Aspar 8I8O Скачать руководство пользователя страница 15

SDM-8I8O

User Manual

Modbus

Dec

Hex

Register Name

Access

Description

40085

84

0x54 CCounter 1 LSB

Read & Write

32-bit value of captured counter  1

40086

85

0x55 CCounter 1 MSB

Read & Write

40087

86

0x56 CCounter 2 LSB

Read & Write

32-bit value of captured counter  2

40088

87

0x57 CCounter 2 MSB

Read & Write

40089

88

0x58 CCounter 3 LSB

Read & Write

32-bit value of captured counter  3

40090

89

0x59 CCounter 3 MSB

Read & Write

40091

90

0x5A CCounter 4 LSB

Read & Write

32-bit value of captured counter  4

40092

91

0x5B CCounter 4 MSB

Read & Write

40093

92

0x5C CCounter 5 LSB

Read & Write

32-bit value of captured counter  5

40094

93

0x5D CCounter 5 MSB

Read & Write

40095

94

0x5E CCounter 6 LSB

Read & Write

32-bit value of captured counter  6

40096

95

0x5F CCounter 6 MSB

Read & Write

40097

96

0x60 CCounter 7 LSB

Read & Write

32-bit value of captured counter  7

40098

97

0x61 CCounter 7 MSB

Read & Write

40099

98

0x62 CCounter 8 LSB

Read & Write

32-bit value of captured counter  8

40100

99

0x63 CCounter 8 MSB

Read & Write

40117

116

0x74 Counter Config 1

Read & Write

Counter Configuration

+1 – time measurement (if 0 counting 
impulses)
+2 – autocatch counter every 1 sec
+4 – catch value when input low
+8 – reset counter after catch
+16 – reset counter if input low
+32 – encoder (only for counter 1 and 3)

40118

117

0x75 Counter Config 2

Read & Write

40119

118

0x76 Counter Config 3

Read & Write

40120

119

0x77 Counter Config 4

Read & Write

40121

120

0x78 Counter Config 5

Read & Write

40122

121

0x79 Counter Config 6

Read & Write

40123

122

0x7A Counter Config 7

Read & Write

40124

123

0x7B Counter Config 8

Read & Write

40133

132

0x84 Catch

Read & Write

Catch counter

40134

133

0x85 Status

Read & Write

Captured counter

Expansion Module – 8 digital inputs, 8 digital outputs

User Manual

Version 1.3

15 z 18

Содержание 8I8O

Страница 1: ...SDM 8I8O Expansion Module 8 digital inputs 8 digital outputs Version 1 3 User Manual Manufactured for...

Страница 2: ...by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law This information does not release you from the obligation of own judg...

Страница 3: ...N2 and IN3 and IN4 can be used to connect two encoders All inputs and outputs are isolated from the logic of using optocouplers Each channel can be individually configured in one of several modes This...

Страница 4: ...30V Max current 500mA Output Type PNP Output protection 4A polymer fuse Isolation 1500 Vrms Counters No 8 Resolution 32 bity Frequency 1kHz max Impulse Width 500 s min Temperature Work 10 C 50 C Stor...

Страница 5: ...rectly to the rail in the DIN industry standard Power connectors communication and IOs are at the bottom and top of the module USB connector configuration and indicators located on the front of the mo...

Страница 6: ...es and their cross sections 3 2 Network Termination Transmission line effects often present a problem on data communication networks These problems include reflections and signal attenuation To elimin...

Страница 7: ...DBUS RTU or MODBUS ASCII 3 5 1 Default settings You can restore the default configuration by the switch SW8 see 3 5 2 Restore the default configuration Boud rate 19200 Pariti Nie Data bits 8 Stop bits...

Страница 8: ...00 other value 10 40005 4 0x04 Parity 0 none 1 odd 2 even 3 always 1 4 always 0 40004 3 0x03 Stop Bits LSB 1 one stop bit 2 two stop bit 40004 3 0x03 Data Bits MSB 7 7 data bits 8 8 data bits 40006 5...

Страница 9: ...ss 2 3 Module address 4 4 Module address 8 5 Module address 16 6 Module address 32 7 Module address 64 8 Restoring default settings Restoring default settings see 3 5 1 Default settings i 3 5 2 Restor...

Страница 10: ...removing To remove the panel and gain access to the switch you must pry open the panel using a thin tool eg a small screwdriver as in the picture below Expansion Module 8 digital inputs 8 digital outp...

Страница 11: ...it received the correct packet and sends the answer Inputs state LED indicates that the signal to input is connected Outputs state LED indicates that the output is on Expansion Module 8 digital inputs...

Страница 12: ...SDM 8I8O User Manual 7 Module Connection Expansion Module 8 digital inputs 8 digital outputs User Manual Version 1 3 12 z 18...

Страница 13: ...SDM 8I8O User Manual Expansion Module 8 digital inputs 8 digital outputs User Manual Version 1 3 13 z 18...

Страница 14: ...ct packets MSB Read Write 40037 36 0x24 Sent packets LSB Read Write No of sent packets 40038 37 0x25 Sent packets MSB Read Write 30051 50 0x32 Inputs Read Inputs state 40052 51 0x33 Outputs Read Write...

Страница 15: ...6 0x60 CCounter 7 LSB Read Write 32 bit value of captured counter 7 40098 97 0x61 CCounter 7 MSB Read Write 40099 98 0x62 CCounter 8 LSB Read Write 32 bit value of captured counter 8 40100 99 0x63 CCo...

Страница 16: ...ate 10805 804 0x324 Input 5 Read Input 5 state 10806 805 0x325 Input 6 Read Input 6 state 10807 806 0x326 Input 7 Read Input 7 state 10808 807 0x327 Input 8 Read Input 8 state 817 816 0x330 Output 1 R...

Страница 17: ...Read Write Captured value of counter 3 2132 2131 0x84B Captured 4 Read Write Captured value of counter 4 2133 2132 0x84C Captured 5 Read Write Captured value of counter 5 2134 2133 0x84D Captured 6 Re...

Страница 18: ...r registers of the module This program can be a convenient way to test the system as well as to observe real time changes in the registers Communication with the module is done via the USB cable The m...

Страница 19: ...odbus Registers 7 3 5 Communication settings 7 3 5 1 Default settings 7 3 5 2 Restore the default configuration 7 3 5 3 Configuration registers 8 4 Switches 9 5 Front panel removing 10 6 Indicators 11...

Отзывы: