DAC or the LCU it has been locked by using the
following steps.
Turn on the power to the reader.
Red LED illuminates solid, indicating that the reader is locked.
Turn Conf. DIP ON and OFF at one second intervals 6-8 times.
When the reader switches from red to green is it unlocked.
Configuration of sector reading
1.
Cut and connect the power to the reader, by lifting the “plug able” terminal and
putting it back.
2.
Green indication flashes for 90 seconds.
3.
Show the Setup card to the reader, before it stops flashing.
4.
The reader indicates that the programming is finished with a “chirp” and the
green indication is unlit.
5.
The reader is now programmed with the encryption keys of the site.
Note!
If a card presented to an ASSA Pando display reader doesn’t have encryption keys
corresponding with the reader the reader will not indicate that anything is wrong and the
reader will not send any data.
Technical specifications
Power supply
12-24V DC
Power Consumption
12V: 65 mA Max 130mA
Recommended cable
EKKX 2x2x0,2
Hi-O Cable length
Total:
Max. 50 m
Branch:
Max. 10 m
Dimensions
H 185 mm, W 69 mm, D 22 mm.
Terminal
CH
Can H
Connection to the Hi-O bus (DIP6 = ON)
LCU9101, DAC530II or DAC564II
CL
Can L
+V
+ V (12-24 DC)
Power to the reader.
0V
0V
A
RS485
Connecting to ASSA SIO bus (RS485)
B
RS485
NC
Free
Termination
If the reader is finally on the SIO bus, the termination shall be activated.
Set DIP 2 "Term" in the ON position.
IS559686940C