![Aspar 8I8O Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/aspar/8i8o/8i8o_user-manual_2984696015.webp)
SDM-8I8O
User Manual
Modbus
Dec
Hex
Register Name
Access
Description
40085
84
0x54 CCounter 1 LSB
Read & Write
32-bit value of captured counter 1
40086
85
0x55 CCounter 1 MSB
Read & Write
40087
86
0x56 CCounter 2 LSB
Read & Write
32-bit value of captured counter 2
40088
87
0x57 CCounter 2 MSB
Read & Write
40089
88
0x58 CCounter 3 LSB
Read & Write
32-bit value of captured counter 3
40090
89
0x59 CCounter 3 MSB
Read & Write
40091
90
0x5A CCounter 4 LSB
Read & Write
32-bit value of captured counter 4
40092
91
0x5B CCounter 4 MSB
Read & Write
40093
92
0x5C CCounter 5 LSB
Read & Write
32-bit value of captured counter 5
40094
93
0x5D CCounter 5 MSB
Read & Write
40095
94
0x5E CCounter 6 LSB
Read & Write
32-bit value of captured counter 6
40096
95
0x5F CCounter 6 MSB
Read & Write
40097
96
0x60 CCounter 7 LSB
Read & Write
32-bit value of captured counter 7
40098
97
0x61 CCounter 7 MSB
Read & Write
40099
98
0x62 CCounter 8 LSB
Read & Write
32-bit value of captured counter 8
40100
99
0x63 CCounter 8 MSB
Read & Write
40117
116
0x74 Counter Config 1
Read & Write
Counter Configuration
+1 – time measurement (if 0 counting
impulses)
+2 – autocatch counter every 1 sec
+4 – catch value when input low
+8 – reset counter after catch
+16 – reset counter if input low
+32 – encoder (only for counter 1 and 3)
40118
117
0x75 Counter Config 2
Read & Write
40119
118
0x76 Counter Config 3
Read & Write
40120
119
0x77 Counter Config 4
Read & Write
40121
120
0x78 Counter Config 5
Read & Write
40122
121
0x79 Counter Config 6
Read & Write
40123
122
0x7A Counter Config 7
Read & Write
40124
123
0x7B Counter Config 8
Read & Write
40133
132
0x84 Catch
Read & Write
Catch counter
40134
133
0x85 Status
Read & Write
Captured counter
Expansion Module – 8 digital inputs, 8 digital outputs
User Manual
Version 1.3
15 z 18