RS485 MODBUS Module 8AI
User Manual
Modbus Dec
Hex
Register Name
Access
Description
+256 – output set if value is greater than alarm value
(40065 register) („cooling”)
+512 – output set if value is below than alarm value
(40065 register) („warming”)
40064
63
0x3F Alarm value
Read & Write
Alarm value
40065
64
0x40 Alarm hysteresis
Read & Write
Hysteresis for alarm
7.2. Bit access
Modbus
Address
Dec
Address
Hex
Address
Register name
Access
Description
801
800
0x320
Voltage input
Read
Voltage input state
802
801
0x321
Current input
Read
Current input state
817
816
0x330
Voltage alarm
Read & Write
Voltage alarm state
818
817
0x331
Current alarm
Read & Write
Current alarm state
819
818
0x332
Digital output
Read & Write
Digital output state
Expansion Module – 1 analog input, 1 digital output
User Manual
Version 1.3
10 / 12