13
E N G L I S H
ASPIRCOMFORT PRO X 380V
2.3 CONDENSATE DISCHARGE CONNECTION
Due to the cooling system, the condensate discharge pipe (Ø16mm internal not supplied) must be connected to
the pipe at the rear of the unit. For this reason, it is essential that the discharge line has a minimum slope of at
least 3% at each point. The tube to be used can be rigid or flexible with a minimum internal diameter of 16 mm. If
the line enters a sewage system, siphoning must be carried out before the pipe enters the main discharge. This
siphon must be at least 300 mm below the inlet of the appliance.
If the drainage line flows into a container (tank or other), it must be ensured that the container is hermetically
sealed and above all that the drainage pipe does not remain immersed in water.
The hole for the condensate pipe must always have an outward slope.
The exact position of the pipe opening in relation to the machine is defined on the drilling template.
Take care in this case that the water expelled does not cause damage or inconvenience to property or persons.
During the winter period this water can cause ice sheets to form outside.
When connecting the condensate discharge, take care not to crush the rubber hose.
If necessary, the condensate tray can be emptied through a safety drain on the base of the appliance.
N.B.: for the installation of the condensation discharge pipe towards the outside, it is recommended to cover the
internal pipe supplied with the appliance with anti-condensation insulation with an internal diameter of 10 mm
(see ref. 2 in the figure).
The insulation must be inserted up to the mouth of the external condensate discharge pipe embedded in the wall.
1 - Safety drain for emptying the water tray
2 - Condensate discharge pipe