OM00020 Rev 2, FP00091, FP00101 Operation Manual
Page
8
of
15
Figure 7: RMC Pressure/ Flow Curve
The RMC is equipped with a bypass valve to prevent the pump from generating excessive pressures. The
bypass valve begins to crack around 4.0 bar (58 psig). The bypass valve will prevent the system (and
external components) from seeing pressures greater than 6.9 bar (100 psig). This valve will open at a
lower differential pressure, as there is pressure drop in the system return line.
Controller Interface
The RMC is equipped with a controller, which monitors and controls the system. The primary interface
of the system is shown in Figure 8 below.
Figure 8: Controller Interface
During normal operation the controller displays the symbols showing the compressor, fan and pump are
operating. The display also shows the coolant temperature and the compressor speed signal (0
–
100%).
These are displayed in Figure 8.
During normal operation if the user presses the
button, the controller will display the setpoint
temperature.
Primary Functionality
Below are some of the critical functions of the RMC. Additional functionality can be accessed in the
parameter tree.
Changing the Setpoint
To change the setpoint, the user must do the following:
Press
.